CABLE TERMINAL
CABLE LOCK
CABLE TERMINAL
LOWER SCREW
Pass the release cable in the slit in the base and then inside the
adjustment register as shown in the figure. Then position the
cable terminal on the release handle cable lock (see figure).
Now, insert the release handle on the base of the mechanism,
being careful to keep the cable terminal in the seat of the cable
lock and the handle in the correct position. When inserting the
handle, the cable terminal must be in the position just beyond
the lower fastening screw, in a clockwise direction.
Drill the wall and fasten the base of the release mechanism
using the fastening screws.
Apply the adhesive label as shown in the figure, taking the four
black bands on the label as a reference, which must be
positioned in correspondence of the 4 cardinal points.
Insert the adjustment register using 2 nuts, one in the plastic
slot and the other outside of it.
BLACK BANDS
BLACK BANDS
FASTENING SCREW
FASTENING SCREW
Identify the fastening point on the wall, taking into account that
the standard cable sheath is 3 metre long and that it must reach
the electric lock.
SCREW COVER
LABEL
10.4) INSTALLATION OF THE MANUAL RELEASE ON THE WALL
Once the handle is inserted, fasten the closing screw, insert the
sheath and turn the handle to the UNRELEASED position. In
this position, only the orange part of the label with the black
arrows must be visible.
Make sure that the system is operating by turning the handle
clockwise and keeping the cable taut with your hand.
WARNING!:
THE HANDLE TURNS BY MAX 45-50 DEGREES AND AT
THE END, THERE ARE STEPS IN ORDER TO MAINTAIN
THE POSITION AFTER THE LOCK
.
Apply the provided screw cover label as shown in the figure and
return the handle to the
UNRELEASED
position.
19