background image

MagnaTherm Boilers and Water Heaters

Page 93

Frame and Jacket Assembly

2000

3000

4000

Item #

Description

Part No.

Part No.

Part No.

1

Base assembly

20N1000

30N1000

40N1000

2

Filter

A2121700

A2121700

A2121700

2a

Filter assembly (includes filter)

20N2600

30N2600

40N2600

3

Stanchion

20N3001

30N3001

40N3001

4

Panel, left bottom

20N3002

30N3002

40N3002

5

Panel, right bottom

20N3004

30N3004

40N3004

6

Extension brace, rear

30N3007

30N3007

30N3007

7

Brace, upper side

20N3008

30N3008

40N3008

8

Brace, lower right side

20N3047

30N3011

40N3047

9

Frame mounting bracket

20N3005

30N3012

40N3005

10

Brace

20N3013

30N3013

40N3013

11

Panel, upper rear

20N3019

30N3019

40N3019

12

Panel, center rear

20N3020

30N3020

40N3020

13

Panel, lower rear

20N3021

30N3021

40N3021

14

Panel, right

20N3036

30N3036

40N3036

15

Strut, upper panel support

30N3043

30N3043

30N3043

16

Panel, top

20N3045

30N3045

40N3045

17

Brace, lower left side

20N3047

30N3049

40N3047

18

Hinge mounting bracket, left

20N3163

30N3050

40N3163

19

Hinge mounting bracket, right

20N3164

30N3051

40N3164

20

Panel, right, rain splatter

30N3053

30N3053

40N3050

21

Panel, left, rain splatter

30N3054

30N3054

40N3050

22

Bracket, hinge brace

30N3055

30N3055

30N3055

23

Panel, top left

20N3035

30N3057

40N3035

24

Bracket, pressure switch

5F7007

5F7007

5F7007

25

Cover, field connections

17J3025

17J3025

17J3025

26

Gasket, .75" x .06" x 2 feet

R2074402

R2074402

R2074402

Final Assembly

2000

3000

4000

Item #

Description

Part No.

Part No.

Part No.

1

Heat Exchanger

R20N2070

R30N2070

R40N2070

2

Plate, rear panel, gas pipe

30N3034

30N3034

30N3034

3

Door, right

20N3100

30N3100

40N3100

4

Door, left

20N3150

30N3150

40N3150

5

Control panel assemblies:
MGH

30N7080

30N7080

40N7080

MGH with CSD-1

30N7081

30N7081

40N7081

MGV

30N7082

30N7082

40N7082

MGV with CSD-1

30N7083

30N7083

40N7083

6

Condensate trap assembly

20N2010

30N2010

40N2010

7

Panel, drain access

40N3048

40N3048

40N3048

8

Pressure switch

E2344902

E2344901

E2344901

9

Pressure switch

E2348101

E2348102

E2348101

10

Outlet box (not shown)

E2350900

E2350900

E2350900

11

Spacer

F2035400

F2035400

F2035400

12

Silicone rubber bumper

F2039700

F2037900

F2037900

13

Bushing, nylon

S0064900

S0064900

S0064900

14

Grommet, 2" pipe

S2116500

S2116500

S2116500

15

Grommet, push-in

S2123600

S2123600

S2123600

16

Plug, button, 7/8"

F0032300

F0032300

F0032300

Waterway Outlet Assembly

2000

3000

4000

Item #

Description

Part No.

Part No.

Part No.

1

Pipe, outlet manifold

20N4023

30N4020

40N4020

2

PRV 75# (MGH)

A0002700

A0000300

A208000

PRV 125# (MGV)

A0064400

A0000200

A0000200

3

Flow switch

RE0013000

RE0013000

RE0013000

Flow switch paddle?????

E2255800

E2255800

E2255900

4

Well, immersion, 1/2"NPT

RE2058300

RE2058300

RE2058300

5

Sensor, water temperature, duplex

RE2319900

RE2319900

RE2319900

6

Coupling, flexible victaulic

P2086500

P2086500

P2086600

7

Plug
MGH

N/A

P2088300

P2088300

MGV

N/A

P2080300

P2080300

8

Grommet, rubber

S2114000

S2114000

S2114000

9

Sensor, water temperature (MGH)

RE2320600

RE2320600

RE2320600

10

Gauge, temp & pressure

RA0079000

RA0079000

RA0079000

Blower Burner Assembly

2000

3000

Item #

Description

Part No.

Part No.

1

Burner

L2019500

L2020600

2

Gasket, burner

S2125500

S2125100

3

Adapter plate

20N5037

30N5037

4

Sight glass

RF0044800

RF0044800

5

Flame sensor

W2014000

W2014000

6

Gasket, blower outlet flange

S2125600

S2125200

7

Venturi / Air intake assembly

A2123300

30N5092

8

Gasket, blower intake

20N5095

S2125300

9

Flow sensor, diff pressure

N/A

A2121601

10

Blower

A2122100

A2122100

11

Ignitor, hot surface

W2014400

W2014400

12

Pilot tube

20N5088

30N5093

13

Compression fitting

P2085000

P2085000

14

Gasket, filter box flange

20N5094

N/A

15

Pipe & flange weldment

20N5092

N/A

16

Pipe & flange weldment

20N5090

N/A

17

Gasket, venturi / gas valve

S2104900

N/A

4000

Item #

Description

Part No.

1

Burner

L2019900

2

Gasket, burner

S2124100

3

Gasket, spacer

40N5092

4

Pilot tube

40N5090

5

Gasket, blower outlet flange

40N5093

6

Flow sensor, diff pressure

A2121600

7

Gas/air intake assembly

40N5069

8

Gasket, blower intake

S2125300

9

Blower

A2120900

10

O-Ring

S2124800

11

Adapter 1/4" tube x 1/8" female

P2090200

12

Blower tube

40N5077

13

Gasket, burner

S2124600

14

Ignitor, hot surface

W2013900

15

Sight glass

RF0044800

16

Flame sensor

W2014000

Gas Train Assembly

2000

3000

Item #

Description

Part No.

Part No.

1

Pressure switch, low gas

R2004100

R2004100

2

Pressure switch, high gas

R2004000

R2004000

3

Elbow

P0008600

P0008700

4

Nipple

P0019800

P0021200

5

Nipple, 2"NPTx4"

P0022600

P0022600

6

Bushing, reducing, 1/4x1/8

P2032400

P2032400

7

Adapter, 2"NPTx1-1/2"NPT

N/A

P2085700

8

Nipple

P2092800

P2091600

9

Bushing, nylon

S0064900

S0064900

10

Gas valve, main

V2021200

V2021200

11

Flange, gas valve

V2021900

V2021900

12

Pilot regulator

V2022100

V2022100

13

Ball valve, 3/8"

V2022200

V2022200

14

Compression fitting, 1/4" tube

P2085000

P2085000

15

Compression fitting, 1/4" tube x 1/4NPT

P0004100

P0004100

16

Pilot tube

20N5086

30N6027

17

Nipple, 1/8"x2"

P0011300

P0011300

18

Elbow, 1/8"

P2008900

P2008900

19

Nipple, 1/8"

P0011100

P0011100

20

Nipple/tee weldment

30N6031

30N6031

21

Tee, 1/8"

P0027100

P0027100

22

Nipple, 1/8" x close

P0011100

P0011100

23

Plug

70-236

70-236

24

Ball valve

V2003300

R2011600

25

Ball valve

V2003200

R2011600

26

Adapter, 1/8 FNPT x 1/8 ISO male

P2089600

P2089600

27

Adapter, 1/4 tube barb to 1/8 NPT male

P2089300

P2089300

28

Flange, adjustable shutter

V2022400

V2022000

29

Nipple, 1-1/2" x close

N/A

P0019100

30

Nipple, 3/8"x3"

P2090500

P2090500

31

Tee, 3/8x3/8x3/8

P2090600

P2090600

32

Bushing, reducing, 3/8x1/8

P2090700

P2090700

33

Union

P0030700

N/A

34

Nipple

P2072800

N/A

35

Elbow

P0008700

P0008700

36

Nipple

P0015500

P0021200

37

Nipple

P0021200

P0021200

4000

Item #

Description

Part No.

1

Pressure switch, low gas

R2004100

2

Pressure switch, high gas

R2004000

3

Elbow, 45°, 2"

P2090900

4

Nipple, 2"x14"

P2091000

5

Union, 2"

P0030800

6

Nipple, 2"x6"

P0021700

7

Ball valve

R2011600

8

Bushing, 2"x1-1/2"

P0001400

9

Elbow, 90°, 1-1/2"

P0009600

10

Nipple, 1-1/2"x2.5"

P2045300

11

Flange, adjustable shutter

V2022000

12

Washer, sealing

S2123500

13

Adapter, 1/8 FNPT x 1/8 ISO Male

P2089600

14

Nipple, 1/8 x close

P0011100

15

Tee, 1/8"

P0027100

16

Plug, 1/8"

70-236

17

Bushing, 1/4"x1/8"

P2032400

18

Pipe, gas inlet

40N6034

19

Elbow, 90°, 2"

P2091100

20

Nipple, 2"x2"

P0021100

21

Flange, 2"

V2021900

22

Elbow, 90°, 1/8"

P2008900

23

Tee, 3/8"

P2090600

24

Bushing, 3/8"x1/8"

P2090700

25

Nipple, 3/8"x2"

P2089000

26

Ball valve, 3/8"

V2022200

27

Pilot regulator

V2022100

28

Compression fitting, 1/4" tube x 1/4NPT

P0004100

29

Pilot tube

40N6025

Control Panel Assembly

2000

3000

4000

Item #

Description

Part No.

Part No.

Part No.

1

DIN rail assembly 

30N7040

30N7040

30N7040

2

Low water cutoff

RE2075100

RE2075100

RE2075100

3

Bushing, 7/8 nylon, open

E2074300

E2074300

E2074300

4

Relay, 24VAC, DPDT

E2327800

E2327800

E2327800

5

Display, touch control

E2339800

E2339800

E2339800

6

Bushing, 7/8 nylon, split

S0064900

S0064900

S0064900

7

High limit, manual reset

E2217800

E2217800

E2217800

8

High limit, auto reset

E2217700

E2217700

E2217700

9

Plug, terminal block

E2346300

E2346300

E2346300

10

Vari-Prime control (MGH)

30N7067

30N7067

30N7067

11

Control panel sheet metal assembly

30N7050

30N7050

40N7050

22

Control module, programmed
Standard

RXN7051

RXN7051

RXN7051

CSD-1

RXN7052

RXN7052

RXN7052

APPROVALS

INTENDED SIZE:

1

2

3

.010 

 1/8" 

AL 6-17-13

D

W

G

N

O

.

SOFTWARE

R

EV

S

CJT 6/17/13

SH

40

N

50

68

1

DWG.  NO:

D

SHEET 1  OF 1

REV.

TOLERANCES  ARE:

40N5068

BLOWER BURNER ASSEMBLY, 

TITLE:

A

1

A

STANDARD, MGT 4.0

FRACTIONS 

 DECIMALS .XXX 

.1 

SEE PARTS LIST

SEE PARTS LIST

FINISH

MATERIAL:

DECIMALS .XX  .03 

DECIMALS .X 

DIMENSIONS ARE IN INCHES.

UNLESS  OTHERWISE  SPECIFIED:

APPR

ENGR

DRAFT

ANGLES 

DO NOT SCALE DRAWING.

THIRD ANGLE PROJECTION.

 SCALE: NONE

PART NUMBER

40N5070

 CSD-1

DESCRIPTION

40N5068

STANDARD

N

O

IT

P

I

R

C

S

E

D

.

O

N

 

T

R

A

P

.

Y

T

Q

/

8

6

0

5

N

0

4

.

Y

T

Q

/

0

7

0

5

N

0

4

ITEM

NO.

BOM Table

1

1

S2125300

GASKET, AF-12 BLOWER INTAKE, MAGNATHERM

17

6

1

M

D

P

E

 ,

3

6

1

#

 ,

2

3

/

3

 

X

 

D

"

6

 ,

G

N

I

R

O

0

0

8

4

2

1

2

S

1

1

5

1

0

.

4

 

T

G

M

 ,

P

O

T

 

R

E

N

R

U

B

 ,

T

E

K

S

A

G

0

0

6

4

2

1

2

S

1

1

4

1

0

.

4

 

T

G

M

 ,

T

E

L

T

U

O

 

R

E

W

O

L

B

 ,

T

E

K

S

A

G

 ,

R

E

C

A

P

S

3

9

0

5

N

0

4

2

2

3

1

0

.

4

 

T

G

M

 ,

R

E

N

R

U

B

 ,

T

E

K

S

A

G

 ,

R

E

C

A

P

S

2

9

0

5

N

0

4

4

4

2

1

0

.

4

 

T

G

M

 ,

R

E

N

R

U

B

 ,

T

E

K

S

A

G

0

0

1

4

2

1

2

S

1

1

1

1

S

S

 ,

E

P

I

P

 

E

L

A

M

E

F

 

T

P

N

 

8

/

1

 

X

 

E

B

U

T

 "

4

/

1

 ,

R

E

T

P

A

D

A

0

0

2

0

9

0

2

P

2

2

0

1

0

.

4

 ,

T

G

M

 ,

R

E

N

R

U

B

0

0

9

9

1

0

2

L

1

1

9

C

N

I

Z

 ,

.

G

L

 "

5

.

1

 

X

 

C

N

U

 

6

1

-

8

/

3

 ,

P

A

C

 

X

E

H

 ,

W

E

R

C

S

7

9

3

0

2

F

8

8

8

D

T

L

P

 

C

N

I

Z

,

C

N

U

 

6

1

-

8

/

3

,

T

U

N

0

0

1

3

0

0

0

F

6

1

6

1
16

16

F2037700

WASHER, THICK FLAT, 3/8, STEEL, ZINC PLATED, 13/16" OD

7
6

L

E

E

T

S

 

S

S

E

L

N

I

A

T

S

 ,

L

 "

2

/

1

 

X

 

8

#

 ,

W

E

R

C

S

0

0

9

6

0

0

2

F

2

2

5

"

6

 ,

W

O

L

F

 

E

R

U

S

S

E

R

P

 

L

A

IT

N

E

R

E

F

F

I

D

 ,

R

O

S

N

E

S

0

0

6

1

2

1

2

A

1

1

4

T

G

M

 

0

.

4

 

E

B

U

T

 

T

O

L

I

P

 ,

T

N

E

M

D

L

E

W

0

9

0

5

N

0

4

1

1

3

0

.

4

 

T

G

M

 ,

T

N

E

M

D

L

E

W

 ,

E

B

U

T

 

R

E

W

O

L

B

7

7

0

5

N

0

4

1

1

2

0

.

4

 

T

G

M

 ,

Y

S

S

A

 

E

K

A

T

N

R

I

A

9

6

0

5

N

0

4

1

1
1

-

40N6021

GAS TRAIN ASSEMBLY, CSD-1

1

-

1

40N6020

GAS TRAIN ASSEMBLY, STANDARD

 3

 5

9

6

11

13

12

4

 3

7

 1

10

11

 2

 8

14

15

16

13.2.6  Blower Burner assembly,  

Part numbers (model 4000)

Summary of Contents for MAGNATHERM MGH2000

Page 1: ...se serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instructions donn es dans cette notice pour r du...

Page 2: ...Massachusetts 14 3 4 Common Vent Test 15 3 5 Outdoor Installation 16 Section 4 Gas Supply and Piping 4 0 Gas Supply and Piping 16 Section 5 Pump Requirements 5 1 MagnaTherm Boiler Flow and Head Requi...

Page 3: ...up Instructions 10 1 Filling the Boiler System 62 10 2 Initial Operation 63 10 2 1 Initial Burner Operation 63 10 2 2 Combustion Setup Procedure 63 10 3 Shutting Down the MagnaTherm 63 10 4 Restarting...

Page 4: ...LAARS Heating Systems...

Page 5: ...onfiguration can cause fuel buildup and explosion Improper user operation may result in property loss severe physical injury or death Any changes to safety related configuration parameters must only b...

Page 6: ...following information describes the model number structure 1 2 Model Series Designation M G MagnaTherm 3 Usage H Hydronic V Volume Water 4 7 Size 2 0 0 0 1 999 000 BTU hr input 3 0 0 0 3 000 000 BTU...

Page 7: ...r Condensing Unit Air Intake and Filter Water Outlet Water Inlet Vent Power Pack Perspective from opposite corner Perspective from front left corner Shown with front doors and left side panels removed...

Page 8: ...LAARS Heating Systems Page 4 Manual gas valve Blower Touch Screen Model 3000 Air Intake and Filter Water Outlet Water Inlet Vent Power Pack Condensate Trap Heat Exchanger Condensing Unit...

Page 9: ...ers and Water Heaters Page 5 Model 4000 Manual gas valve hidden behind main gas valve Blower Touch Screen Air Intake and Filter Water Outlet Water Inlet Vent Power Pack Condensate Trap Heat Exchanger...

Page 10: ...8 75 85 6 G H J K l m n P q r S t Inches cm Inches cm 60 8 154 2 6 7 8 4 21 67 4 171 4 10 39 2 100 30 4 77 16 41 23 58 10 2 26 14 36 13 33 71 180 4 10 8 9 23 76 8 195 4 3 11 44 4 113 34 5 88 17 7 45 2...

Page 11: ...l for snow accumulation in the local area both terminals should be installed at an appropriate level above grade or the maximum expected snow line The dimensions and requirements that are shown in Tab...

Page 12: ...stalled or the combustion air can be ducted directly to the unit Ventilation air must be provided in either case 3 1 1 Combustion Air From Room In the United States the most common requirements specif...

Page 13: ...t pipe length allowed is 100 feet 30 m Each elbow is considered to be 5 feet 1 5m When using polypropylene or stainless steel materials in horizontal duct configurations a single elbow must be install...

Page 14: ...hout the addition of an external vent extraction fan professionally engineered and approved by the local jurisdiction MagnTherm units are never permitted to share a vent with any Catagory 1 appliances...

Page 15: ...e gas sampling port internal to the MagnaTherm so one must be installed in the vent system external to the MagnaTherm A flue gas sampling port available as a component of the ULC S636 certified vent s...

Page 16: ...gulator vent outlet See note 4 3 feet 91 cm J Clearance to nonmechanical air supply Direct vent only 36 91cm inlet to building or the combustion air inlet Other than Direct vent 4 ft 1 2m below 36 inc...

Page 17: ...roup is 84 213 cm See Figure 5 6 The vent outlet must be at least 12 above the top of the air inlet and must be at least 84 213 cm horizontally from the air inlet See Figure 5 84 213 12 Figure 4 Minim...

Page 18: ...d In addition the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling build...

Page 19: ...to their previous conditions of use 7 Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or CA...

Page 20: ...p must be provided upstream of the gas controls 7 All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas 8 The appliance and its individual shutoff va...

Page 21: ...bic Feet of Gas per Hour Table 8 Pipe Capacity for Natural Gas Table 9 Pipe Capacity for Propane Nominal 1 2 2 3 4 Actual ID 1 61 2 067 2 469 3 068 4 026 Length ft 10 3 520 6 790 10 800 19 100 39 000...

