Page 14
Table 2. Required Combustion Air Pipe Material.
SECTION 4. Installation
(continued)
4.3 Combustion Air
LT Series water heaters must have provisions for
combustion and ventilation air in accordance with the
applicable requirements for Combustion Air Supply
and Ventilation in the National Fuel Gas Code,
ANSI Z223 1; or in Canada, the Natural Gas and
Propane Installation Code, CSA B149.1. All applicable
provisions of local building codes must also be
adhered to.
An LT Series unit can take combustion air
from the space in which it is installed, or the
combustion air can be ducted directly to the unit.
Ventilation air must be provided in either case.
4.3.1 Combustion Air from Room
In the United States, the most common requirements
specify that the space shall communicate with the
outdoors in accordance with method 1 or 2, which
follow. Where ducts are used, they shall be of the
same cross-sectional area as the free area of the
openings to which they connect.
Method 1
:
Two permanent openings, one
commencing within 12" (300mm) of the top and one
commencing within 12" (300mm) of the bottom, of
the enclosure shall be provided. The openings shall
communicate directly, or by ducts, with the outdoors
or spaces that freely communicate with the outdoors.
When directly communicating with the outdoors, or
when communicating to the outdoors through vertical
ducts, each opening shall have a minimum free area
of 1 square inch per 4000 Btu/hr (550 square mm/kW)
of total input rating of all equipment in the enclosure.
When communicating to the outdoors through
horizontal ducts, each opening shall have a minimum
free area of not less than 1 square inch per 2000 Btu/
hr (1100 square mm/kW) of total input rating of all
equipment in the enclosure.
Method 2
:
One permanent opening, commencing
within 12" (300mm) of the top of the enclosure, shall
be permitted. The opening shall directly communicate
with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or spaces
that directly communicate with the outdoors and shall
have a minimum free area of 1 square inch per 3000
Btu/hr (734 square mm/kW) of the total input rating of
all equipment located in the enclosure. This opening
must not be less than the sum of the areas of all vent
connectors in the confined space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform
to the requirements in the applicable codes listed
above.
In Canada, consult local building and safety codes or,
in absence of such requirements, follow CAN/CGA
B149.
4.3.2 Ducted Combustion Air
The combustion air can be taken through the wall, or
through the roof. When taken from the wall, it must
be taken from out-of-doors by means of the horizontal
wall terminal. When taken from the roof, a field-
supplied rain cap or an elbow arrangement must be
used to prevent entry of rain water.
As allowed by local codes use ABS, PVC, CPVC,
Polypropylene for the Combustion air intake. Route
the intake to the water heater as directly as possible.
Seal all joints. Provide adequate hangers. The unit
must not support the weight of the combustion air
intake pipe. Maximum linear pipe length allowed is
shown in Table 6.
Subtract 5 allowable linear ft. (1.5m) for every elbow
used.
The connection for the intake air pipe is at the top of
the unit.
In addition to air needed for combustion, air shall also
be supplied for ventilation, including air required for
comfort and proper working conditions for personnel.
COMBUSTION AIR INSTALLATION STANDARDS
MATERIAL
UNITED STATES
CANADA
ABS
ANSI/ASTM D1527
Air pipe material must be chosen CPVC, sch 40, ANSI/ASTM,
Polypropylene
based upon the intended application of the
water heater.
PVC, sch 40 Polypropylene
ANSI/ASTM D1785/1738 or D2665
CPVC, sch 40 Polypropylene
ANSI/ASTM F441
UL1738, ULC S636.
Single wall galv. steel
26 gauge
Summary of Contents for LT Series
Page 42: ...Page 42 4 20 Wiring Diagram...
Page 43: ...Page 43 4 21 Ladder Diagram...