2.3 

DC Input Connections 

Before making any of the DC output connections, make sure you read and fully understand the DC Connection 
Procedure on the following page. Select proper size for the DC wires using the table below. Refer to Appendix A 

for the DC input current draws at full load capacity. This is

 

based on an overload 

current of 110-115%

 of the 

input current listed on the inverter nameplate. If the distance between the 

inverter’s DC in

put and the battery 

exceeds 10 feet, use the Power Wiring Guide in Appendix B to minimize the voltage drop across the wire distance.  

 

WARNING:

 Before beginning any work inside the inverter, ensure that all incoming AC/DC power is 

de-energized and/or isolated. Verify that no voltage is present inside the case by using a voltmeter at 

all input and output terminals. Assure the inverter that is being used is the same number and type of 
cell as the inverter front nameplate specifications.

  

 

The FT inverter DC terminal bolts accept a 5/16”

 or M8 ring terminal stud size. 

 

NOTE:

 It is recommended to use a battery disconnect breaker between inverter and battery bank; helpful during 

battery or inverter maintenance. The breaker/disconnect should be sized with consideration of the full load DC 

input current of the inverter. Refer to Appendix A for the DC input current draws at full load capacity. 

 

Breaker Size/ 

Fuse Size (Amps) 

Minimum AC/DC Wire 

Size Requirement 

Equipment Grounding 

Conductor Minimum 

25 

#10 

#12 

30 

#10 

#10 

40 

#8  

#10 

50 

#8 

#10 

60 

#6  

#10 

70 

#6  

#8 

80 

#4 

#8 

90 

#4 

#8 

100 

#4 

#8 

125 

#2 

#6 

150 

#1 

#6 

175 

#1/0 

#6 

200 

#2/0 

#6 

250 

#4/0  

#4 

300 

250 MCM  

#4 

 

Table 2 

 AC/DC & Ground Wire Size Minimum Requirements 

(All wires specified in the table are rated at 90 °C or 194 °F) 

 

NOTE:

 These are recommended sizes per La Marche Standards. The National Electrical Code (NEC) and Local 

Wiring Codes must be followed. 

 

 

DC Connection Procedure 

The battery connections should be done in the following order: 

 

1.

 

Assure that the incoming AC mains input power to the inverter is turned off. 

2.

 

Check polarity of DC input cables and verify with multimeter. 

3.

 

Connect  the  positive  DC  input  cable  to  the  positive  terminal  and  the  negative  DC  input  cable  to  the 
negative terminal. 

OBSERVE PROPER POLARITY

 
 

 

Summary of Contents for FT Series

Page 1: ...9 1188 Fax 847 299 3061 Revision A00 Rev Date 05 21 ECN 22891 This manual is subject to change without notice You may obtain the newest version of the manual at www lamarchemfg com La Marche Manufactu...

Page 2: ...sure that neither liquids nor any wet material come in contact with any internal components Do not operate this unit outside the input and output ratings listed on the unit nameplate Do not use this u...

Page 3: ...rter sent back for evaluation and repair CAUTION Failure to properly file a claim for shipping damages or provide a copy of the claim to La Marche may void warranty service for any physical damages re...

Page 4: ...llation 2 2 1 Mounting the FT Series Inverter 2 2 1 1 Wall Mounting the FT Series Inverter 2 2 2 FT Series Inverter Overview 3 2 3 DC Input Connections 4 2 4 AC Output AC Input Connections 5 2 5 Alarm...

Page 5: ...ries model number is coded to describe the features that are included Find the model number on the nomenclature nameplate of the enclosure Follow the chart below to determine the configuration of the...

Page 6: ...mounting the FT Series Inverter consider the size and weight of the inverter The FT Series Inverter is wall mounting system Refer to Table 1 to verify the weight of the inverter The location chosen f...

Page 7: ...iew 251 Enclosure DC Terminal DC Terminal GND Terminal DC Terminal DC Terminal GND Terminal GND Terminal AC Input N AC Input L AC Output N AC Output L GND Terminal Inverter AC Output Breaker Charger A...

Page 8: ...rminal stud size NOTE It is recommended to use a battery disconnect breaker between inverter and battery bank helpful during battery or inverter maintenance The breaker disconnect should be sized with...

Page 9: ...es 2 5 Alarms The FT series inverter has an audible buzzer alarm which activates depending on the status of the inverter Below are the available alarms status indicators Load Powered by Battery Beeps...

Page 10: ...the output voltage Power Down Sequence To power down the FT inverter simply press the ON OFF button while the screen is on The inverter s display should turn off and the output voltage should decrease...

Page 11: ...eter AC Output Voltage Meter Equipment Operating Mode Selection Grid Priority Mode Energy Saving Mode Battery Priority Mode Operating Mode can be entered by long pressing the Function button for secon...

Page 12: ...restarting the inverter Up Charge Current Menu Long press for 5 seconds Charge Current Selection Charger Output Current LCD icon will display active Charge Current Select Using C0 C1 C2 C3 C4 C5 C6 0...

Page 13: ...battery When the battery is connected to the external charging device like solar charging system after adequate power charged inverter will automatically switch to battery mode through internal relay...

Page 14: ...0VAC 5 Inverter Mode Frequency 50 60Hz 1 Inverter Mode Output Current 230VAC Model 4 5A 9 1A 13 6A 18 2A 22 7A 27 3A 36 3A Output Current 110VAC Model 9 1A 18 2A 27 2A 36 4A 45 2A 54 6A 72 7A Output W...

Page 15: ...loop feet MaxAmp Maximum allowable amperes for given voltage drop AVD Allowable voltage drop K 11 1 for commercial TW copper wire 17 4 for aluminum Calculating Wire Size Requirements AVD K LF A CMA Ca...

Page 16: ...12 Appendix C Example Wiring Diagram Battery Connections 12VDC Series Battery Wiring 24VDC Series Battery Wiring 48VDC Series Battery Wiring AC Mains Input AC Output Connections AC Loads Mains Supply...

Page 17: ...ion adjustments and service arrangements Should minor adjustments be required the local La Marche Sales Representative should be contacted to provide this service All sales are final Only standard La...

Page 18: ...14 Appendix E Document Control and Revision History Part Number 144911 Instruction Number P25 LFT 1 Issue ECN 22891 05 21...

Reviews: