Page 6
2.2
Specifications
Model Name
FTCF140
Gas Input Rate
MAX
140,000 Btu/h
MIN
28,000 Btu/h
Hot Water Capacity
35°F
Rise
7.1 Gal
45°F
Rise
5.5 Gal
77°F
Rise
3.2 Gal
Installation
Indoor / Floor stand type
Flue System
Sealed Combustion Direct / Single / Concentric Vent/ SideWall Vent
Vent Run
2"(50ft) , 3"(100ft) Schedule 40 CPVC, PP
Gas Supply Pressure
NG
3.5" WC to 10.5" WC
LP
8.0" WC to 13" WC
Manifold Pressure
Gas Type
LP
NG
Vent size
2" VENT
3" VENT
2" VENT
3" VENT
FTCF140
Min fire
-0.15" WC
-0.216" WC
-0.15" WC
-0.216" WC
Low fire
0.1" WC
0.079" WC
0
" WC
0.002" WC
Power Supply
Main Supply
120V 60Hz / 6A
Maximum Power
Consumption
160W
Ignition System
Direct Electronic Ignition / Automatic Flame Sensing
Burner System
Single Orifice Premixed Fuel Modulation
Ceramic Infrared
Gas Valve System
Combination modulating (Current proportional)
Minimum Flow Rate
0.5 GPM
Dimensions
W15.7" - H52.4" – D26.7"
Shipping Weight
230 lbs (
104 kg
)
Sub Heat Exchanger Water Capacity(DHW)
Under 15 Gallon
Main Controller / Control Panel
GTX-920CP / P-920C
Water Pressure
Min 15 ~ Max 150 PSI
Connection Sizes
Cold Water Inlet / Hot
Water Outlet
3/4" NPT
Space Heating
Supply / Return
1" NPT
Gas Inlet
1/2" NPT
Materials
Casing
Cold Rolled Carbon Steel
Heat Exchanger
Primary Heat Exchanger : Stainless Steel
Sub Heat Exchanger : Stainless Steel
Safety Devices
Flame Rod, Overheat Cut Off Device, Gas Valve Operation
Detector, Exhaust Temperature High Limit Switch, Water
Temperature High Limit Switch
800.900.9276
•
Fax 800.559.1583
(Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
Fax 603.335.3355
(Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
•
Fax 905.366.0130
www.Laars.com
Document 4290B
The FT Series, Floor-Standing, Gas Conversion Kit
pg 3 of 4
Manifold pressure
‘NG’ type combustibility
‘LP’ type combustibility
2" VENT
3" VENT
2" VENT
3" VENT
FTCF140
MAX Fire
-0.15
"
WC
-0.216
"
WC
-0.15
"
WC
-0.216
"
WC
MIN Fire
0
”
WC
0.002
”
WC
0.1
”
WC
0.079
”
WC
FTCF199
MAX Fire
-0.134
”
WC
-0.173
”
WC
MIN Fire
-0.015
”
WC
-0.015
”
WC
Figure D
15.
Setup your combustion analyser and place the sensor
into the combustion test port
16.
Per
Table B for Max Fire
,
change dip switch 6 to ON and 7 to OFF.
The unit will cycle up to MAX fi re.
17.
WAIT for your combustion analyser to stabilize. This may take up to 3 minutes depending on your combustion
analyser. Then check the CO
2
measurement for MAX fi re. Refer to Table D for acceptable MAX fi re
combustion readings. At this point, just record the CO
2
readings at MAX Fire.
Do NOT attempt to adjust
CO2 at MAX Fire. ONLY in MIN Fire, so...
18.
Per
Table B for MIN Fire
,
change dip switch 6 to OFF and 7 to ON. The unit will cycle down to MIN Fire.
19.
WAIT for your combustion analyser to stabilize. Then check the CO
2
measurement at MIN fi re. Refer to
Table D for acceptable MIN fi re combustion readings.
20.
If CO2
readings in Max Fire and MIN fi re are acceptable, then skip ahead to Step 23. If not, then open the
Gas Valve Adjustment Port by removing the cap screw with a 4mm Allen wrench. See Figure E.
21.
Then use the 4 mm Allen wrench to make a minor adjustment (1/8 turn) to either increase or decrease CO
2
.
Table B
DIP Switch Settings
MBH N/A 140 N/A 199
ON
OFF
MIN
Fire
Normal Operation
MAX
Fire
Normal Operation
NG Natural
LP Propane
3” Vent Size
2” Vent Size
ON
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
DO
N
OT
C H
A N
G E
REFE
RENCE
ON
LY.
CO
2
value
‘NG’ type combustibility
‘LP’ type combustibility
2" VENT
3" VENT
2" VENT
3" VENT
FTCF140
MAX Fire
8.5~10.5%
9.5~11 %
MIN Fire
8~10%
9~10.5 %
FTCF199
MAX Fire
8.5~10.0%
9.5~11 %
MIN Fire
8~10%
9~10.5 %
Table C
Table D