background image

Mascot II Boilers and Water Heaters

Page 35

SECTION 11.
Maintenance

 WARNING

Disconnect all power to the appliance before
attempting any service to the appliance. Contact with
electricity can result in severe injury or death.

11.1  System Maintenance

(yearly, unless otherwise noted)

1.

If a strainer is employed in a pressure reducing
valve or the piping, clean it every six months.

2.

Inspect the venting system for obstruction or
leakage at least once a year. Periodically clean the
screens in the vent terminal and combustion air
terminal (when used).

3.

Keep the appliance area clear and free from
combustible materials, gasoline, and other
flammable vapors and liquids.

4.

If the appliance is not going to be used for
extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water.

5.

Low water cutoffs, if installed, should be checked
every year. Float type low water cutoffs should be
flushed periodically.

6.

Inspect and clean the condensate collection system
yearly.

7.

When a means is provided to neutralize
condensate, ensure that the condensate is being
neutralized properly.

8.

Removal of burner door and inspection of
combustion coil and flue passages is required at
least once a year. Clean with a soft bristle brush /
vacuum or wash with water if necessary. Sooting
and buildup on the coils is an indication of
improper set up and poor combustion. Determine
the cause and make corrections.

9.

Inspect the vent system and air intake system, and
ensure that all joints are sealed properly. If joints
need to be resealed, completely remove existing
sealing material, and clean with alcohol. Apply
new sealing material, and reassemble.

11.2  Appliance Maintenance and

Component Description

Use only genuine LAARS replacement parts.

 Caution

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.

Mascot II gas and electric controls are engineered

for long life and dependable operation, but the safety of
equipment depends on their proper functioning. Only a
qualified service technician should inspect the basic

items listed below every year:

a. Appliance control

f. Flow switch

b. Automatic gas valve

g. Low water cutoff

c. Pressure switches

h. Burner

d. Blower

i. Heat exchanger

e. Pump

11.2.1  Burner

Check the burner for debris. Remove the blower

arm assembly to access the burner. Remove the 4 bolts
connecting the blower to the arm (

see Figure 32

).

Remove the 5 bolts, which hold the burner arm in place.
Pull burner up and out. Clean burner, if necessary, by
blowing compressed air from the outside of the burner
into the center of the burner, and wipe the inside of the
burner clean with glass cleaner. A dirty burner may be
an indication of improper combustion or dirty
combustion air. Determine the cause, and correct. If
damaged, replace the burner gasket when replacing the
burner.

NOTE:

When installing the burner, make sure the

flange is aligned with the mating surface, as each is
keyed to control fit.

11.2.2  Appliance Control

Mascot II has an integrated control that

incorporates manual reset high limit control, operating
temperature control, modulating control, ignition
control, outdoor reset control, pump control and many
other features. If any of these features are thought to be
defective, please consult the factory for proper trouble
shooting practices prior to replacing the control. If
control replacement is required, turn off all power to the
appliance and shut off all manual gas valves to the
appliance. Remove the front door to the appliance and
the control panel plastic bezel. Remove all wire
connections from the control board. The control board
connections are keyed to only allow connection in the
proper location, but proper handling techniques should
be used to avoid damage to the wiring or connectors. To
remove the control push in on the two tabs on the left
side of the board to unlatch the clips from the control
panel. Rotate the control around the fastening points on
the right side of the control to remove the hooks from
the control panel. To replace the control repeat the steps
above in the reverse order making sure to connect all
wires in the proper location. Place the appliance in
operation following the steps outlined in 

Section 10

.

11.2.3  Ignitor Assembly

The ignitor assembly is a two rod system that

consists of a ground rod and a sense rod. To remove the
ignitor assembly, shut off the 120 Volt power supply to
the appliance. Turn off all manual gas valves connecting
the appliance to the main gas supply line. Remove the
front door of the boiler to gain access to the ignitor
assembly. Remove the two wires connected to the
assembly. Then remove the two bolts connecting the
ignitor assembly to the burner door. Remove and
replace the old ignitor assembly gasket. Reinstall a new

Summary of Contents for Mascot II

Page 1: ...monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or operation will void the warranty AVERTISSEMENT Assurez vous de bien suivres les instr...

Page 2: ...ating System Pump Capacity 17 SECTION 6 Water Connections 6 1 Central Heat System Piping 17 6 2 Cold Water Make Up 17 6 3 Freeze Protection 18 6 4 Suggested Piping Schematics 19 6 5 Recognized Chemica...

