background image

Mini-Combo II

Page 5

2C. Piping

To Prevent damage to the unit, all soldering is to
be done prior to assembling the cold and hot
water, and any other connections to the tank.

Use suitable pipe dope or tape.

Before piping the boiler to the heating system,
be sure to install the system check valve
(provided with the unit) onto the inlet (return)
tee of the boiler with arrow pointed downward
(see Figure 3).

If anti-freeze is used in boiler system, local codes
may require a backflow preventer on cold supply
line. Use anti-freeze specifically intended for
hydronic heating system. Inhibited propylene
glycol is recommended.

WARNING

Do not use automotive or ethylene glycol anti-
freeze, or any undiluted anti-freeze. This can cause
severe personal injury, death or substantial property
damage.

If a backflow preventer, pressure reducing valve

or check valve is in cold water supply, install an
expansion tank on cold water supply line (Figure 4) to
prevent normal thermal expansion from repeatedly
forcing open the T&P relief valve.

T&P relief valves discharge piping must be

directed so that hot water flows away from all persons.
Attach run-off tube to T&P valve and run tube within
6" (152mm) from floor. No reducing couplings,
valves, or any other type of restriction is to be
installed in this line. This run-off tube must be
installed to allow free and complete drainage of both
valve and run-off tube.

Filling Storage Water Tank

1.

Open hot water faucet in house to allow air in the
tank and in piping to escape.

2.

Open shut-off valve(s) in cold water supply line.

3.

Open shut-off valve(s) in hot water supply line.

4.

When water discharges from the faucet, close it.
Check for system leaks and repair if necessary.

Filling and connecting boiler pipes:
Consult the JV boiler manual, Document 1025.

Caution

Never use water heater/boiler unless it is
completely filled with water.

2D. Wiring

Priority System: Under this wiring the storage

tank will be supplied before space heating. This will
insure that it gets adequate hot water flow from the
boiler to maintain a fully rated delivery of domestic
hot water.

Caution

In this priority mode, any demand for space heating
is postponed until the storage water tank has
reached set temperature. This delay in supplying
the space heating zones is usually not noticed by
the inhabitants of the living spaces. However, in the
event of certain storage water tank malfunctions,
space heating could be delayed indefinitely. If
undetected and uncorrected, freezing damage to
piping could result.

WARNING

Electrical shock can cause severe personal injury
or death. Disconnect power supply to the boiler
before doing any electrical work.

Electrical Connection: (See Figure 5, 6 and 7)

1.

Remove the two screws attaching the front cover
of the control box.

2.

There are five wires coiled in the area on the
right side of the control box, supplied with wire
nuts: 2 black wires twisted together, 2 white
wires twisted together, and a brown wire.

3.

Follow Figures 5, 6 and 7. Remove the wire nut
from the two black wires, and connect the hot
lead from a 115 volt power supply to both wires.
Secure the three wires with the wire nut.

4.

The two white, neutral wires should be joined to
the other neutral lead coming from the 115 volt
power supply, and the neutral lead coming from
the pump (space heating).

5.

The brown wire attaches to the hot side of the
space heating pump.

6.

There is a molex connector located on the left
side of the control panel. Connect the vent
damper harness to the molex connector and the
other end to the vent damper receptacle.

NOTE: The connection in step 6 should remain

intact at all times, otherwise the boiler will not fire.

Some Canadian units are supplied with vent

damper jumper plug. Do not remove jumper unless
vent damper is to be installed.

Summary of Contents for Mini-Combo II MCT

Page 1: ...loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not tou...

Page 2: ...2 LAARS HEATING SYSTEMS TABLE OF CONTENTS SECTION 1 General Information 1A Introduction 3 SECTION 2 Installation 2A Location 3 2B Heater Placement 3 2C Piping 5 2D Wiring 5 6 7 2E Sequence of Operati...

Page 3: ...hot water taps take special precautions Install an anti scald valve at water heater or at each hot water faucet bath and shower outlet Use lowest practical temperature setting Studies have indicated...

Page 4: ...318 5 127 1 274 124 100 59 1518 14 362 5 127 1 280 127 125 59 1518 14 362 6 152 1 286 130 Domestic Figure 1 Dimensional Information Figure 2 Closet Installation 7 178 Figure 4 Typical Expansion Tank I...

Page 5: ...n Never use water heater boiler unless it is completely filled with water 2D Wiring Priority System Under this wiring the storage tank will be supplied before space heating This will insure that it ge...

Page 6: ...VENTER FAN PROVING SWITCH RECEPTACLE SEE DOC 1056 P Y W Y Figure 5 Wiring Diagrams H2001600J PILOT BURNER WITH SPARK ELECTRODE SENSOR THE BOILER WILL NOT OPERATE WITHOUT THE AUTOMATIC VENT DAMPER THE...

Page 7: ...Mini Combo II Page 7 Figure 6 MCT Schematic Some Canadian units are supplied with vent damper jumper plug Do not remove jumper unless vent damper is to be installed...

Page 8: ...Page 8 LAARS HEATING SYSTEMS Figure 7 MCS Schematic Some Canadian units are supplied with vent damper jumper plug Do not remove jumper unless vent damper is to be installed...

Page 9: ...peration 115 Volts Supply Tank Stat common Domestic Demand N C Heating Demand N O Tank Pump energized High Limit Switch Vent Damper Open Power Vent Fan Switch optional Heating Pump energized Safety Li...

Page 10: ...Page 10 LAARS HEATING SYSTEMS Figure 9 Parts Identification...

Page 11: ...d Supplied Nipple Brass 1 NPT x 3 LG 27 2 20087300 Door Latch Assembly 28 1 H2020600 Logo Mini Como II 29 1 H2016800 Label Warning Installation 30 2 H0090700 Label Hot 31 not shown part not sold 32 56...

Page 12: ...CA 93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laar...

Reviews: