MagnaTherm Boilers and Water Heaters
Page 79
code Description
Lockout
or Hold
Procedure
187
invalid DHw (Domestic Hot water)
high limit enable setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
188
invalid DHw (Domestic Hot water)
high limit response setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
189
Invalid flame sensor type setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
192
invalid igniter on during setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
193
invalid ignite failure delay setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
194
invalid ignite failure response setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.\
195
invalid ignite failure retries setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
196
invalid ignition source setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
197
invalid interlock open response setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
198
invalid interlock start check setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.
199
invalid Lci (Limit control input) enable
setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. if fault repeats, verify electrical grounding.
3. if fault repeats, replace module.