Page 75
Figure 46. Gas Valve 399 - 500
Mbtu
GAS TYPE HIGH FIRE, CO
2
LOW FIRE,
CO
2
MANIFOLD
PRESSURE
Natural
8.8 to 9.0%
0.5% lower than
-.005” to
Propane
9.8 to 10.0%
high fire setting
-.015” wc
Table 19. Commercial, sizes 399 - 850 Mbtu CO
2
Range and Manifold Pressure
399
500
The Gas Valve in the
399 and 500
is at the front of the
unit and can be reached after the front panel is pulled
forward and then off.
Always be patient with your combustion analyzer
when making adjustments to the valve at both Hi-Fire
and Low-Fire.
N
EO
T
HERM
Commercial Boilers and Water Heaters