LAARS Heating Systems
Page 6
Section 2
loCatInG tHe UnIt
2.1
locating the Unit
The NeoTherm unit may be installed indoors or
outdoors. The unit may only be installed outdoors
in a location which will never experience freezing
temperatures. Choose a location for the unit which
allows clearances on all sides for maintenance and
inspection. See Table 1. Always install the unit on a
firm, level surface. Level the unit using the leveling
feet.
The unit should not be located in an area where
leakage of any connections will result in damage to
the area adjacent to the appliance, or to lower floors
of the structure.
When this type of location is not available, install
a suitable drain pan, adequately drained, under the
appliance.
The appliance is design-certified by CSA-
International for installation on combustible flooring;
in basements; in closets, utility rooms or alcoves
.
NeoTherm boilers must never be installed on
carpeting.
The location for the appliance should
be chosen with regard to the vent pipe lengths and
external plumbing.
The unit shall be installed such that the gas ignition
system components are protected from water
(dripping, spraying, rain, etc.) during operation and
service (circulator replacement, control replacement,
etc.).
When vented vertically, the NeoTherm must be
located as close as practical to the vertical section
of the vent. If the vent terminal and/or combustion
air terminal terminate through a wall, and there is
potential for snow accumulation in the local area,
both terminals should be installed at an appropriate
level above grade or the maximum expected snow
line.
The dimensions and requirements that are shown in
Table 1 should be met when choosing the locations
for the appliance.
2.2
locating Unit for Correct Vent
Distance from outside Wall or
roof termination
The forced draft combustion air blower in the
appliance has sufficient power to vent properly when
the guidelines in Table 2
are followed.
note -
When located on the same wall, the
NeoTherm combustion air intake terminal must
be installed a minimum of 12” below the exhaust
terminal. There must also be a minimum horizontal
APPLIANCE
SUGGESTED SERVICE ACCESS CLEARANCE
SURFACE
InCHeS
cm
Front
24
60.9
Left Side
12
30.5
Right Side
18
45.7
Back
24
60.9
Top
24
60.9
APPLIANCE
REQUIRED CLEARANCE TO COMBUSTIBLES
SURFACE
InCHeS
cm
Front
2
5.1
Left Side
0
0
Right Side
0
0
Back
0
0
INTAKE / EXHAUST
STANDARD
MAX EQUIV.
SIZE VENT
ft.
m
1000 6”
100
30
Installations in the U.S. require exhaust vent pipe that is PVC or
CPVC complying with ANSI/ASTM D1785 F441, polypropylene
complying with ULC-S636, or stainless steel complying with
UL1738. Installations in Canada require exhaust vent pipe that is
certified to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with ANSI/
ASTM D1785 F441, ABS that complies with ANSI/ASTM D1527,
stainless steel, or galvanized material.
Closet and alcove installations do not allow the use of PVC under
any circumstances
To calculate max equivalent length, measure the linear feet of the
pipe, and add 5 feet
(1.5 m)
for each elbow used.
table 2 - Vent / air Pipe Sizes
table 1 - Clearances
distance from intake to the exhaust terminal of 36.”
For concentric vent terminal kit (optional), follow
installation instructions included with the kit.
Summary of Contents for NTV1000
Page 2: ......
Page 35: ...NeoTherm Boilers and Water Heaters Page 31 Fig 20 Ladder Diagram...
Page 36: ...LAARS Heating Systems Page 32 Fig 21 Wiring Diagram...
Page 37: ...NeoTherm Boilers and Water Heaters Page 33...
Page 51: ...NeoTherm Boilers and Water Heaters Page 47 Fig 52 Connection Terminals...
Page 130: ...LAARS Heating Systems Page 126 Fig 140 Machine Frame and Rear Panel 13 3 PARTS ILLUSTRATIONS...
Page 131: ...NeoTherm Boilers and Water Heaters Page 127 Fig 141 Front Panel and Covers...
Page 132: ...LAARS Heating Systems Page 128 Fig 142 Burners and Combustion Chambers...
Page 134: ...LAARS Heating Systems Page 130 Fig 145 Electronic Components...
Page 135: ...NeoTherm Boilers and Water Heaters Page 131 Fig 146 Condensate Trap Fig 147 Control Bezel...
Page 136: ...LAARS Heating Systems Page 132 Fig 148 Flow Switch...
Page 137: ...NeoTherm Boilers and Water Heaters Page 133 This page intentionally left blank...