Page 60
Choose S2 (J8-6) 4-20 mA, then press OK
Then scroll over to the Modulation sub-menu and
click onto Modulation rate source.
Select Local, then press OK.
8.G.3
Outdoor Reset Configuration
At this sub-menu, confirm that Central Heat is Enabled.
Next, press onto the Maximum Outdoor Temperature,
Minimum Outdoor Temperature, and Low Water
Temperature to get to each and adjusting their setpoints in
those sub-menus.
8.G.4
DHW - Domestic Hot Water Config
DHW - Domestic Hot Water is used to configure the
DHW temperature parameters for water heaters
(Heater) and for indirect water heaters that are used
with boiler (Boiler) systems.
Press on the Setpoint box to get to the adjustment sub-
menu. Then adjust it up or down to your desired DHW
setpoint.
8.G.5
Warm Weather Shutdown Config
From this sub-menu you will be able to enable/disable the
Warm Weather Shutdown feature and adjust the set point.
LAARS Heating Systems
Summary of Contents for Neotherm NTH
Page 4: ...LAARS Heating Systems...
Page 36: ...Page 36 Figure 22 Hydronic Piping Single Boiler Zoning with Circulators LAARS Heating Systems...
Page 52: ...Page 52 Figure 36 Ladder Diagram 7 H Ladder Diagram LAARS Heating Systems...
Page 100: ...Page 100 Parts Illustration 4 Internal Components Sizes 750 850 LAARS Heating Systems...
Page 102: ...Page 102 Parts Illustration 6 Gas Train Components Sizes 600 850 LAARS Heating Systems...