LAARS Heating Systems
Page 52
Select ‘Configure’.
In the Configuration Menu, Scroll down and select
‘Lead Lag Slave Configuration’.
identify each unit (including the Lead/Lag Master) as a
slave by turning on “Slave Enable.”
you will be prompted to sign in. This can be done by
pressing the ‘LOcK’ symbol at the top right
type in ‘
lnt
’ (LnT lower case) and press OK.
Then you can select Slave Enable.
Select ‘Enable slave for built-in Lead Lag master’ .
Then select OK
Then select a Modbus address (number) for that boiler.
Then select OK
Repeat on all boilers, keeping them in a sensible
sequencial order. ’ .