Page 44
LAARS Heating Systems
Menu 7.
Safety Parameter Confirmation
5. For each group, check the list carefully. Press
Yes if all of the parameters in the group have
been entered correctly. For each group, you are
given 30 seconds to select Yes/No.
A count-down timer is shown at the bottom of
the screen.
If you made changes in other safety-related
groups, verify the entries in those groups in the
same way. Do this until the following screen
shows
Menu 8.
Safety Parameter Reset
6. When the process is complete, the system will
tell you to reset the control system. The Reset
button is located on the front of the controller.
You must press the Reset button within 30
seconds, or the verification will be cancelled. A
count-down timer is shown at the bottom of the
screen.
8.4 Checking Individual Parameters
1. From the ‘Home’ screen (Menu 9), press the
icon for the controller.
Menu 9.
‘Home’ screen
2. The Status Summary page for the controller
will appear. This shows the current operating
condition of the controller, and also shows some
of the configuration settings.
See Menu 10
Menu 10.
Status Summary Screen
Notice the four buttons at the bottom of each
Status Summary screen:
• Configure – Allows an installer to change
some of the setup parameters used by the
system. A password may be required.
• Operation – Used to adjust the setpoints,
change the fan speed, turn a burner on or off,
or turn the pumps on or off.
• Diagnostics – Allows you to run diagnostic
tests, or check the inputs and outputs used by
the system.
• Details – Allows you to check the status of all
of the setup parameters on the control system.
Summary of Contents for NTH
Page 4: ...LAARS Heating Systems...
Page 13: ...Page 9 NEOTHERM Boilers and Water Heaters 38 1 2 98 8 3 4 22 7 1 2 19 64...
Page 30: ...Page 26 LAARS Heating Systems Figure 21 Hydronic Piping Single Boiler Zoning with Circulators...
Page 86: ...Page 82 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Page 88: ...Page 84 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Page 90: ...Page 86 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Page 93: ...Page 89 NEOTHERM Boilers and Water Heaters Notes...
Page 94: ...Page 90 LAARS Heating Systems Notes...
Page 95: ...Page 91 NEOTHERM Boilers and Water Heaters Notes...