NeoTherm Boilers and Water Heaters
Page 95
power supply to the boiler. Turn off all manual gas
valves connecting the boiler to the main gas supply
line. Remove the front door of the boiler to gain
access to the gas valve and Venturi. Disconnect the
four flange bolts connecting the gas manifold pipe
to the gas valve. Remove the electrical connections
to the gas valve. Remove the bolts connecting the
Venturi flange to the blower. This allows the entire
gas valve/Venturi assembly to be removed as an
assembly to facilitate inspection and cleaning.
After the valve has been removed, reassemble in
reverse order making sure to include all gaskets and
O-rings. Turn on the manual gas valves and check
for gas leaks. Turn on the 120 Volt power. Place the
unit in operation following the instructions in Section
10. Once the boiler is operating, check for leaks
again and confirm all fasteners are tight.
Check the setup for the unit according to the
instructions in Section 9.
11.2.3 Controllers
Each NeoTherm unit has two integrated controllers
that incorporate manual reset high limit control,
operating temperature control, modulating control,
ignition control, outdoor reset control, pump control
and many other features. If any of these features are
thought to be defective, please consult the factory for
proper troubleshooting practices before replacing a
control.
If it is necessary to replace a controller, turn off
all power to the unit and shut off all manual gas
valves to the unit. Remove the front door to the
unit and the control panel plastic bezel. Remove
all wire connections from the control board. The
control board connections are keyed to only allow
connection in the proper location, but proper
handling techniques should be used to avoid damage
to the wiring or connectors. To remove the control,
undo the mounting screws. To replace the control
repeat the steps listed above in the reverse order
making sure to connect all wires in the proper
locations. Place the unit in operation following the
steps outlined in Section 10.
11.2.4 Ignitor assembly
The ignitor assembly is a two rod system that
consists of a ground rod and a sense rod. To remove
the ignitor assembly, shut off the 120 Volt power
supply to the unit. Turn off all manual gas valves
connecting the unit to the main gas supply line.
Remove the front door of the boiler to gain access
to the ignitor assembly. Remove the two wires
connected to the assembly. Then remove the two
bolts connecting the ignitor assembly to the burner
door. Remove and replace the old ignitor assembly
gasket. If the old assembly is determined to be
defective, install a new ignitor assembly in the
reverse order. Replace the gasket if necessary.
11.2.5 flame Sensor
The flame sensor is a single rod system. To replace
the flame sensor electrode, shut off the 120 Volt
power supply to the boiler. Turn off all manual gas
valves connecting the boiler to the main gas supply
line. Remove the front door of the boiler to gain
access to the flame sensor electrode. Remove the
flame sensor wire from the electrode. Remove the
two bolts fastening the electrode to the burner doors.
Remove and replace the old flame sensor gasket.
If the old electrode is determined to be defective,
reinstall a new flame sensor electrode in the reverse
order.
Caution
The igniters and sensors get become very hot. If
you touch these parts accidentally, this can cause
burns or injury.
11.2.6 transformer with Integral Circuit
Breaker
The appliance has a 24 VAC transformer with
integral 4 amp circuit breaker installed for supplying
the control voltage required for the unit only. The
transformer is sized for the load produced by the
unit only and should not be used to supply power
to additional field devices. If additional loads are
added or a short occurs during installation, the
integral circuit breaker may trip. If this happens, be
sure to reset the circuit breaker before replacing the
transformer.
If the transformer must be replaced, turn off the 120
VAC power to the unit. Remove the transformer
wires from the terminal blocks. Remove the
fasteners holding the transformer, and remove the
transformer. Replace with a new transformer in
reverse order.
If the transformer is replaced with a part other
than the OEM transformer, be sure to add circuit
protection if it is not integral to the new transformer.
WarnInG
Failure to include proper circuit protection may
lead to premature component failure, fire, injury or
death.
Summary of Contents for NTV1000
Page 2: ......
Page 35: ...NeoTherm Boilers and Water Heaters Page 31 Fig 20 Ladder Diagram...
Page 36: ...LAARS Heating Systems Page 32 Fig 21 Wiring Diagram...
Page 37: ...NeoTherm Boilers and Water Heaters Page 33...
Page 51: ...NeoTherm Boilers and Water Heaters Page 47 Fig 52 Connection Terminals...
Page 130: ...LAARS Heating Systems Page 126 Fig 140 Machine Frame and Rear Panel 13 3 PARTS ILLUSTRATIONS...
Page 131: ...NeoTherm Boilers and Water Heaters Page 127 Fig 141 Front Panel and Covers...
Page 132: ...LAARS Heating Systems Page 128 Fig 142 Burners and Combustion Chambers...
Page 134: ...LAARS Heating Systems Page 130 Fig 145 Electronic Components...
Page 135: ...NeoTherm Boilers and Water Heaters Page 131 Fig 146 Condensate Trap Fig 147 Control Bezel...
Page 136: ...LAARS Heating Systems Page 132 Fig 148 Flow Switch...
Page 137: ...NeoTherm Boilers and Water Heaters Page 133 This page intentionally left blank...