The following features are FORBIDDEN and therefore
they endanger the good operation of the device:
asbestos cement, galvanized steel, rough and porous
internal surfaces. Picture 4 gives some examples of
execution.
The minimum section must be 4 dm
2
(for example 20
x 20 cm) for devices whose duct diameter is
lower than 200 mm or 6.25 dm
2
(for example 25 x 25
cm) for devices with diameter greater than 200
mm.
The draught created by the flue must be sufficient, but not
excessive.
A too big flue section can feature a too big volume to be
heated and consequently cause difficulties in the
operation of the device; to avoid this, tube the flue along
its whole height. A too small section causes a decrease of
the draught.
The flue must be properly spaced from any
flammable materials or fuels through a proper
insulation or an air cavity.
It is forbidden to let plant piping or air feeding channels
pass in the same flue. Moreover, it is forbidden to create
movable or fixed openings on the same for the
connection of further other devices.
6. CONNECTION TO THE CHIMNEY
For safety reasons the door of the appliances with constructive system 1, must be opened only for the loading
of the fuel or for removing the ashes, while during the operation and
the rest, the door of the hearth must
remain closed.
The appliances with constructive system 2 must be connected to their own flue. The operating with open door
is allowed under supervision. The connection pipe to the flue must be the shortest possible, right, tight and
according to the current regulations.
The connection to the chimney must be performed with stable and strong pipes (we recommend a thickness of
2 mm). The pipe for smokes exhaust must be fixed hermetically to the chimney. The diameter inside the
connection pipe must correspond to the external diameter of the smokes exhaust small trunk of the stove. This
is ensured by pipes according to DIN 1298.
ATTENTION: Eventual flammable pieces in the area of 20 cm round the connection pipes must be changed
with fireproof and not sensitive to heat materials.
For a good operation of the equipment it is essential that in the installation place it is introduced sufficient air
for combustion (see CHAPT. 10).
The depression on the chimney should be 12 - 14 Pa (=1.2-1.4 mm of water column). The measurement must
be done always with the equipment hot (rating calorific value). When the depression exceeds 17 PA (1.7mm of
water column) it is necessary to reduce the same with the installation of an additional flue adjuster (butterfly
valve) on the exhaust pipe or in the chimney.
For safety reasons the door of the stove must be opened only for the loading of the fuel or for removing the
ashes, while during the operation and
the rest, the door of the hearth must remain closed.
6.1. CHIMNEY CAP POSITION
The draught of the flue depends also on the suitability of the chimney cap.
Therefore, if it is handicraft constructed, the output section must be more than twice as big as the internal
section of the flue.
Should it be necessary to exceed the ridge of the roof, the chimney cap must assure the discharge also in
case of windy weather (Picture 5).
The chimney cap must meet the following requirements:
Picture 4
(1) AISI 316 steel flue with double chamber
insulated with material resistant to 400°C.
Efficiency 100% excellent.
(2) Refractory flue with double insulated chamber
and external coating in lightweight concrete.
Efficiency 100% excellent.
(3) Traditional clay flue square section with
cavities. Efficiency 80% excellent.
(4) Avoid flues with rectangular internal section
whose ratio differs from the drawing. Efficiency
40% poor.
A+1/2A
A
Max.
A+1/2A
(3)
(1)
(2)
(4)
Summary of Contents for ANTHEA
Page 2: ...ANTHEA VENERE 2 7194201 Rev 06 IT EN DE FR...
Page 53: ...ANTHEA VENERE 7194201 Rev 06 IT EN DE FR 53...
Page 54: ...ANTHEA VENERE 54 7194201 Rev 06 IT EN DE FR...
Page 55: ...ANTHEA VENERE 7194201 Rev 06 IT EN DE FR 55...
Page 56: ...ANTHEA VENERE 56 7194201 Rev 06 IT EN DE FR 10 x 10 x...
Page 57: ...ANTHEA VENERE 7194201 Rev 06 IT EN DE FR 57...
Page 59: ...ANTHEA VENERE 7194201 Rev 06 IT EN DE FR 59...
Page 60: ...ANTHEA VENERE 60 7194201 Rev 06 IT EN DE FR...
Page 61: ...ANTHEA VENERE 7194201 Rev 06 IT EN DE FR 61...
Page 62: ...ANTHEA VENERE 62 7194201 Rev 06 IT EN DE FR...
Page 64: ...ANTHEA VENERE 64 7194201 Rev 06 IT EN DE FR ANTHEA Verticale...
Page 65: ...ANTHEA VENERE 7194201 Rev 06 IT EN DE FR 65 VENERE...