background image

   

C Series Operation Manual  

17

7.4.4  Amplifier Gain

All C Series amplifiers feature adjustable input gain. 
This versatility enables the amplifier to accommodate 
a multitude of system configurations with various 
input sources and speaker layouts. 

Amplifier gain is set globally for all four channels. The 
range is +23 dB to +44 dB in 3 dB steps. Individual 
channel fine level adjustment is available using the 
potentiometers on the front panel. 

The unique adjustable input gain feature of the C 
Series makes it easier to attain the optimum balance 
between headroom and signal-to-noise ratio in the 
signal path. A weak signal at the input might require 
the gain to be raised in order to achieve maximum 
output power with the lowest signal-to-noise ratio. A 
“hot” input signal, however, would require a lowering 
of the gain to avoid sending the amplifier into Voltage 
or Current clipping.

See Appendix to review the table containing Gain 
versus VPL setting implications for input sensitivity 
and output power.

Bridge  mode  operation  automatically 

compensates by -6 dB, keeping all channels 
at the same gain.

7.4.4.1  Channel gain/Level (front panel pots)

Individual channel gain (level) may be adjusted using 
the potentiometers located on the front panel behind 
the dust-filter cover. Range is from 0 dB to -Infinity 
in 21 steps. The attenuation is logarithmic, with the 
12 o’clock position indicating -10 dB.

Use  your  fingers  or  a  screwdriver  to  adjust  the 
potentiometers. 

If the level control is used to attenuate to 
a lower level than the headroom relative to 
input sensitivity AND the amplifier input is 
driven into clip, there is a danger of clipping 

the input stage before the current or voltage peak 
limiters are activated.

7.4.4.  Amplifier sensitivity

Sensitivity is defined as how many Volts (rms) or 
dBu (referred to 0.775 Vrms) are required to achieve 
full (maximum) output power. As the output power 
varies with the load impedance, 4 ohms is usually 

the common reference. 

Since C Series amplifiers are capable of providing 
multiple maximum output power levels through use 
of the VPL feature, many sensitivity calculations 
may be required for a single amplifier. We recom-
mend use of the DeviceControl editor to simplify this 
process. DeviceControl’s device view page, used in 
combination with the DIP switch settings display, 
will automatically produce a sensitivity calculation 
from the given data (VPL, Gain and load).

7.4.5  Output Voltage Peak Limiter (VPL)

Voltage Peak Limiter (VPL) is a unique feature in C 
Series amplifiers. It is used to select the maximum 
power available on each output channel. Eight levels 
can be set using the DIP switches on the amplifier’s 
rear panel.

V

peak

V

rms

141

100

118

84

100

70

85

60

71

50

59

42

50

35

42

30

The values for VPL are displayed as maximum Voltage 
Peak. To translate Voltage Peak into V

rms

, you must 

divide the Voltage Peak values by 1.41 (see table).

The VPL allows you to set the correct maximum  
output peak power for optimum performance with the 
connected speakers. The correct setting depends on 
the system type (lo-or hi-impedance) and the specific 
load connected to the channel. Since each channel 
can be configured to deliver either very high voltage 
peak power OR high current draw at low impedances, 
it is important to set the VPL correctly.

To  configure  an  individual  output  channel  for  a 
constant voltage system, you simply adjust the DIP 
switches to the desired voltage. However, when 
using an output for a low impedance system (2, 
4,  8  or  16  ohms),  then  sometimes  you  need  to 
adjust the VPL to a lower setting to avoid either 
delivering excessively high continuous power to the 

OPERATION AND PERFORMANCE  7

Summary of Contents for C 68:4

Page 1: ...Rev 2 01 Operation manual C Series Installation Dedicated Amplifiers C 68 4 C 48 4 C 28 4 C 16 4 Part no UM CS...

Page 2: ...and performance optimization 7 4 2 5 NomadLink Ethernet control and monitoring network 7 5 installation 8 5 1 Unpacking 8 5 2 Mounting 8 5 3 Cooling 8 5 4 Operating voltage 8 5 5 Grounding 9 6 quick g...

Page 3: ...ng open load 19 7 5 6 Lo impedance protection short circuit 19 7 5 7 Temperature protection 20 7 5 8 Power Average Limiter PAL 20 7 5 9 Soft Start 20 7 6 Front panel monitoring and adjustments 21 7 6...

Page 4: ...r replacement of the obsolete outlet Connect only to AC power outlets rated 100 120 V or 200 240 V 50 60 Hz Do not use this amplifier if the power cord is broken or frayed Protect the power cord from...

Page 5: ...pment on and off the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the antenna Increase the separation between the equipment and r...

Page 6: ...impedance or constant voltage 70 V 100 V mode NomadLink an easy to use network for monitoring and control is implemented as a standard feature on all C Series amplifiers Although C Series features and...

Page 7: ...d a malfunctioning cable or driver is short circuiting the output High impedance warning reports an alert when at the same time output signal is high simultane ously and no current draw is measured Th...

Page 8: ...sufficient space to allow the exhaust to escape If the amplifier is rack mounted do not use covers or doors on the front or rear of the rack Should a heat sink overheat the temperature sensing circuit...

Page 9: ...h power is controlled and limited during soft start enabling multiple amplifiers to be powered up simultaneously 5 5 Grounding There is no ground lift switch or terminal on the C Series amplifiers The...

Page 10: ...will not switch on until a Power On command is received from the network When the remote switch is off it is not possible to switch amplifier power on or off using NomadLink network control 6 1 2 Fron...

Page 11: ...t fan feature lowers fan speed when no signal is present Bridged A B and C D Switches the channel pairs into bridged mode operation automatic 6 dB gain compensation VPL Voltage Peak Limiter adjustment...

Page 12: ...erCon XLR type housings on the cables US National Differences cl 16 3 requires that NomadLink network cables must be rated VW 1 The OUT port from the NLB 60E must be connected to the IN port of the fi...

Page 13: ...C Series Operation Manual 13...

Page 14: ...Amplifier Overall amplifier input gain is adjusted using the input stage DIP switches Please note that the gain setting is global affecting all four channels Following the input stage the dedicated l...

Page 15: ...right Complete input sensitivity tables for all VPL and Gain settings for all C Series models can be found at www labgruppen com The headroom available through the input stage to the clip limiter is...

Page 16: ...ained to all speakers in the system As the amplifier outputs produce high voltage do not connect or disconnect speaker cables when the mains power is on Also attach the safety cover on the speaker ter...

Page 17: ...2 Amplifier sensitivity Sensitivity is defined as how many Volts rms or dBu referred to 0 775 Vrms are required to achieve full maximum output power As the output power varies with the load impedance...

Page 18: ...matically un mute An input signal must be present to allow detection of short circuit or low impedance conditions If the CPL LED is steadily illuminated orange while the output is muted and the 4 dB s...

Page 19: ...er Output will be muted long before maximum output power is attained To measure the true peak output power use a burst signal 7 5 4 DC protection DC protection is implemented on each output to prevent...

Page 20: ...ntervals The output will un mute when the channel or power supply returns to a safe operating temperature 7 5 8 Power Average Limiter PAL The Power Average Limiter PAL controls the current drawing rel...

Page 21: ...no speaker is connected For more detailed signal level indications use the DeviceControl editor application 1 2 3 4 5 8 6 2 Level adjust Step Attenuation 1 Min Inf dB 2 Inf dB 3 50 dB 4 40 dB 5 35 dB...

Page 22: ...ce When detected the output will mute for 6 seconds before re measuring the output impedance This will continue until the short circuit is removed CPL remains constant orange in a fault condition only...

Page 23: ...B 60E Should an amplifier fail or be inadvertently disconnected from the mains OPERATION AND PERFORMANCE 7 network integrity is fully maintained and all amplifiers remain visible on the system 7 7 2 C...

Page 24: ...between amplifiers Ethernet Cat5 Ethernet Cat5 Ethernet Cat5 Ethernet Cat5 NLB 60E IN OUT 300m 980ft 300m 980ft 100m 328ft total cable length for links in between amplifiers 300m 980ft Amp 1 IN OUT Am...

Page 25: ...Control editor The DeviceControl editor is Lab gruppen s proprietary software application for monitoring and controlling networked C Series power amplifiers DeviceControl runs on a Windows PC which co...

Page 26: ...feet In a non closed loop daisy chained subnet the maximum cable length is 400 meters 1300 feet In a closed loop subnet the maximum cable length is 700 meters 2300 feet Exceeding these limits may res...

Page 27: ...what you were looking for in this Operation Manual check out the website at www labgruppen com where you can find a multitude of additional documentation for C Series Drawings technical data sheets t...

Page 28: ...dling 1 8 of rated power Pink noise 12 dB crest factor 16 0 8 0 1123 600 523 1784 2484 626 21 2 10 6 1378 600 778 2655 669 570 Max power 3 Pink noise 6dB crest factor 35 2 17 6 2296 1200 1096 3740 942...

Page 29: ...068 9 4 4 7 10 4 5 2 529 663 269 564 567 Max power 3 Pink noise 6dB crest factor 24 0 12 0 1790 1589 933 16 A CEE7 20 A 5 20P 467 451 21 4 10 7 1458 933 115VAC 230VAC In Out Dissipated BTU hr kCal hr...

Page 30: ...r 2 ch s 1 3400 W 2400 W 1200 W 600 W 4 ohms bridged per 2 ch s 1 2400 W 1200 W 600 W n r 4 Hi Z 140V 200V bridged per 2 ch s 1 3200 W 1800 W 1400 W 800 W Mains connector 230V CE version 16A CEE7 16A...

Page 31: ...lly balanced Output connectors per ch Barrier strip 2 pole screw terminals Output bridge mode A B and or C D inputs A and C are signal source NomadLink network On board 2 x RJ45 EtherCon connectors IN...

Page 32: ...any loss due to cancellation of any events or rent of replace ment equipment or costs due to a third party s or customer s loss of profit or any other indirect cost or losses however incurred Lab grup...

Page 33: ...L a b g r u p p e n AB S w e d e n 4 6 3 0 0 5 6 2 8 0 0 T C El e ct r o n i c I n c U S a 8 1 8 6 6 5 4 9 0 0 m a i l i n f o L ABGRUPPEN c o m w w w l a b g r u p p e n c o m...

Reviews: