26
Combustion Blower Dip Switch Settings for Vent Length Compensation Under 22 Feet (6.7 m):
To assure optimum efficiency and reduced noise levels, the combustion blower switch has two dip switch
settings. Dip switch number 1 (top dip switch) is shipped from the factory set to the OFF position to
compensate for the maximum vent/air intake length.
Depending upon the vent/air intake length of the installation, Dip Switch Number 1 may need to be
adjusted to compensate for the venting system distance.
When the Equivalent Length of vent pipe, D, is more than 22 feet (6.7 m), leave the Dip Switch
Number 1 in the OFF position. This is the factory Dip Switch setting.
When the Equivalent Length of vent pipe, D, is 22 feet (6.7 m) or less, Dip Switch Number 1 must
be moved to the ON position.
Dip Switch #1 is located in the top row of dip switches, 1 through 8 on the PC board. See the following
diagram to identify the correct switch. If you do not understand the information concerning the Dip Switch
settings or the location of the Dip Switch, contact
Laars Service
(800-
900
-
9276
) or
T
echnical
Applications
(
603
-33
5
-
6300
) for assistance. Use the following examples and the previous discussion
on calculating the equivalent vent length to determine the correct setting for Dip Switch #1.
Example #1:
You have 6 feet (1.82 m) of vent pipe and two 90
°
elbows.
D = 6 + (2 x 6) + (0 x 1.5)
D = 18 feet (5.49 m) of equivalent vent pipe
Dip Switch #1 should be moved to ON position.
Example #2:
You have 15 feet (4.57 m) of vent pipe, one 90
°
elbow, and two 45
°
elbows.
D = 15 + (1 x 6) + (2 x 1.5)
D = 24 feet (7.3 m) of equivalent vent pipe
Leave Dip Switch #1 in the OFF position (factory setting).
WARNING
Do not alter Dip Switch #1 before using the formula and venting charts to determine the equivalent vent
length. All other dip switches with the exception of Dip Switch #1 shown in the illustration MUST NOT be
altered. Unauthorized adjustments can cause property damage, personal injury, scalding, or death.
Dip Switch Settings
Figure 11
Summary of Contents for IGI-180C-5N
Page 7: ...7 EVERHOT IGI Model Series Dimensions Figure 1...
Page 14: ...14 Recommended Piping for a Basic Installation Figure 2...
Page 15: ...15 Recommended Piping for a Circulation System Figure 3...
Page 35: ...35 Horizontal Vent System Installation examples Figure 36...
Page 38: ...38 Vertical Vent System Installation examples Figure 40...
Page 39: ...39 Cut Line Template Figure 41...
Page 44: ...44 Wiring Diagram Schematic Figure 43...
Page 59: ...59 Schematic Diagram of Internal Parts Figure 53...
Page 61: ...61 Internal Components...
Page 62: ...62 Internal Components...
Page 63: ...63 Electrical Components...
Page 67: ...67 NOTES...