background image

Pennant Pool Heater

Page 13

Figure 6). The LCD screen will display the pool loop
return temperature during normal operation. When the
control is first powered up, it displays 

. It then

displays the temperature at the pool loop sensor. After
the temperature is displayed, the current settings
(parameters) may be viewed. To scroll through the
parameters, press the down arrow button to advance to
the next parameter.

5.3.2 Programming Control Parameters

There are thirteen (13) control parameters. Only

three (3) of those should be set, LSP, dLS and Pd. The
remaining parameters are factory set and should not be
changed.

The pool loop temperature (desired pool

temperature) is set by changing the LSP parameter.
After scrolling through the parameters until LSP is
displayed, press the enter button. The setpoint will be
displayed. Press the up arrow or down arrow buttons
until the desired setpoint is displayed. Press the enter
button and the setpoint will be activated. The display
will return to indicating the present pool loop
temperature.

In addition to the ability to set the pool loop

temperature, the differential associated with that
setting may also be adjusted. The differential is set by
changing the dLS parameter. After scrolling through
the parameters until dLS is displayed, press the enter
button. The setpoint will be displayed. Press the up
arrow or down arrow buttons until the desired setpoint
is displayed. Press the enter button and the setpoint
will be activated. The display will return to indicating
the present pool loop temperature.

The last parameter that may be adjusted is Pd,

the pump off delay. After again scrolling through the
parameters until Pd is displayed, press the enter
button. The pump delay time will be displayed. The
pump off delay may be set between 0.1 and 10
minutes. Press the up arrow or down arrow buttons
until the desired setpoint is displayed. Press the enter
button and the setpoint will be activated. The display
will again return to indicating the present pool loop
temperature.

Figure 6. Pool Heater Controller.

5.1 Main Power

Pennant appliances are fitted with pigtail leads

for main power connection. Connect a fused 15-
ampere, 120-volt supply to the black wire. Neutral leg
is connected directly to the white wire. Ground wire is
connected to the green wire.

Wiring diagrams are shown in Section 10 in

Figures 12 through 15. Field wiring is shown in
Section 10 in Figures 16 and 17.

IMPORTANT NOTE: If the backwash operation is
manual the heater must be shut off manually during
backwashing.

Auxiliary Time Clock Wiring:

If a time clock is used to control the pool filter

pump operation, a separate switch or relay must be
used to shut off heater at least 15 minutes before the
filter pump is shut off.  Wire the switch or relay to the
field-wiring board’s “Other Ints” terminals. Wire the
switch or relay to the field-wiring board’s “Other Ints”
terminals, after removing the factory-installed jumper.

All field-installed electrical safety devices and

field-installed controllers can be connected in series to
the Pennant’s “Other Ints” terminals on the field-
wiring board (remove the factory-installed jumper).

5.2 Temperature (Operating) Control

The Pennant temperature control operates by

measuring the pool loop return temperature, before the
heater inlet piping. It is adjustable to a maximum of
104° F and will prevent heater operation at return
temperatures above 104° F. It also controls the pool
heater pump and the temperature of the water entering
the heat exchanger. It also controls the Pennant pump
operation and the mixing system, which tempers the
water entering the heat exchanger to prevent damage
from condensation. The sensors for the control are
installed as shown in Figure 5 and Section 4.3, Sensor
Locations. The automatic mixing system sensor,
already installed, is shown in Figure 4. During
operation, the automatic mixing system diverts water
from the outlet to the inlet to “pre warm” the water to
a minimum inlet temperature of 120°F. This prevents
condensation from forming, which can damage the
heater.

5.3 Programming the Temperature

Control

5.3.1 Temperature Control Overview

The digital display on the control has the

following uses:

To display the actual pool loop temperature
during normal operating mode.

To allow the user to view and adjust the
control settings.

Figure 6 identifies the control buttons.
The Pool Heater Temperature Control face

contains an LCD screen and four (4) buttons (see

Summary of Contents for Pennant PNCP

Page 1: ...alified in hot water boiler installation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death...

Page 2: ...amming Control Parameters 13 5 3 3 Setpoint LSP 14 5 3 4 Differential dLS 14 5 3 5 Pump Operation 14 5 3 6 Heater Purge Pump Delay PD 14 5 4 Limit Controls 14 SECTION 6 Operating Instructions 6 1 Sequ...

Page 3: ...oper installation The Pennant appliance is protected against over pressurization A pressure relief valve is fitted to all appliances It is installed on the outlet header at the water outlet of the app...

Page 4: ...age to the area adjacent to the appliance or to lower floors of the structure When such a location is not available it is recommended that a suitable drain pan adequately drained be installed under th...

Page 5: ...86 101 8 26 30 78 29 75 8 22 8 22 80 203 8 20 12 30 8 20 1500 78 199 39 101 101 8 26 30 78 29 75 8 22 8 22 91 231 8 20 12 30 8 20 1750 89 226 44 113 101 8 26 30 78 29 75 8 22 8 22 101 256 8 20 14 36...

Page 6: ...er may result SECTION 2 Venting and Combustion Air 2 1 Combustion Air Pennant pool heaters must have provisions for combustion and ventilation air in accordance with section 5 3 Air for Combustion and...

Page 7: ...ke to the heater as directly as possible Seal all joints with tape Provide adequate hangers The unit must not support the weight of the combustion air intake pipe Maximum linear pipe length allowed is...

Page 8: ...dition to following proper vent sizing construction and safety requirements from the National Fuel Gas Code ANSI Z223 1 or in Canada from CSA B149 1 as well as all applicable local codes it is require...

Page 9: ...possible locations under windows or near doors should be avoided 4 Locate the vent terminal so that it cannot be blocked by snow The National Fuel Gas Code requires that it be at least 12 inches 30 c...

Page 10: ...door Units For outdoor applications the vent and combustion air openings must be covered with proper terminals to prevent rain snow and other objects from falling into the Pennant Part numbers for the...

Page 11: ...line must be firing at maximum capacity to properly measure the inlet supply pressure The pressure can be measured at the supply pressure port on the gas valve Low gas pressure could be an indication...

Page 12: ...er outlet This sensor is a capillary and bulb It shall be used with the immersion well that is provided Figure 5 Pool Heater Piping The Pennant Pool Heater is shipped with a field installed mixing sys...

Page 13: ...wer connection Connect a fused 15 ampere 120 volt supply to the black wire Neutral leg is connected directly to the white wire Ground wire is connected to the green wire Wiring diagrams are shown in S...

Page 14: ...6 Operating Instructions 6 1 Sequence of Operation The amber Ready light on the front panel indicates that the control system is energized Upon a call for heat from the pool temperature control the gr...

Page 15: ...0 to 2500 Feet Altitude The setup must be checked before the unit is put in operation Problems such as failure to start rough ignition strong exhaust odors etc can be due to improper setup Damage to...

Page 16: ...ignition control label c Open gas shutoff valve Restart the appliance The ignition sequence will start again and the burner will start The appliance will return to its previous mode of operation NOTE...

Page 17: ...ated temperatures in spas and hot tubs can be hazardous Follow these Safety Rules for Hot Tubs Spa or hot tub water temperatures should never exceed 104 F 40 C A temperature of 100 F 38 C is considere...

Page 18: ...e the retainer clip and the control Replace in reverse order 7 2 7 Ignition Controls The ignition controls ensure the proved interrupted type ignition system They control the hot surface ignitor s and...

Page 19: ...nt rear and bottom of the integral metal sections and remove the heat controls the blower s pre purge and post purge Pennant models 500 750 and 1000 have one ignition control Models 1250 1500 1750 and...

Page 20: ...y adjusting the air shutter s at the bottom of the fan s Check the CO2 and adjust the air shutters if further adjustment to the CO2 is needed Models 1250 1500 1750 and 2000 have two blowers and two ai...

Page 21: ...and not at the light blue wire on that connector replace the control 8 6 Troubleshooting Pennant Controls The Pennant series consists of three models with one ignition module 500 750 1000 and four mod...

Page 22: ...placement Parts Only genuine Laars replacement parts should be used 9 1 General Information To order or purchase parts for the Laars Pennant contact your nearest Laars dealer or distributor If they ca...

Page 23: ...op 5C2002 5C2002 5C2002 5C2002 5C2002 5C2002 5C2002 24 Exhaust Plenum 5C2007 10C2007 10C2007 20C2007 20C2007 20C2007 20C2007 25 Bracket Chamber Front 5C2009 7C2009 10C2009 25 Bracket Chamber Front Lef...

Page 24: ...401 20255401 20255401 20255401 20255401 20255401 20255401 49 Relief Valve 75 PSI A0063300 A0063300 A0063600 A0063600 A0063600 A0063600 A0002700 50 Tee Adapter Outlet Bronze 20150301 20150301 20150301...

Page 25: ...700 E2310700 E2310700 74 Transformer E2108700 E2108700 E2108700 E2310400 E2310400 E2310400 E2310400 75 Switch Rocker E2106600 E2106600 E2106600 E2106600 E2106600 E2106600 E2106600 Sensor E2314300 E231...

Page 26: ...0 1 1 2 1 1 81 Burner Tray Manifold 3 Burners Left L2012800 L2012800 L2012800 L2012800 L2012800 1 1 3 1 2 81 Burner Tray Manifold 4 Burners Right L2012700 L2012700 L2012700 L2012700 1 1 1 2 81 Burner...

Page 27: ...Pennant Pool Heater Page 27 Figure 9 Sheet Metal Components...

Page 28: ...LAARS Heating Systems Page 28 Figure 10 Internal Components NOTE Model 2000 shown for reference...

Page 29: ...Pennant Pool Heater Page 29 Figure 11 Heat Exchanger Components A See pump chart below for pump numbers...

Page 30: ...LAARS Heating Systems Page 30 Figure 12 Pennant 500 1000 Ladder Diagram SECTION 10 Wiring Diagrams...

Page 31: ...Pennant Pool Heater Page 31 Figure 13 Pennant 1250 2000 Ladder Diagram...

Page 32: ...LAARS Heating Systems Page 32 Figure 14 Pennant 500 1000 Wiring Schematic...

Page 33: ...Pennant Pool Heater Page 33 Figure 15 Pennant 1250 2000 Wiring Schematic...

Page 34: ...LAARS Heating Systems Page 34 Figure 16 Field Wiring PNCP 500 1000...

Page 35: ...Pennant Pool Heater Page 35...

Page 36: ...93021 805 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars...

Reviews: