The FT Series Floor Standing, Combination Boiler
Page 65
SECTION 6 Error Codes
Error
Code
Error Code
Description
Possible Remedies
Recover
methods
10
Flame has
Extinguished 8 (Eight)
Times
Press the Power button to clear the Error Code.
If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is
between 3.5 and 14” WC.
2. Check gas valve wire. Ensure connection is secure.
3. Check flame detection sensor. Ensure connections are secure. Normal operating
settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
4. Check vent terminations. Ensure there are no blockages.
5. Assure that the flame is stable when lit.
6. If the problem persists, replace the main control.
Hard
Lock
11
Ignition has Failed 10
(Ten) Times
Press the Power button to clear the Error Code.
If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is
between 3.5 and 14” WC.
2. Check gas valve wire. Ensure connection is secure.
3. Check flame detection sensor. Ensure connections are secure. Normal operating
settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
4. Check igniter transformer for proper connection.
5. Clean the spark igniter with steel wool to remove oxides. Ensure proper separation (3-4 mm).
6. Replace the spark igniter if damaged.
7. Assure that the flame is stable when lit.
8. If the problem persists, replace the main control.
Hard
Lock
16
Operating
Temperature Sensor
detects Water
Temperature Greater
than 203°F (95°C)
Press the Power button to clear the Error Code.
If Error happens again:
1. Check if dip switch Max Fire setting is ON. Switches 6 and 7 should be OFF for
normal operation.
2. Check if CH inlet pipe is blocked. Ensure there is enough water flowing to the
appliance.
3. Check Operating Temperature sensor at CH heat exchanger outlet. If resistance is
zero, replace the sensor.
4. If the problem persists, replace the main control
Hard
Lock
20
Condensate – Closed
is Normal, Open is
Fault (Condensate
Drain Trap)
Press the Power button to clear the Error Code.
1. Check Condensate and main controller connections. Ensure all are secure.
2. Check Condensate sensor resistance. If resistance is zero, replace the switch.
3. Check Condensate hose. Ensure it is connected and in good condition.
4. Check condensate line and termination for blockages.
5. Check Vent Pipe for blockages.
6. If the problem persists, replace the main control.
Hard
Lock
28
Overheat Sensor Open
or Short
This Error Code will go away when CH temperature decreases.
If Error happens again:
1. Check overheat temperature sensor. Ensure connections are secure.
2. Check overheat sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Soft Lock
30
DHW Storage
Temperature Sensor
Open or Short
This error Code will go away when outlet stroage temperature decreases.
If Error happens again:
1. Check stroage temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Soft Lock
32
DHW Sensor Open or
Short
This Error Code will go away when outlet DHW temperature decreases.
If Error happens again:
1. Check DHW outlet temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Soft Lock
33
CH Temperature
Sensor Open or Short
This Error Code will go away when CH temperature decreases.
If Error happens again:
1. Check CH temperature sensor. Ensure connections are secure.
2. Check CH sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Soft Lock
6.1
Error Code Tables