LAARS Heating Systems
Page 4
All installations must be made in accordance
with:
1) In the U.S., the " National Fuel Gas Code "ANSI
Z223.1/NFPA54, Latest Edition and all applicable
local codes as required by the Authorities Having
Jurisdiction (AHJ), or
2) In Canada, the "Natural Gas and Propane
Installation Code", CSA B149.1, latest edition and all
applicable local codes as required by the AHJ.
All electrical wiring is to be done in accordance with:
1). In the U.S., the "National Electrical Code" (NEC),
ANSI/NFPA 70, latest Edition and all applicable local
codes as required by the AHJ, or
2). In Canada, the “Canadian Electrical Code - Part
1”, CSA STD. C22.1 and all applicable local codes as
required by the AHJ.
This appliance must be electrically grounded in
accordance with the applicable codes and standards
referenced above.
1.2 Model Identification
Consult the rating plate on the unit. The
following information describes the model number
structure.
Model Character Designation
1-3 Model Series Designation
P N C = Pennant
4 Usage
H = Hydronic
V = Volume Water
5-8 Size
0 5 0 0 = 500,000 BTU/h input
0 7 5 0 = 750,000 BTU/h input
1 0 0 0 = 999,000 BTU/h input
1 2 5 0 = 1,250,000 BTU/h input
1 5 0 0 = 1,500,000 BTU/h input
1 7 5 0 = 1,750,000 BTU/h input
2 0 0 0 = 1,999,000 BTU/h input
9 Fuel
N = Natural Gas
P = Propane
10 Altitude
A = 0-10,000 feet
11 Location
C = Indoor and Outdoor
12 Firing Mode
C = On-Off
13 Revision
2 = Revision Level 2
14 Heat Exchanger
B = Glass-lined CI / copper / brz trim (std. PNCV)
C = Glass-lined cast iron / copper (std. PNCH)
N = Glass-lined cast iron / cu-nickel
P = Glass-lined cast iron / cu-nickel / brz trim
15 Option Code
X = Standard Low Temp Control
J = CSD-1, FM, IRI, IL
16 Pump Options
H = TACO, Hard water pump (PNCV only)
N = TACO, Normal water pump
S = TACO, Soft water pump (PNCV only)
C = B&G, Hard water pump (PNCV only)
B = B&G, Normal water pump
D = B&G, Soft water pump (PNCV only)
1.3 Warranty
Laars Heating Systems’ appliances are covered
by a limited warranty. Owners should submit online
warranty registration at
www.Laars.com
.
All warranty claims must be made to an authorized
Laars Heating Systems representative, directly to
Customer Service, or online at
www.Laars.com
.
Claims must include the serial number and model
(this information can be found on the rating plate),
installation date, and name of the installer. Shipping
costs are not included in the warranty coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
filed with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
1.4 Dimensions
See Figure 1.
1.5 Locating the Appliance
The appliance should be located to provide
clearances on all sides for maintenance and inspection.
It should not be located in an area where leakage of
any connections will result in damage to the area
adjacent to the appliance or to lower floors of the
structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
The appliance is design certified by CSA-
International for installation on combustible flooring;
in basements; in closets, utility rooms or alcoves
.
Pennant Boilers or Water Heaters must never be
installed on carpeting.
The location for the appliance
should be chosen with regard to the vent pipe lengths
and external plumbing. The unit shall be installed such
that the gas ignition system components are protected
from water (dripping, spraying, rain, etc.) during
operation and service (circulator replacement, control
replacement, etc.). When vented vertically, the Pennant
must be located as close as practical to a chimney or
outside wall. If the vent terminal and/or combustion
air terminal terminate through a wall, and there is
potential for snow accumulation in the local area, both
terminals should be installed at an appropriate level
Summary of Contents for Pennant PNCH
Page 23: ...Low Temperature Pennant Page 23 Figure 12 Ladder Diagram Sizes 500 1000 ...
Page 24: ...LAARS Heating Systems Page 24 Figure 13 Ladder Diagram Sizes 1250 2000 ...
Page 25: ...Low Temperature Pennant Page 25 Figure 14 Wiring Diagram Sizes 500 1000 ...
Page 26: ...LAARS Heating Systems Page 26 Figure 15 Wiring Diagram Sizes 1250 1500 ...
Page 27: ...Low Temperature Pennant Page 27 Figure 16 Wiring Diagram Sizes 1750 2000 ...