background image

INSTRUCTION MANUAL FOR PC63 CAGE 

Page 9 of 10 

 
 
 
 
 

General Maintenance Procedure 

 

Yearly

 

 
1.  Blow out rectifier/inverter with a low-pressure air hose. 
2.  Make sure all connections are tight. 
3.  Perform a visual check on all internal components. 
4.  Check front panel meters and alarms for accuracy. 
 
 

4th Year  

 

REPEAT ABOVE WITH THE ADDITION OF: 

 
1.  Check relay contacts for pitting or corrosion. 
2.  Check capacitors for leakage. 
 
 

7th Year 

 

REPEAT ALL, WITH THE ADDITION OF: 

 
1.  Filter, resonating capacitors and control relays should be replaced. 
 
 

10th Year 

 

REPEAT ALL WITH THE ADDITION OF: 

(except replacing capacitors and control relays, they should be replaced every 7 years) 

 
1.  Check magnetics, components and wiring for signs of excessive heat.  

 
 

Summary of Contents for PC63 Series

Page 1: ...OR PC63 CAGE Page 1 of 10 INSTRUCTION MANUAL FOR PC63 CAGE ECN DATE CPN106833 16816 6 05 106 BRADROCK DRIVE DES PLAINES IL 60018 847 299 1188 FAX 847 299 3061 ISSUE DATE 15689 12 02 INSTRUCTION DRAWIN...

Page 2: ...THE INSTRUCTIONS EXACTLY To reduce risk of battery explosion follow these instructions and those published by the battery manufacturer and manufacturer of any equipment you intend to use in the vicin...

Page 3: ...orrode and damage equipment A sealed maintenance free or valve regulated lead acid VRLA may be placed below this equipment Never allow the battery electrolyte to drip on this unit when reading the spe...

Page 4: ...to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for handling Unti...

Page 5: ...4V A63 24V A63 PC63 30 48V 130V 48V A63 48V A63 TPCD DISTRIBUTION CENTER PC63 60 24V 130V 24V A63 24V A63 TPCD DISTRIBUTION CENTER PC63 120 12V 130V 12V A63 12V A63 12V A63 12V A63 Input DC The A63 mo...

Page 6: ...ept a TPCD connect the negative wire from the battery must be connected to the terminal marked negative and the positive wire from the battery must be connected to the terminal marked positive on the...

Page 7: ...ENT CUSTOMER CONNECTION EQUIPMENT GROUNDING CONDUCTOR MINIMUM FUSE SIZE WIRE SIZE REQUIREMENT CUSTOMER CONNECTION EQUIPMENT GROUNDING CONDUCTOR MINIMUM 1 14 14 150 1 6 3 14 14 175 1 0 6 4 14 14 200 2...

Page 8: ...enotes all sizes larger than 0000 are expressed in MCM TABLE OF CONVENTIONS CMA Cross section of wire in circular MIL area A Ultimate drain in amperes LF Conductor loop feet MAX AMP Maximum allowable...

Page 9: ...ers and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH THE ADDITION OF 1 Filter...

Page 10: ...lity for proper installation installation adjustments and service arrangements Should minor adjustments be required the local La Marche Sales Representative should be contacted to provide this service...

Reviews: