background image

1.2 

Electrical Connections 

Before beginning installation of electrical connections, ensure that all sources (AC & DC) are de-energized; verify 
that no voltage is present on the field wiring by using a voltmeter.  Check that the source voltage and frequency 
match the 

charger’s

 specifications. Select field wire size using Table 1 below. 

Wire terminal table 

AC Input Terminal 
Line-1, GND, N/L2 

DC Output Terminal 

Pos & Neg 

Remote Temperature 

Probe 

+ + & - - 

Minimum 

Recommended 

Wire Size * 

18Ga 

14Ga 

Optional accessory supplied 

by La Marche.  Temp probe 

includes correct wire size, 

pre-crimped ferrules, and is 

marked (+ + & - -) 

Range of wire sizes 

which fit the LMESpro 

push-in spring terminals 

18ga 

 14Ga stripped 

18ga 

 14Ga w/ferrule 

14Ga 

 8Ga stripped 

14Ga 

 10Ga w/ferrule 

Wire Strip Length 

(Inch”/mm)

 

0.4” / 10mm

 

0.6” / 15mm

 

Table 1 

 AC/DC & Ground Wire Size Minimum Requirements  

(All wires specified in the table are copper rated at 90 °C or 194 °F) 

*

 NOTE:

 These are minimum recommended sizes per La Marche Standards. The National Electrical Code (NEC) 

and Local Wiring Codes must be followed.

The LMESpro utilizes spring-loaded push-in style connectors.  It is recommended to use wire crimp ferrules on 
the AC & DC field wiring when installing the charger, however it is not absolutely necessary.  Crimp ferrules will 

prevent wire strands from fraying near the connectors.  Being spring-loaded, the connectors are highly resistant 
to vibration and do not require periodic torque checks as with a screw-terminal.  See Figure-2.   

To connect field wiring, you can simply push in the prepared conductors until fully seated.  To make the wires 
easy to push-in, you may insert a small flat-head screwdriver tip into the rectangular opening  above the wire 

entry to relieve spring-tension on the wire connection.    

Figure 3 - Wire installation 

To remove a wire connection (on a completely de-energized system AC & DC), insert a small screwdriver tip in 

the rectangular opening above the wire to release spring pressure, then pull the wire out.  See Figure 3. 

Summary of Contents for LMES Pro

Page 1: ...w lamarchemfg com 106 Bradrock Dr Des Plaines IL 60018 1967 CPN 144074 Instruction Drawing Number P25 LLMESP 01 Tel 847 299 1188 Fax 847 299 3061 Revision A00 Rev Date 03 21 ECN 22774 La Marche Manufacturing Company www lamarchemfg com LMESpro Smart Battery HCAP Charger Installation and Operation Manual ...

Page 2: ...tact with any internal components Do not operate this unit outside the input and output ratings listed on the unit nameplate Do not use this unit for any purpose not described in the operation manual Mechanical Safety This unit or parts of the unit may get very hot during normal operation use care when working nearby Do not expose equipment to rain or snow Always install in a clean dry location Do...

Page 3: ...y that you have all the necessary parts as per your order for proper assembly CAUTION Failure to properly file a claim for shipping damages or provide a copy of the claim to La Marche may void warranty service for any physical damages reported for repair Returns for Service Save the original shipping container If the product needs to be returned for service it should be packaged in its original sh...

Page 4: ...l Connections 4 1 2 1 AC Input Connections 5 1 2 2 DC Output Connections 6 1 2 3 Remote Temperature Probe Connection 6 2 Operation 7 2 1 Initial Setup 7 2 2 DIP Switch Settings 7 2 3 Lead Acid Four Stage Charge Curve 8 2 4 HCAP Four Stage Charge Curve 9 2 5 Indication Details 10 2 6 Fault Indications and Alarms 10 2 7 Reset Button 11 3 Service 12 3 1 User Serviceable Parts 12 3 2 Performing Routin...

Page 5: ...l AC Input and the output is selectable for either 12 VDC or 24 VDC Understanding the Model Number The LMESpro model number is coded to describe the options that are included Find the model number on the nomenclature nameplate of the charger Follow the chart to determine the configuration of your battery charger Optional Accessories Included in the Charger This charger may have been outfitted with...

Page 6: ... the temperature to prolong the life of the battery or HCAP The charger also detects an open or shorted external probe When the temperature probe is not connected or defective temperature compensation is disabled High DC Protection If 24V DC battery is connected to the charger when 12V mode is selected it will shut down in High DC protection No damage will occur to the charger Output Short Circuit...

Page 7: ...n an upright position as shown in Figure 1 to promote convection air flow Provide clearance for at least 6in 152mm of free air must be maintained on the left right sides and at least 6 152mm top bottom sides for cooling Maintain 36in 914mm or more of clearance at the front of the charger in order to allow for operation and maintenance Install the LMESpro using appropriate hardware on the wall When...

