NeoTherm Boilers and Water Heaters
Page 3
1.3
Safety notes
WarnInG
Fire or Explosion Hazard
Improper configuration can cause fuel buildup and
explosion. Improper user operation may result in
property loss, severe physical injury, or death.
Any changes to safety-related configuration
parameters must only be done by experienced and/or
licensed burner/boiler operators and mechanics.
If any odor of gas is detected, or if the gas burner
does not appear to be functioning in a normal
manner,
close the main gas shutoff valve
. Do not
shut off the power switch. Contact your heating
contractor, gas company, or factory representative.
The NeoTherm unit is protected against over-
pressurization. A pressure relief valve is included
with each NeoTherm.
The inlet gas pressure to the appliance must not
exceed 13” W.C. (3.2 kPa).
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-
Latest Edition “National Fuel Gas Code” or 2) CSA
B149.1 “Natural Gas and Propane Installation Code”
and with the requirement of the local utility or other
authorities having jurisdiction. Such applicable
requirements take precedence over the general
instructions contained herein.
WarnInG
Carbon Monoxide Hazard
Improper adjustment of the burners may lead to poor
combustion quality, increasing the amount of carbon
monoxide produced. Excessive carbon monoxide
levels may lead to personal injury or death.
WarnInG
Electrical Shock Hazard
Electrical shock can cause severe injury, death or
property damage. Disconnect the power supply
before beginning installation or changing the
wiring to prevent electrical shock or damage to the
equipment. It may be necessary to turn off more than
one power supply disconnect.
All electrical wiring is to be done in accordance with
local codes, or in the absence of local codes, with:
1) The National Electrical Code ANSI/NFPA No.
70 - latest Edition, or 2) CSA STD. C22.1 “Canadian
Electrical Code - Part 1.” This appliance must be
electrically grounded in accordance with these
codes.
1.4
Model Identification
Consult the rating plate on the unit. The following
information describes the model number structure.
(1-2)
model Series Designation
N T = NeoTherm
(3)
Usage
H = Hydronic
V = Volume Water
(4-7)
Size
1 0 0 0 = 1,000,000 BTU/hr input
(8)
fuel
N = Natural Gas
P = LP Gas
(9)
options Code
J = CSD1 Version
X = Standard Unit
(10)
Pump options
X = No pump
(configuration available for all sizes)
(11)
revision
1 = First version
1.5
Unit overview
See Figure 4.
model nomenclature
1 2 3
4 5 6
8
9
10
11
N T H
1
SERIES
n t
USAGE
H -
HYDRONIC
V -
VOLUME
WATER
SIZE
MBTU/h
1 0 0 0
FUEL
n -
NATURAL
P -
PROPANE
OPTIONS CODE
J
- CSD1
X -
STANDARD
PUMP OPTIONS
X -
NO PUMP
REVISION
1 -
FIRST
7
Summary of Contents for NTV1000
Page 2: ......
Page 35: ...NeoTherm Boilers and Water Heaters Page 31 Fig 20 Ladder Diagram...
Page 36: ...LAARS Heating Systems Page 32 Fig 21 Wiring Diagram...
Page 37: ...NeoTherm Boilers and Water Heaters Page 33...
Page 51: ...NeoTherm Boilers and Water Heaters Page 47 Fig 52 Connection Terminals...
Page 130: ...LAARS Heating Systems Page 126 Fig 140 Machine Frame and Rear Panel 13 3 PARTS ILLUSTRATIONS...
Page 131: ...NeoTherm Boilers and Water Heaters Page 127 Fig 141 Front Panel and Covers...
Page 132: ...LAARS Heating Systems Page 128 Fig 142 Burners and Combustion Chambers...
Page 134: ...LAARS Heating Systems Page 130 Fig 145 Electronic Components...
Page 135: ...NeoTherm Boilers and Water Heaters Page 131 Fig 146 Condensate Trap Fig 147 Control Bezel...
Page 136: ...LAARS Heating Systems Page 132 Fig 148 Flow Switch...
Page 137: ...NeoTherm Boilers and Water Heaters Page 133 This page intentionally left blank...