Page 58
LAARS Heating Systems
500
399
GAS TYPE
HIGH FIRE, CO
2
LOW FIRE, CO
2
DIFFRNTL PRESSURE
(
inches wc
)
Natural
8.8 to 9.8%
0.5% lower than
3.6” to 3.9”
Propane
9.8 to 10.2%
high fire setting
Table 17. (Residential, sizes 150 - 285 Mbtu)
CO
2
Range and Differential Pressure
GAS TYPE
HIGH FIRE, CO
2
LOW FIRE, CO
2
MANIFOLD
PRESSURE
Natural
8.8 to 9.0%
0.5% lower than
-.005” to
Propane
9.8 to 10.0%
high fire setting
-.015” wc
150–285
Figure 46.
NeoTherm Gas Valves (ALL)
Outlet Gas
Pressure
(manifold
pressure)
8.10.2 – Adjusting CO
2
See Section 8.10
Table 18. (Commercial, sizes 399 - 850 Mbtu)
CO
2
Range and Manifold Pressure