LAARS’ ProtoNode Startup Guide
Page 25 of 43
6
LONWORKS (FPC-N35): COMMISSIONING PROTONODE ON A LONWORKS
NETWORK
Commissioning may only be performed by the LonWorks administrator.
6.1 Commissioning ProtoNode FPC-N35 on a LonWorks Network
The User will be prompted by the LonWorks Administrator to hit the Service Pin on the ProtoNode
FPC-N35 at the correct step of the Commissioning process which is different for each LonWorks
Network Management Tool.
•
If an XIF file is required, see steps in Section 6.1.1 to generate XIF
6.1.1 Instructions to Download XIF File from ProtoNode FPC-N35 Using Browser
•
Connect a Cat 5 Ethernet cable (Straight through or Cross-Over) between the PC and
ProtoNode.
•
The Default IP Address of ProtoNode is
192.168.1.24
, Subnet Mask is
255.255.255.0
. If the
PC and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the
192.168.1.xxx network.
•
For Windows XP:
Go to
>
>
Right-click on Local Area Connection > Properties
Highlight
>
•
For Windows 7:
Go to
>
>
>
>
Right-click on Local Area Connection > Properties
Highlight
>
Figure 20: LonWorks Service Pin Location
The LAARS Gateway LER and RER Startup Guide
Page 25 of 43
20
Industrial Way, Rochester, NH, USA 03867
•
(800) 900-9276
•
www.Laars.com
1604 Document 4236E