Page 3: ...Operating the Burner and Set Up 32 10 2 1 Burner Operation 32 10 2 2 Boiler Setup and Adjustment 33 10 3 Shutting Down Mascot II 33 10 4 To Restart Mascot II 33 SECTION 11 Maintenance 11 1 System Main...

Page 4: ...he PRV should be installed prior to filling the system Refer to Figures 1 and 2 for PRV locations IMPORTANT The inlet gas pressure to the appliance must not exceed 13 W C 3 2kPa All installations must...

Page 5: ...sponsible for shortages and damage to the shipment whether visible or concealed 1 5 Unpacking The Mascot II is shipped in a single crate with the following standard components packed with the applianc...

Page 6: ...LAARS Heating Systems Page 6 Figure 2 Location of Components...

Page 7: ...Water Heaters Page 7 Figure 3 Dimensional Drawing Cond Hydronic DHW 2nd Gas Hydronic DHW 2nd Outlet Return Inlet Return Supply Supply Outlet Supply 3 4 3 4 1 2 3 4 1 2 3 4 1 2 3 4 PVC copper NPT copp...

Page 8: ...ertified to ULC S636 Intake air pipe must be PVC or CPVC that complies with ANSI ASTM D1785 F441 ABS that complies with ANSI ASTM D1527 or galvanized material Installer must comply fully with manufact...

Page 9: ...ll bracket are purposely offset NOTE Mascot II models include 16 on center mounting holes on upper rear of boiler jacket These holes are not identified on the mounting template If mounting conditions...

Page 10: ...of the combustion air intake pipe Maximum linear pipe length allowed is shown in Table 2 Subtract 5 allowable linear ft 1 5m for every elbow used The connection for the intake air pipe is at the top...

Page 11: ...el or otherwise must be certified to this ULC standard Appropriate selection of vent material is very important for proper performance and safe operation of the Mascot II The flue temperature of the M...

Page 12: ...e a nuisance or hazard 3 Locate the vent terminal so that vent gases cannot be drawn into air conditioning system inlets 4 Locate the vent terminal so that vent gases cannot enter the building through...

Page 13: ...4 3 feet 91 cm J Clearance to nonmechanical air supply Direct vent only 12 30cm 80 285 36 91cm inlet to building or the combustion air inlet 399 850 Other than Direct vent 4 ft 1 2m below 36 inches 91...

Page 14: ...shall be the responsibility of the property owner to secure the services of qualified licensed professionals for installation of hard wired carbon monoxide detec tors a In the event that the side wal...

Page 15: ...um speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so the appliance will operate...

Page 16: ...ing plate Mascot II will function properly without the use of high altitude modification at elevations up to 10 000 feet 3050 m 2 The maximum inlet gas pressure must not exceed 13 W C 3 2kPa The minim...

Page 17: ...toff valves where required by code Suggested piping diagrams are shown in Figures 12 through 19 These diagrams are meant only as a guide Components required by local codes must be properly installed M...

Page 18: ...a boiler is subjected to freezing conditions and the boiler is not able to fire and or the water is not able to circulate there is a risk of freezing in the boiler or in the pipes in the system When w...

Page 19: ...itable for use in the Mascot II Please refer to the manufacturers instructions for proper selection and application 1 Sentinel Performance Solutions Group 2 Hercules Chemical Company 3 Dow Chemical Co...

Page 20: ...3 42 38 15 33 31 28 Table 8 DHW and Pump Performance Data Caution Scalding Risk Laars recommends the use of a thermostatic mixing valve at domestic hot water outlet boiler location to reduce potential...

Page 21: ...Mascot II Boilers and Water Heaters Page 21 Figure 16 Hydronic Piping Multi boilers for large homes with long multiple baseboard zones Installer to provide DHW anti scald thermostatic mixing valve...

Page 22: ...LAARS Heating Systems Page 22 Figure 17 Hydronic Piping Multi boilers for large homes with long multiple radiant zones Installer to provide DHW anti scald thermostatic mixing valve...

Page 23: ...Mascot II Boilers and Water Heaters Page 23 Figure 18 Hydronic Piping Heating zones piped with zone pumps Installer to provide DHW anti scald thermostatic mixing valve...

Page 24: ...LAARS Heating Systems Page 24 Figure 19 Hydronic Piping Heating zones piped with zone valves Installer to provide DHW anti scald thermostatic mixing valve...

Page 25: ...he 24V field interlock as shown in the wiring diagram s 7 1 Main Power Plug power cord into a non switched 115V electrical outlet with 15A circuit protection FLA is 2A There is an internal 10A breaker...

Page 26: ...teps until all Modbus port 1 terminal A connections are wired d Repeat the above steps for Modbus port 1 terminal B and C connections to complete the wiring e Connect the drain wire from the twisted p...

Page 27: ...Mascot II Boilers and Water Heaters Page 27 Figure 22 Wiring Diagram...

Page 28: ...in Tables 9 11 Once in a particular menu structure navigation consists of pressing the next button to scroll from item to item and then pressing the up and down arrows to change values Once the value...

Page 29: ...to control temperature of an indirect tank 8 8 Lead Lag Cascading Lead Lag Cascading allows multiple boilers to be connected together and controlled from one common sensor input Up to 8 boilers can b...

Page 30: ...Reset Outdoor reset varies the control point setpoint based on the actual outdoor temperature The reset function works as shown in Figure 24 When the outdoor air temperature reaches the high outdoor t...

Page 31: ...then the boilers will simultaneously drop their firing rate If when reaching the point where both boilers drop toward their minimum firing rate 20 then the first slave will drop out Slave1 will remai...

Page 32: ...energize for pre purge then the ignition sequence starts After all safety devices are verified the gas valve opens If ignition doesn t occur turn off the Mascot II check that there is SECTION 10 Oper...

Page 33: ...can be forced to low fire to allow for easier setup Refer to Section 8 1 Table 11 for instructions on how to access the forced rate menu CO2 readings should be between the values shown in Table 13 If...

Page 34: ...LAARS Heating Systems Page 34 GAS TYPE HIGH FIRE CO2 LOW FIRE CO2 Natural 9 0 9 0 Propane 10 0 10 0 Table 13 CO2 Range Figure 25 Adjustment Screws and Settings for CO2...

Page 35: ...e Pump 11 2 1 Burner Check the burner for debris Remove the blower arm assembly to access the burner Remove the 4 bolts connecting the blower to the arm see Figure 32 Remove the 5 bolts which hold the...

Page 36: ...e soot deposits with a wet brush or fine water spray before servicing the heat exchanger 1 Shut off the 120 Volt power supply to the boiler 2 Turn off all manual gas valves connecting the boiler to th...

Page 37: ...um input CO2 Any high fire adjustment may affect low fire settings Screws for adjustment are shown in Figure 26 7 Reinstall front cover SECTION 12 Trouble Shooting 12 1 Sequence of Operation Mascot II...

Page 38: ...92 Outlet sensor fault 93 DHW sensor fault Faulty sensor or wiring Check wiring replace sensor condition can be 95 Stack sensor fault caused by short 96 OAT temperature sensor fault Faulty outdoor ai...

Page 39: ...values min 12 C 22 F to a difference greater than 22 F 12 C 255 CH setpoint minus ODR Increase Outdoor water min water temperature was temperature min and max too small min 12 C 22 F values to a diff...

Page 40: ...ral Information To order or purchase parts for the LAARS Mascot II contact your nearest LAARS dealer or distributor If they cannot supply you with what you need contact Customer Service see back cover...

Page 41: ...1 4 npt E2337500 8O Exchanger heat plate 8P Tie cable 14 3 4 long x 0 31 wide heat stabilized F2029100 8Q Flow switch water E2337400 8R Pipe tailpiece 1 npt M x 3 4 tube cu 12H4023 8S O ring 120 1 ID...

Page 42: ...LAARS Heating Systems Page 42 Figure 28 Panel Assembly Door Top...

Page 43: ...Mascot II Boilers and Water Heaters Page 43 Figure 29 Panel Assembly Door Middle...

Page 44: ...LAARS Heating Systems Page 44 Figure 30 Panel Assembly Door Bottom...

Page 45: ...Mascot II Boilers and Water Heaters Page 45 Figure 31 Base Jacket Assembly...

Page 46: ...LAARS Heating Systems Page 46 Figure 32 Heat Exchanger Cabinet Fan...

Page 47: ...Mascot II Boilers and Water Heaters Page 47 Figure 33 Heat Exchanger Burner Components...

Page 48: ...LAARS Heating Systems Page 48 Figure 34 Pump Assembly Components...

Page 49: ...Mascot II Boilers and Water Heaters Page 49 Figure 35 Plumbing Components...

Page 50: ...LAARS Heating Systems Page 50...

Page 51: ...Mascot II Boilers and Water Heaters Page 51...

Page 52: ...Fax 603 335 3355 Applications Engineering 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1111 Document 1230A Dime...

Reviews: