Page 9
N
EO
T
HERM
Boilers and Water Heaters
Setting up the Lead/Lag Master Control continues
5. A smaller box will appear on the screen. Choose the box for
“Enable”,
then press
“OK”.
6. With the Master Control now Enabled , press the setting
box labeled
“CH setpoint”.
Here you can adjust the
desired Lead/ Lag system set point.
7. Press
“Advanced Settings”
8. From this screen, use the Left or Right arrows to scroll
to other screens. Make adjustments if needed.
9. If you are using Outdoor Reset for Lead/ Lag, adjust the
Maximum Outdoor Temp, Minimum Outdoor Temp and
Low Water Temp
by touching each set point line.
The set point screen will appear. Make the adjustment,
then press OK.
When finished, press the arrow to advance to the
“Warm Weather Shutdown
” screen.
10. From the
“Warm Weather Shutdown “
screen, adjust the
setpoint.
When finished, press the arrow to advance to the
“Rate Allocation”
screen.
9