Page 22: ...Therm Electrical Op Temp Rise Flow Head Loss Grains F C GPM LPM Feet m per Gallon 2000 20 12 177 670 43 9 13 4 10 3000 25 14 220 833 46 14 10 4000 30 17 266 1006 41 2 12 6 10 Size Size Size temperatur...

Page 23: ...er Section 6 Water Connections MGH Boilers 6 1 MGH System Piping Hot Supply Connections Note This appliance must be installed in a closed pressure system with a minimum of 12 psi 82 7 kPa static press...

Page 24: ...g Schematics Figure 7 through Figure 10 show suggested piping configurations for MGH boilers These diagrams are only meant as guides All components or piping required by local code must be installed 6...

Page 25: ...feed controls Air vent 4 pipe dia max 4 pipe dia max 4 pipe dia max 4 pipe dia max Low temp radiant zone Space heating zone circuits Space heating zone circuit System pump Note This drawing is a sche...

Page 26: ...one Air vent Water feed controls Expansion tank 4 pipe dia max Indirect DHW tank Anti scald mixing valve Domestic hot water out Cold water Note This drawing is a schematic representation of a piping s...

Page 27: ...ow temp radiant zone Space heating zone circuit Air vent Water feed controls Expansion tank Common piping must be sized for the combined water flow of all of the boilers 4 pipe dia max 4 pipe dia max...

Page 28: ...pipe dia max 4 pipe dia max 4 pipe dia max Indirect DHW tank Note Indirect pump must be sized for boiler and indirect Anti scald mixing valve Domestic hot water out Cold water Note In this piping arr...

Page 29: ...r less with a pH range of 6 5 to 9 5 pH Values outside of this range may reduce the life expectancy of the product Operating the MGV in water with higher hardness levels will cause heat exchanger foul...

Page 30: ...ndensate inside and outside of the boiler from freezing Damage due to freezing water or condensate is not covered by the warranty If installed indoors and there is an event such as a power outage comp...

Page 31: ...n the drain connection and a floor drain or condensate pump if a floor drain is not accessible The condensate drain must be installed to prevent the accumulation of condensate When a condensate pump i...

Page 32: ...m line is equipped with multiple voltage packages to adapt to customer needs ranging from 120 600 volts with single or 3 phase versions Refer to the rating plate for appropriate voltage and current ra...

Page 33: ...mp terminals are found on the Main control board TB1 15A through 20A They are fed 120 Volts internally from the main power feed The current rating of the contacts is 7 4 amps and an appropriately size...

Page 34: ...LAARS Heating Systems Page 30 Figure 14 Electronics Panel Layout 1 CA 2 KM 1 E23 1 E23 1 KM 1 A00 A00 1 E00 1 30 QTY PA 5 2 4 6 8 1 9 7 3 8 4 Control Panel Layout...

Page 35: ...ESET HIGH LIMIT CONTROL 8 1 E2339800 TOUCH SCREEN ALARM SILENCE SWITCH MANUAL RESET HIGH LIMIT ALARM BELL optional LOW WATER CUT OFF BAS GATEWAY optional 7 1 E2346100 6 1 KM004300 5 1 A0014300 4 Termi...

Page 36: ...OR OR W BR Y BL W BR BL BK W BK Y G BK W V BR BL W R W R W Y 4 DISPLAY 7 DISPLAY 8 LWCO 2 120V N P1 P2 ADDITIONAL HIGH LIMIT BLOCKED FLUE BLOCKED INTAKE THERMAL CUTOUT FLOW SWITCH HIGH GAS MANUAL RESE...

Page 37: ...TEMP DRAIN WIRE FROM SHIELDED CABLE BL BL W W BK BL BL V V R R BL BL Y Y Y USED ON SIZE 4 0 KBTU ONLY BL Y BL V W V OR OR W W BK W V W BK BR Y BR Y G W BK BK BK R BK Y W R W R W R GY BL BR R BR Y GY V...

Page 38: ...LTAGE PANEL E23578 D C B 4 3 1 S PROPRIETARY TO LAARS HEATING SYSTEMS AND SHALL NOT BE 2 BY LAARS HEATING SYSTEMS DWG NO SH 1 REV KG 1 17 14 REVISIONS REV CHANGE APPR ENGR APPR ECN DRAFT CHECK RELEASE...

Page 39: ...L A B C D 4 3 1 TITLE PROPRIETARY TO LAARS HEATING SYSTEMS AND SHALL NOT BE 2 BY LAARS HEATING SYSTEMS FRACTIONS DWG NO E23603 SH 1 2 5 14 REVISIONS REV CHANGE APPR ENGR APPR ECN DRAFT REV RELEASED 14...

Page 40: ...1 BY LAARS HEATING SYSTEMS E23602 SH 1 DWG NO REV AL 2 4 14 REVISIONS REV CHANGE APPR ENGR APPR ECN DRAFT CHECK RELEASED JM 2 4 14 14 002N 13 APPROVALS UNLESS OTHERWISE SPECIFIED PURPOSE EXCEPT AS SPE...

