User’s Manual - Mascot II Boilers and Water Heaters

Page 5

Figure 3. The User Interface.

The Mascot II has an integrated electronic control 

that replaces many of the individual component controls 

found on older appliances. The control acts as the 

ignition control, pump control, high limit and cascading/

lead lag control and more. All of these functions and 

setups are managed through the Digital Display.

3.1  Digital Display Navigation

The Digital Display is centered in the middle 

of the User Interface and has 3 seperate modes of 

control. They are USER, SETUP and DIAGNOSTIC. 

The names of these modes gives you an idea of the 

levels of control. A USER might be the homeowner or 

a service technician. SETUP displays all the controls 

needed when setting up or expanding the boiler. And 

DIAGNOSTIC is intended for a Mascot ll trained 

technician.  Please view 

Table 1, Table 2, and Table 3

 

         USER Mode is the home screen shown on the 

control. If the display is not in USER Mode wait for the 

display timeout period to be reached or press the Done 

button to return to the USER Mode.

SETUP Mode is accessed by holding the up and 

down arrow keys simultaneously for 3 seconds.

DIAGNOSTIC Mode can be activated by a trained 

Mascot II technician.

Once in a particular menu structure, navigation 

consists of pressing the next button to scroll from item 

to item and then pressing the up and down arrows to 

change values. Once the value is adjusted, the NEXT or 

DONE button can be pressed. 

MENU ITEM 

DEFINITION

F or C  

Selects temperature units

LBTHODLOD  Outdoor reset enable/disable - 

 

enables menu items

LBT 

Low boiler setpoint  during outdoor reset

HOD 

High outdoor temperature setpoint

LOD 

Low outdoor temperature setpoint

RMT Add 

Used for Lead/Lag (follow menus)

LL 

Lead/Lag enable/disable - enables menu items

HS 

Hysteresis - temp range between on/off cycles

bL 

Base Load % - input rate before next boiler fires

Sd 

Warm weather shut-down temperature

ASC 

Anti short cycle - minutes of delay between   

 startup

bAC 

Future use - Press DONE to exit menu.

PAS 

Future use - Press DONE to exit menu.

NOTE:

  When enabling/disabling functions, select "Done" and wait 30  

 

seconds before scrolling.

Table 2.  SETUP Mode Parameters.

 MENU ITEM 

FUNCTION 

RANGE 

DEFAULT

 Outlet water  Displays the current outlet  55-180°F  120°F

 temperature  water temperature & allows 

 

the setpoint to be adjusted

 Inlet water 

Displays the current inlet 

— 

— 

 temperature  water temperature 
 Delta T 

Displays the current  

— 

 

temperature rise across 

 

the heat exchanger

 DHW 

Domestic Hot Water                  

 

Caution

 Stack 

Displays the current stack 

— 

 temperature  temperature

 Outdoor 

Displays the current outdoor 

— 

 temperature  air temperature

 Firing Rate  Displays an indicator of the  

— 

 

current firing rate based

 

upon fan RPM. The actual 

 

firing rate may vary.

Table 1.  USER Mode Menu.

  MENU ITEM 

DESCRIPTION

                            Please view your Install/Operating Manual

Table 3.  DIAGNOSTIC Mode Menu.

3. Digital Display and Control

 

 

Caution

Scalding Risk: Laars recommends 

the use of a  thermostatic mixing 

valve at domestic hot water 

outlet (boiler location) to 

reduce potential for scalding.

The following thermostatic mixing 

 

valve model has been tested and  

approved for Mascot II application: Honeywell AM100-

US-1.  Contact Laars for additional recommended models.

Summary of Contents for LMC

Page 1: ...xide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instructio...

Page 2: ...For Your Mascott II 3 2 Filling Shut Down and Restart 3 4 3 Digital Display and Control 5 7 To open the front panels Remove these two phillips screws and fold lower door down The middle panel will th...

Page 3: ...ion of all flue product carrying areas of the boiler and its venting system 2 Filling Shut Down and Restart 2 1 Filling the Boiler System 1 Ensure the system is fully connected Close all bleeding devi...

Page 4: ...ezing All water must be removed from heat exchanger and condensate trap or else damage from freezing may occur This step to be performed by a qualified service person 2 3 To Restart Mascot II If drain...

Page 5: ...rature units LBTHODLOD Outdoor reset enable disable enables menu items LBT Low boiler setpoint during outdoor reset HOD High outdoor temperature setpoint LOD Low outdoor temperature setpoint RMT Add U...

Page 6: ...hen there is a central heat call supplied the system pump relay is active If there is a DHW call supplied while the central heat call is active the system pump turns off This happens because of domest...

Page 7: ...er operation the LL menu should be set to LDR To set the boiler to slave SLA should be selected 3 8 3 Lead Lag Address The Lead Lag address must be set for each boiler connected to the lead lag system...

Page 8: ...mer Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 01...

Reviews: