Page 41
HTD
Notes
Map Descriptor Name
BACnet
Data Type
BACnet
Object ID Read/Write
Modbus
Address Type
R/W
245 = Trial for Ignition
250 = Trial for Ignition Main
52=Post Purge
89
U16
Read
Boiler Pump Status
AI
89
Read
90
U16
Read
Cascade Master Heat Demand
AI
90
Read
91
U16
Read
Burner 1 Run Time
AI
91
Read
i
128
S16 Read/Write CH1 Enable/Disable
AV
0
Read/Write
129
S16 Read/Write CH1 Set Point
AV
1
Read/Write
130
S16 Read/Write CH1 P
AV
2
Read/Write
131
S16 Read/Write CH1 I
AV
3
Read/Write
132
S16 Read/Write CH1 D
AV
4
Read/Write
133
S16 Read/Write CH2 Enable/Disable
AV
5
Read/Write
134
S16 Read/Write CH2 Set Point
AV
6
Read/Write
135
S16 Read/Write CH2 P
AV
7
Read/Write
136
S16 Read/Write CH2 I
AV
8
Read/Write
137
S16 Read/Write CH2 D
AV
9
Read/Write
148
S16 Read/Write DHW Enable/Disable
AV
20
Read/Write
149
S16 Read/Write DHW Set Point
AV
21
Read/Write
150
S16 Read/Write DHW P
AV
22
Read/Write
151
S16 Read/Write DHW I
AV
23
Read/Write
152
S16 Read/Write DHW D
AV
24
Read/Write
155
S16 Read/Write Cascade CH Set Point
AV
27
Read/Write
156
S16 Read/Write Cascade CH P
AV
28
Read/Write
157
S16 Read/Write Cascade CH I
AV
29
Read/Write
158
S16 Read/Write Cascade CH D
AV
30
Read/Write
163
S16 Read/Write Hybrid Set Point
AV
35
Read/Write
164
S16 Read/Write Hybrid Differential Temperature
AV
36
Read/Write
165
S16 Read/Write Vari-Prime P - Proportional Term
AV
37
Read/Write
166
S16 Read/Write Vari-Prime I - Integral Term
AV
38
Read/Write
167
S16 Read/Write Vari-Prime D - Derivative Term
AV
39
Read/Write
168
S16 Read/Write Vari-Prime Delta T
AV
40
Read/Write
174
S16 Read/Write DHW Demand switch
BV
0
Read/Write 0 = No Heat Demand; 1 = Heat Demand
175
S16 Read/Write CH 1 Demand switch
BV
1
Read/Write 0 = No Heat Demand; 1 = Heat Demand
176
S16 Read/Write CH 2 Demand switch
BV
2
Read/Write 0 = No Heat Demand; 1 = Heat Demand
179
S16 Read/Write Modbus Parameter Write Enable