Page 41: ...6 37 38 39 40 42 41 TOD FEED J10 2 J6 8 J6 7 ALARM 27 28 26 25 24 23 22 21 TB1 4A 20 19 18 17 15 16 FIELD CONNECTIONS TT ANALOG OUTDOOR SYSTEM DHW PUMP SYSTEM PUMP BOILER PUMP J8 3 TB1 13 J8 6 J8 7 J8...

Page 42: ...5 24 23 22 21 TB1 4A 20 19 18 17 15 16 FIELD CONNECTIONS TT ANALOG OUTDOOR SYSTEM DHW PUMP SYSTEM PUMP BOILER PUMP J8 3 TB1 13 J8 6 J8 7 J8 11 J8 12 J4 2 J4 4 TB1 4A TB1 4A J4 6 VFD 16 VFD 17 J4 2 J4...

Page 43: ...DISPLAY 4 35 36 37 38 39 40 42 41 TOD FEED J10 2 J6 8 J6 7 ALARM 27 28 26 25 24 23 22 21 TB1 4A 20 19 18 17 15 16 FIELD CONNECTIONS TT ANALOG OUTDOOR SYSTEM DHW PUMP SYSTEM PUMP BOILER PUMP J8 3 TB1 1...

Page 44: ...al operation the Touch Screen will automatically present this Home screen See Menu 1 Menu 1 Home Screen Menu 2 Status Summary Figure 22 To access the Touch Screen The home screen shows a picture of th...

Page 45: ...d Setup and parameter changes made when the system is installed and some diagnostic and troubleshooting functions The installer level password is lnt lower case LNT User Level no password required Non...

Page 46: ...s andmechanics Hazardousburnerconditionscan happenwithimproperoperationsthatmayresultin PROPERTYLOSS PHYSICALINJURY orDEATH Press OK to continue The system will ask you to login before you make a chan...

Page 47: ...ify the entries in those groups in the same way Do this until the following screen shows Menu 8 Safety Parameter Reset 6 When the process is complete the system will tell you to reset the control syst...

Page 48: ...uts used by the system Details Allows you to check the status of all of the setup parameters on the control system 9 5 Configuring Parameters In this section we will give you a quick explanation of ho...

Page 49: ...and Alert logs will be incorrect The display has a removable battery CR2032 to store time date lockout and alerts in the event of a power failure To set the clock 1 Start at the home screen Menu 14 H...

Page 50: ...display information regarding software date codes model numbers and program name as well as giving the installer access to re name the boiler and to change the modbus addresses for lead lag operation...

Page 51: ...ect water heaters that are used with boiler MGH systems 9 7 5 Warm Weather Shutdown Configuration Connect the outdoor reset sensor as descibed in Section 9 7 3 From this menu you will be able to enabl...

Page 52: ...er Run Time DHW Pump Cycles Boiler Pump Cycles and System Pump Cycles This menu is Read Only 9 7 10 High Limits The outlet High limit can be adjusted using the installer password After a change is mad...

Page 53: ...ght normally Model Propane Orifice inches Propane Pressure Natural Pressure 2000 0 040 3 4 3 4 3000 0 035 3 4 3 4 4000 0 047 2 3 3 4 Table 14 Required Gas Pressures 9 7 15 System Configuration The ins...

Page 54: ...Lead Lag Master A Run sequence is initiated when the system temperature falls to the Lead Lag Central Heat setpoint Actually this is the LL CH setpoint less the On Hysteresis value The default settin...

Page 55: ...at the firing rate of that first boiler rises to your boiler configurations Base Load Value see Table 15 the next boiler in the sequence will start up and begin firing at 20 to 35 fan speed depending...

Page 56: ...turning on Slave Enable You will be prompted to sign in This can be done by pressing the LOCK symbol at the top right type in lnt LNT lower case and press OK Then you can select Slave Enable Select En...

Page 57: ...entral Heat CH Config Central Heat CH Config Setpoint CH Config Setpoint CH Config Setpoint CH Config Setpoint CH Config Setpoint CH Config Setpoint CH Config Setpoint CH Config Modulation CH Config M...

Page 58: ...Auto 22 50 Auto On 100 100 60 100 60 100 CH LL Slave CH DHW LL Slave DHW CH DHW Arrow Points to Loop with Higher Priority Arrow Points to Loop with Higher Priority Shutdown Immediately 95F Shutdown I...

Page 59: ...me Shutdown Immediately Shutdown Immediately Disabled 65 65F 40F 150F 0 Disabled 0 100 Enable Disable DHW CH Enabled CH DHW DHW CH Enable Disable Drop After Priority Time 240 min or 4 Hrs Boost During...

Page 60: ...gs Modulation Lead Lag Master Config Adv Settings Modulation Lead Lag Master Config Adv Settings Modulation Lead Lag Master Config Adv Settings Modulation Lead Lag Master Config Adv Settings Modulatio...

Page 61: ...protocols contact the factory Signals from the Building Automation System will be connected to the COM2 terminals located on TBI 33A through 35A of this master boiler display WARNING When servicing th...

Page 62: ...100 10 VDC or 20 mA 5 Once the Main Gas valve is energized the PCB will maintain pump output at 100 for 60 seconds to allow the system to stabilize Once the 60 second timer has expired the PCB will t...

Page 63: ...on in the lower left corner Menu 24 Configuration Menu 5 From the Configuration menu select the line Burner Control Ignition Menu 25 Burner Control Ignition Once there select Pilot Test Hold and turn...

Page 64: ...n high fire CO2 0 5 to 1 2 wc Propane 10 0 0 2 0 25 lower than high fire CO2 0 5 to 1 2 wc 4 000 Natural 9 0 0 2 0 25 lower than high fire CO2 0 5 to 1 2 wc Propane 10 0 0 2 0 25 lower than high fire...

Page 65: ...gh Fire fan speed 100 After entering the appropriate fan speed select Manual Run in the Firing Rate Control section to the left of the same window then hit OK Once the Main flame establishes the contr...

Page 66: ...ontrol that may have been under water Section 10 Initial startup Instructions 10 1 Filling the Boiler System 1 Ensure the system is fully connected Close all bleeding devices and open the make up wate...

Page 67: ...ial Operation The initial setup must be checked before the unit is put into operation Problems such as failure to start rough ignition strong exhaust odors etc can be due to improper setup Damage to t...

Page 68: ...ed service technician a Appliance control f Flow switch b Automatic gas valve g Low water cutoff c Pressure switches h Burner d Blower i Heat exchanger e Pump j Ignitor Do the following once every six...

Page 69: ...amic encased hot surface ignitor The silicone nitride element is extremely fragile and should be handled with care in the event of removal never touch the silicone nitride tip with bare skin oils in y...

Page 70: ...have been brushed clean rinse the tubes and combustion chamber with a small amount of water to rinse all of the debris out of the bottom of the flue collector and into the longer condensate trap line...

Page 71: ...o the startup This indicates that the control system is waiting for a condition to be satisfied No Reset is required to recover from an alert The system maintains a history of the 15 most recent alert...

Page 72: ...last 15 Lockout occurances Press Alerts to bring up a list of the last 15 Alerts and Silence Alarm in the event of a lockout condition By silencing the alarm the audible alert has been disabled Howeve...

Page 73: ...ters need verification and a device needs reset to complete verification 2 Configuration ended without verification re enter configuration verify safety parameters and reset device to complete verific...

Page 74: ...odule 2 If fault repeats replace module 18 Internal fault Safety relay test failed due to feedback not ON L Internal fault 1 Reset module 2 If fault repeats replace module 19 Internal fault Safety RAM...

Page 75: ...r H Internal fault 1 Reset module 2 If fault repeats replace module 32 46 Internal fault Safety Key 0 through 14 L Internal fault 1 Reset module 2 If fault repeats replace module 47 Flame Rod to groun...

Page 76: ...heck wiring and correct any faults 2 Check Preignition Interlock switches to assure proper functioning 3 Check the valve operation 4 Reset and sequence the module monitor the PII status 5 If code pers...

Page 77: ...module 91 Inlet sensor fault H 1 Check wiring and correct any possible errors 2 Replace the Inlet sensor 3 If previous steps are correct and fault persists replace the module 92 Outlet sensor fault H...

Page 78: ...ber Correct any errors 2 Make sure that the flame detector is wired to the correct terminal 3 Make sure the F G wires are protected from stray noise pickup 4 Reset and sequence the module if code reap...

Page 79: ...nal hardware test Not a lockout 111 Flame current lower than weak threshold H Hold time of recycle and hold option Will not be a lockout fault Hold Only Internal hardware test Not a lockout 113 Flame...

Page 80: ...FDs Variable speed Fan Drive ability to change speeds 3 Change the VFD 4 If the fault persists replace the module 137 ILK Interlock failed to close H 1 Check wiring and correct any possible shorts 2 C...

Page 81: ...ppears replace the module 157 Combustion pressure and flame OFF L 1 Check that flame is not present in the combustion chamber Correct any errors 2 Make sure that the flame detector is wired to the cor...

Page 82: ...module 2 If fault repeats replace module 174 Safety relay feedback incorrect L Internal Fault 1 Reset module 2 If fault repeats replace module 175 Safety relay open L Internal Fault 1 Reset module 2...

Page 83: ...ical grounding 3 If fault repeats replace module 194 Invalid ignite failure response setting L 1 Return to Configuration mode and recheck selected parameters reverify and reset module 2 If fault repea...

Page 84: ...ctrical grounding 3 If fault repeats replace module 205 Invalid Outlet high limit response setting L 1 Return to Configuration mode and recheck selected parameters reverify and reset module 2 If fault...

Page 85: ...le 219 Invalid Stack limit response setting L 1 Return to Configuration mode and recheck selected parameters reverify and reset module 2 If fault repeats verify electrical grounding 3 If fault repeats...

Page 86: ...3 If fault repeats replace module 230 Invalid CH Central Heat demand source setting L 1 Return to Configuration mode and recheck selected parameters reverify and reset module 2 If fault repeats verify...

Page 87: ...to Configuration mode and recheck selected parameters reverify and reset module 2 If fault repeats verify electrical grounding 3 If fault repeats replace module 12 3 Diagnostic Tests and Input Output...

Page 88: ...ncludes a diagnostic screen that lists some information on the Lead Lag slaves in the system See Menu 39 Menu 39 Lead Lag Diagnostics Use the left and right arrows to see all of the columns in the dis...

Page 89: ...Sequence When there is a call for heat the unit will close pump contacts to energize the customer supplied relay contactor to start water flow Once the LCI circuit flow switch gas pressure switches L...

Page 90: ...BUTION BOX G Section 13 Replacement Parts Use only genuine LAARS replacement parts 13 1 General Information To order or purchase parts for the LAARS MagnaTherm Appliance contact your nearest LAARS dea...

Page 91: ...0N3050 40N3163 19 Hinge mounting bracket right 20N3164 30N3051 40N3164 20 Panel right rain splatter 30N3053 30N3053 40N3050 21 Panel left rain splatter 30N3054 30N3054 40N3050 22 Bracket hinge brace 3...

Page 92: ...LAARS Heating Systems Page 88 DETAIL A View from Back 12 3 12 5 11 14 2 1 4 8 9 13 16 Final Assembly...

Page 93: ...rubber bumper F2039700 F2037900 F2037900 13 Bushing nylon S0064900 S0064900 S0064900 14 Grommet 2 pipe S2116500 S2116500 S2116500 15 Grommet push in S2123600 S2123600 S2123600 16 Plug button 7 8 F003...

Page 94: ...9 Pressure switch E2348101 E2348102 E2348101 10 Outlet box not shown E2350900 E2350900 E2350900 11 Spacer F2035400 F2035400 F2035400 12 Silicone rubber bumper F2039700 F2037900 F2037900 13 Bushing ny...

Page 95: ...witch RE0013000 RE0013000 RE0013000 Flow switch paddle E2255800 E2255800 E2255900 4 Well immersion 1 2 NPT RE2058300 RE2058300 RE2058300 5 Sensor water temperature duplex RE2319900 RE2319900 RE2319900...

Page 96: ...5090 N A 17 Gasket venturi gas valve S2104900 N A 4000 3 Door right 20N3100 30N3100 40N3100 4 Door left 20N3150 30N3150 40N3150 5 Control panel assemblies MGH 30N7080 30N7080 40N7080 MGH with CSD 1 30...

Page 97: ...124600 14 Ignitor hot surface W2013900 15 Sight glass RF0044800 16 Flame sensor W2014000 Gas Train Assembly APPROVALS INTENDED SIZE 1 2 3 010 1 8 AL 6 17 13 SOFTWARE S CJT 6 17 13 DWG NO D SHEET 1 OF...

Page 98: ...LAARS Heating Systems Page 94 28 26 26 23 27 16 31 23 20 5 35 11 10 29 7 25 34 37 2 24 9 12 13 14 3 3 4 36 1 17 19 26 9 6 6 21 17 18 22 30 32 15 8 33 Gas Train Assembly Models 2000 and 3000...

Page 99: ...fitting 1 4 tube x 1 4NPT P0004100 P0004100 16 Pilot tube 20N5086 30N6027 17 Nipple 1 8 x2 P0011300 P0011300 18 Elbow 1 8 P2008900 P2008900 19 Nipple 1 8 P0011100 P0011100 20 Nipple tee weldment 30N6...

Page 100: ...A 1 W2000300 VALVE MANUA 2 S2123500 WASHER SEA 2 P2089600 ADAPTER FEMALE 1 P2089300 ADAPTER 1 4 TUB 1 40N6040 GAS TRA 1 40N6031 GAS TRAIN 1 V2022300 VALVE 18 23 24 16 22 14 13 12 21 20 1 19 17 14 7 25...

Page 101: ...ipe gas inlet 40N6034 19 Elbow 90 2 P2091100 20 Nipple 2 x2 P0021100 21 Flange 2 V2021900 22 Elbow 90 1 8 P2008900 23 Tee 3 8 P2090600 24 Bushing 3 8 x1 8 P2090700 25 Nipple 3 8 x2 P2089000 26 Ball va...

Page 102: ...LAARS Heating Systems Page 98 6 2 7 11 1 5 4 12 10 3 3 8 9 6 Control Panel Assembly...

Page 103: ...40 2 Low water cutoff RE2075100 RE2075100 RE2075100 3 Bushing 7 8 nylon open E2074300 E2074300 E2074300 4 Relay 24VAC DPDT E2327800 E2327800 E2327800 5 Display touch control E2339800 E2339800 E2339800...

Page 104: ...03 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Printed in U S A Laars Heating Systems 1401 Document 1276 Dimensions and sp...

Reviews: