LAARS’ ProtoNode Startup Guide
Page 28 of 43
7.2 CAS BACnet Setup
These are the instructions to set CAS Explorer up for the first time on BACnet MS/ST and
BACnet/IP.
7.2.1 CAS BACnet MS/TP Setup
•
Using the Serial or USB to RS-485 converter, connect it to your PC and the 3 Pin BACnet
MS/TP connector on ProtoNode FPC-N34.
•
In CAS Explorer, do the following:
o
Click on settings
o
Check the BACnet MS/TP box and uncheck the BACnet/IP and BACnet Ethernet
boxes
o
Set the BACnet MS/TP MAC address to 0
o
Set the BACnet MS/TP Baud Rate to 38400
o
Click Ok
o
On the bottom right-hand corner, make sure that the BACnet MS/TP box is green
o
Click on discover
o
Check all 4 boxes
o
Click Send
7.2.2 CAS BACnet BACnet/IP Setup
•
See Section 4.1 to set the IP address and subnet of the PC that will be running the CAS
Explorer.
•
Connect a straight through or cross Ethernet cable from the PC to ProtoNode.
•
In CAS Explorer, do the following:
o
Click on settings
o
Check the BACnet/IP box and uncheck the BACnet MS/TP and BACnet Ethernet
boxes
o
In the “Select a Network Device” box, select the network card of the PC by clicking on
it
o
Click Ok
o
On the bottom right-hand corner, make sure that the BACnet/IP box is green
o
Click on discover
o
Check all 4 boxes
o
Click Send