Do not use automotive antifreeze. To help prevent
freezing, Laars recommends the use of inhibited
glycol concentrations between 20% and 35% glycol.
Typically, this concentration will serve as burst
protection for temperatures down to approximately
-5°F (-20°C). If temperatures are expected to be
lower than -5°F (-20°C), glycol concentrations up
to 50% can be used.
When concentrations greater
than 35% are used, water flow rates must be
increased to maintain a 20°F to 25°F temperature
rise through the boiler.
Different glycol products may provide varying
degrees of protection. Glycol products must
be maintained properly in a heating system, or
they may become ineffective. Consult the glycol
specifications, or the glycol manufacturer, for
information about specific products, maintenance
of solutions, and set up according to your particular
conditions.
The following manufacturers offer glycols,
inhibitors, and anti foamants that are suitable for use
in the NeoTherm. Please refer to the manufacturers
instructions for proper selection and application.
• Sentinel Performance Solutions Group
• Hercules Chemical Company
• Dow Chemical Company
6a.4 ntH Suggested Piping Schematics
Figures 11 through 15 show suggested piping
configurations for NTH boilers. These diagrams
are only meant as guides. All components or piping
required by local code must be installed.
Summary of Contents for NTV1000
Page 2: ......
Page 35: ...NeoTherm Boilers and Water Heaters Page 31 Fig 20 Ladder Diagram...
Page 36: ...LAARS Heating Systems Page 32 Fig 21 Wiring Diagram...
Page 37: ...NeoTherm Boilers and Water Heaters Page 33...
Page 51: ...NeoTherm Boilers and Water Heaters Page 47 Fig 52 Connection Terminals...
Page 130: ...LAARS Heating Systems Page 126 Fig 140 Machine Frame and Rear Panel 13 3 PARTS ILLUSTRATIONS...
Page 131: ...NeoTherm Boilers and Water Heaters Page 127 Fig 141 Front Panel and Covers...
Page 132: ...LAARS Heating Systems Page 128 Fig 142 Burners and Combustion Chambers...
Page 134: ...LAARS Heating Systems Page 130 Fig 145 Electronic Components...
Page 135: ...NeoTherm Boilers and Water Heaters Page 131 Fig 146 Condensate Trap Fig 147 Control Bezel...
Page 136: ...LAARS Heating Systems Page 132 Fig 148 Flow Switch...
Page 137: ...NeoTherm Boilers and Water Heaters Page 133 This page intentionally left blank...