45
PARAMETER TABLE
PARAMETERS
EXPLANATION
P01
Opening speed. Max. 0.8 m/s per leaf.
Increasing the value increases the speed during the opening movement.
P02
Closing speed. Max. 0.6 m/s per leaf.
Increasing the value increases the speed during the closing movement.
P03
Reduced opening distance during winter. Min. 20 cm/leaf.
Adjustment, as a percentage of the passage opening, of the reduced opening space.
P04
Thrust power
Adjustment of the motor power during the motion of the door. At maximum value, the maximum thrust is obtained. Automation is equipped with
a safety system that stops and reverses the motion if power limit is exceeded.
P05
Open door pausing time in automatic work programs.
Setting values range between 0 second (closing immediately after opening) and 30 seconds.
P06
Open door pausing time in the Night Lock work program.
Setting values range between 01 second (closing immediately after opening) and 30 seconds. At the default value 0%, the function is disabled.
This parameter allows to set a pausing time in Night Lock mode which exceeds the pausing time set by the parameter P5.
P07
Acceleration ramp when opening
It sets the leaf acceleration phase during the opening cycle start.
Increasing the value will increase leaf starting acceleration during the opening process.
P08
Slowdown ramp during opening
Increase the value for quicker braking at the end of the opening process.
With the function F49= OFF (factory setting), the automatic braking control is active, which optimizes the slowdown stage in the range of values
between that set and 100%. Automatic braking control operates according to the opening speed and to the leaf weight.
P09
Deceleration starting distance when opening
Increasing the value will increase the distance from the end of the run during opening, starting from which the leaf proceeds at slow speed until
the end of the run.
P10
Deceleration starting distance when closing
Increasing the value will increase the distance from the end of the run during closing, starting from which the leaf proceeds at slow speed until
the end of the run.
P11
Motor thrust power at the end of the closing cycle
It sets the thrust power in the last phase of the closing cycle; this is useful to ease the full approach of the leaf to the final ledge. Increasing the
value will increase the thrust power.
P12
Reaction time to the obstacle when closing
Adjustment of the thrust time against the obstacle during the closing cycle before the reversal of the direction of travel.
By increasing the value, sensibility to the obstacle decreases and thrust time increases.
P13
Reaction time to the obstacle when opening
Adjustment of the thrust time against the obstacle during the opening cycle before the reversal of the direction of travel.
By increasing the value, sensibility to the obstacle decreases and thrust time increases.
P14
Reaction time to the obstacle during the slowdown when opening at slow speed
Adjustment of the thrust time against the obstacle in slow speed motion during the opening cycle before the reversal of the direction of travel.
By increasing the value, sensibility to the obstacle decreases and thrust time increases.
P15
Thrust force in case of obstacle or friction of the door
Adjustment of the thrust force on the obstacle. Once the set limit is exceeded, the automation reverses the movement.
After the removal of the obstacle, in the next cycle, the door searches for the ledge, continuing its travel at a slow speed.
P16
Wind stop when the door is closed
It sets the intensity of the contrast force exerted by the motor, should anyone attempt to forcibly open the door.
Increasing the value will increase the intensity of the force contrasting the leaf opening attempt.
P17
Distance from the final closing ledge where the door reopens if an obstacle is detected during the closing cycle
When decreasing this value to 0% the motion direction will be reversed if an obstacle is detected up to 5mm from the final closed door ledge.
Below this distance the door stops, completing the closing cycle.
P18
Distance between the end of the leaf run during opening and the mechanical opening limit device
Increasing the value will increase the distance between the leaf and the mechanical limit device, with respect to the value stored during set‑up.
Decreasing the value will decrease the distance between the leaf and the mechanical limit device, with respect to the value saved during set‑
up.
P19
Waiting time between 2 consecutive door crossing warning gongs.
Adjustment of the waiting time between gong activation when a person crosses the automatic door and its new activation in case of new
crossing, avoiding repeated gongs at short distance. See para. "Gong Function".
P20
Start delay when opening with respect to activation of electric lock
It sets the time after which the door opens, from the issuing of the opening command and the activation of the electric lock.
When the parameter is set to the minimum value, i.e. 0%, the leaf starts as soon as the electric lock is activated; when it is set to 100% the
delay will be of 5 seconds.