In this example, we are still working with the
Primary control for Boiler 1. From the table,
you can see that this control should have a flap
valve ID of “1.” Enter the correct ID from
Table 5 in this field. The system will ask you
to login before you do this.
WarnInG
If the controller cannot find a signal from one
of the flap valves, the control system will act to
prevent backflow by energizing the blower of the
control with the bad flap valve. If this cannot be
done the control will not allow the whole system to
run. For this reason, it is important that all of the
flap valves be identified correctly.
7. At this point, you have set the flap valve ID’s
for both controllers on this boiler. Before you
leave, you must finish the verification process,
or the control system will not let the boiler
operate.
Press the Back arrow to return to the
Configuration screen.
Fig. 75 – Configuration Screen
8. In a moment, you will need to reset the
controller by pressing a button on the front of
the unit. See Fig. 76. The controllers for the
two boilers are mounted behind the door on
the front of the unit.
fig. 76 – reset Button on Controller
The control system allows 30 seconds to press
the reset button. Do not press the Reset button
yet! You will need to do this in a moment.
At this point, we just want to alert you to
something: In order to be able to reach the
controller within 30 seconds, it will be helpful
to open the door and slide out the control panel
first.
When you are ready, press the Verify button on
the Configuration screen.
9. To begin the verification, login to the system
and press Begin.
fig. 77 – edit Safety Data
10. The system will present a listing of a group
which includes the parameter you changed (the
flap valve ID). See Fig. 78.
Summary of Contents for NTV1000
Page 2: ......
Page 35: ...NeoTherm Boilers and Water Heaters Page 31 Fig 20 Ladder Diagram...
Page 36: ...LAARS Heating Systems Page 32 Fig 21 Wiring Diagram...
Page 37: ...NeoTherm Boilers and Water Heaters Page 33...
Page 51: ...NeoTherm Boilers and Water Heaters Page 47 Fig 52 Connection Terminals...
Page 130: ...LAARS Heating Systems Page 126 Fig 140 Machine Frame and Rear Panel 13 3 PARTS ILLUSTRATIONS...
Page 131: ...NeoTherm Boilers and Water Heaters Page 127 Fig 141 Front Panel and Covers...
Page 132: ...LAARS Heating Systems Page 128 Fig 142 Burners and Combustion Chambers...
Page 134: ...LAARS Heating Systems Page 130 Fig 145 Electronic Components...
Page 135: ...NeoTherm Boilers and Water Heaters Page 131 Fig 146 Condensate Trap Fig 147 Control Bezel...
Page 136: ...LAARS Heating Systems Page 132 Fig 148 Flow Switch...
Page 137: ...NeoTherm Boilers and Water Heaters Page 133 This page intentionally left blank...