LAARS Heating Systems
Page 104
Code Description
L or
H
Procedure
26
Internal fault:
Static flame ripple
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
27
Internal fault:
Flame rod shorted to ground detected
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
28
Internal fault:
A/D linearity test fails
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
29
Internal fault:
Flame bias cannot be set in range
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
30
Internal fault:
Flame bias shorted to adjacent pin
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
31
Internal fault:
SLO electronics unknown error
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
32-
46
Internal fault:
Safety Key 0 through 14
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
47
Flame Rod to ground leakage
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
48
Static flame (not flickering)
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
49
24 VAC voltage low/high
H
1. Check the module and display connections.
2. Check the module power supply and make
sure that frequency, voltage and VA meet the
specifications.
50
Modulation fault
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
51
Pump fault
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
52
Motor tachometer fault
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
Summary of Contents for NTV1000
Page 2: ......
Page 35: ...NeoTherm Boilers and Water Heaters Page 31 Fig 20 Ladder Diagram...
Page 36: ...LAARS Heating Systems Page 32 Fig 21 Wiring Diagram...
Page 37: ...NeoTherm Boilers and Water Heaters Page 33...
Page 51: ...NeoTherm Boilers and Water Heaters Page 47 Fig 52 Connection Terminals...
Page 130: ...LAARS Heating Systems Page 126 Fig 140 Machine Frame and Rear Panel 13 3 PARTS ILLUSTRATIONS...
Page 131: ...NeoTherm Boilers and Water Heaters Page 127 Fig 141 Front Panel and Covers...
Page 132: ...LAARS Heating Systems Page 128 Fig 142 Burners and Combustion Chambers...
Page 134: ...LAARS Heating Systems Page 130 Fig 145 Electronic Components...
Page 135: ...NeoTherm Boilers and Water Heaters Page 131 Fig 146 Condensate Trap Fig 147 Control Bezel...
Page 136: ...LAARS Heating Systems Page 132 Fig 148 Flow Switch...
Page 137: ...NeoTherm Boilers and Water Heaters Page 133 This page intentionally left blank...