Page 8: ...at 90 C or 194 F NOTE These are minimum recommended sizes per La Marche Standards The National Electrical Code NEC and Local Wiring Codes must be followed The LMESpro utilizes spring loaded push in style connectors It is recommended to use wire crimp ferrules on the AC DC field wiring when installing the charger however it is not absolutely necessary Crimp ferrules will prevent wire strands from f...

Page 9: ...s For AC Terminal location refer to Figure 5 For AC systems with a line and neutral such as 120Vac service in North America connect Line to the L neutral to the N For AC systems with 2 hot leads or Line 1 Line 2 such as 240Vac service in North America connect Line 1 to L Line 2 to N All installations require the Ground terminal to be connected to the AC service Ground Earth wire All installations ...

Page 10: ...terminal is connected to the negative battery terminal CAUTION Do not touch the charger while it is in operation or just after de energizing the charger as the LMESpro heat sink can become very hot during operation 1 2 3 Remote Temperature Probe Connection It is recommended to use temperature compensated charging with Lead Acid HCAPS especially in environments having a wide temperature range La Ma...

Page 11: ...of the wires pull out of the connector Read section 2 for Initial Setup to set the DIP switches to match the Battery HCAP Read and understand all safety precautions in the manual Apply AC power to the input terminals of the LMESpro to start up the charger after setting the DIP switches for the desired application per 2 2 2 2 DIP Switch Settings The LMESpro output can be configured to account for v...

Page 12: ...e than 90 seconds Provides full current until the battery reaches 102 of its absorption voltage reference Absorption When the battery has recharged to the Absorption voltage level constant voltage regulation is used to prevent heating and excessive battery gassing The charger will hold the absorption voltage mode until the battery is determined to be fully charged The absorption mode detects the f...

Page 13: ...ates to the Bulk Charge mode Note in most applications the HCAP wouldn t regularly be discharged to a voltage that would invoke operating in the Pre Conditioning mode Bulk Charge In this stage the HCAP voltage has not yet reached the Absorption voltage and 100 of rated current is used to recharge the HCAP The LMESpro provides full rated constant current until the HCAP reaches the Absorption voltag...

Page 14: ...ion No damage will occur to the charger The charger will restore its output once it reaches the recovery voltage Refer to the table below for the high DC voltage shutdown and recovery voltages Charger Mode Selected High DC Shutdown Voltage High DC Recovery Voltage 12V 15 3V 14V 24V 30 6V 28V Table 4 High DC Output Alarm Thresholds OUTPUT LOW DC When the battery HCAP drops below 6V for a 12V system...

Page 15: ...pt Invoke a reset by pressing the Reset Button for 0 5 seconds Example If an output short circuit is detected the charger will protect itself see section 2 6 Output Short Circuit Every few minutes the charger will automatically attempt to restart If the short is still present the charger will continue to attempt restart every few minutes and only fully restore output when the short circuit is remo...

Page 16: ...that the AC power is off Disconnect the battery HCAP from the charger Verify that no voltage is present by using a voltmeter at all input and output terminals 3 1 User Serviceable Parts Other than the AC DC fuses there are no user serviceable parts within the LMESpro Only replace fuses with the same current and voltage ratings never substitute a larger ampacity See Figure 13 Figure 13 Location of ...

Page 17: ...k unit specifications against customer order 3 Check AC input connection and verify the AC supply measures within the specified range 4 Measure AC voltage if power outage occurred 5 Check for shipping damage loose connections broken wires etc 6 Certain failures can be caused by defective batteries make sure batteries are free from defects 7 If the red Fault LED is illuminated try using the Reset b...

Page 18: ...ge Status Flashing Green for Bulk Solid Green for Float User Programmable Settings 1 12 24 Volt Output 2 Battery type or HCAP Ambient Operating Temp 40 C to 50 C Derate 70 C internal shutdown 85 C internal Storage Temp Range 40 C to 70 C Protections Output Overcurrent Output Short Circuit Output Reverse Polarity AC Fuse Internal DC Fuse Internal Thermal Protection Transient overvoltage protection ...

Page 19: ...minum Calculating Wire Size Requirements AVD K LF A CMA Calculating Current Carrying Capacity of Wire Table 5 Wire Size Area Table K LF AVD CMA MaxAmp Example If the charger being used has a max ampere output of 33A and 30 loop feet of copper wire cable is required with an allowable voltage drop of 0 5Volts the wire size calculation will be AVD K LF A CMA A 30 LF 30 K 11 1 AV 0 5 5 0 1 11 30 33 CM...

Page 20: ...ansportation cost is required prior to the deployment of the service representative In accepting delivery of the equipment the purchaser assumes full responsibility for proper installation installation adjustments and service arrangements Should minor adjustments be required the local La Marche sales representative should be contacted to provide this service only All sales are final Only standard ...

Page 21: ...17 Appendix D Document Control and Revision History Part Number 144074 Instruction Number P25 LLMESP 01 Issue ECN 22774 22774 03 21 ...

Reviews: