P23
OPENING DISTANCE IN CHEMIST'S MODE
Increasing the value will increase the reduced opening value in chemist's mode; min. se ng 5cm./leaf, max. 20cm./leaf.
Please refer to the "Special func ons with double electric lock ? Chemist's func on" paragraph.
P24
Push & Go func on
Manually moving the leaf by a few cen meters in the opening direc on ac vates an automa c opening cycle.
At 0% func on disable, at minimum value 01% = a er a manual movement of 1 cm of the leaf the door opens automa cally, at 100% = 10cm.
P25
Tension keeping the door closed
It sets the tension the motor exerts when the door is closed, to keep the leaves properly in contact with the ledge.
Increasing the value will increase the thrust exerted by the leaf onto the closing ledge.
P26
ANTIROLL FUNCTION FOR BOATS
0%: DISABLED FUNCTION
01%: ENABLED FUNCTION. Please refer to the "Special func ons with double electric lock ? An roll func on for boats" paragraph.
P27
Not used
P28
Not used
P29
Not used
P30
Not used
P31
Not used
P32
Not used
P33
Not used
P34
Not used
P35
Not used
P36
Not used
P37
Not used
P38
Not used
P39
Not used
P40
Not used
P41
Not used
P42
Not used
P43
Not used
P44
Not used
P45
Not used
P46
Not used
P47
Not used
P48
Scheduled maintenance
This parameter allows you to select the number of cycles of opening/closing a er which the display of the program selector show the
message "SCHEDULED MAINTENANCE ".
The maintenance signal can also be available on the OUT1 or OUT2 outputs of the ET-LOGIC-B control unit through the UR24E relay
module if the opera ng mode G is selected in the F41m or F45m func ons.
When the parameter is set to OFF (default value) the message is not displayed.
Select the number of cycles according to the door opera on and to the usage condi ons:
8K (8000 cycles), 16K (16000 cycles), 32K (32000 cycles), 64K (64000 cycles), 128K (128000 cycles), 256K (256000 cycles), 512K (512000 cycles).
P49
Se ng of the movable leaf total weight, to meet the Low Energy movement speed limits when the door is opening (standard EN16005)
When selec ng the value of the movable leaf total weight, the door opening speed will be automa cally adjusted by the operator to
comply with Low Energy movement limits set by EN16005 and DIN18650 standards.
The Low energy mo on isn't generally protected by other safety devices, as the kine c energy level is not regarded as dangerous.
The low energy mo on, however, is only considered for the risk assessment purposes.
When the value is set to 00 the func on is disabled and the opening speed can be set using the P01 poten ometer. In this case the
installer must take other safety measures, in compliance with the regula ons in force.
The se ng values for the total weight of the movable leaves range between 30 Kg and 320Kg.
P50
Se ng of the movable leaf total weight, to meet the Low energy mo on speed limits when the door is closing (standard EN16005)
When selec ng the value of the movable leaf total weight, the door closing speed will be automa cally adjusted by the operator to
comply with Low Energy movement limits set by EN16005 and DIN18650 standards.
The Low energy mo on isn't generally protected by other safety devices, as the kine c energy level is not regarded as dangerous.
The low energy mo on, however, is only considered for the risk assessment purposes.
When the value is set to 00 the func on is disabled and the opening speed can be set using the P02 poten ometer. In this case the
installer must take other safety measures, in compliance with the regula ons in force.
The se ng values for the total weight of the movable leaves range between 30 Kg and 320Kg.
P21
Internal Radar and Start enabling me when the Night Lock work program is selected
Time during which the Internal Radar and Start inputs remain enabled to open the door a er the Night Lock work program has been set.
At 0% the func on is disabled, at 01% = 10 seconds, at 100% = 120 seconds.
P22
Potentiometer
active if function
F27 = ON
Time a er which the interlock between two automa c doors gets disabled if the open door doesn't close back
Please refer to the "Interlock system" paragraph. When the parameter is set to 0% (the default value), the func on is disabled.
Time a er which the interlock gets automa cally disabled if the currently open door doesn't close back due to the high flow of people.
In this case if the internal radar of the second door is ac vated by the people who are in the gap between the two doors, the second
door opens allowing people to move out.
At 01% the interlock disabling me and the second door opening me will be of 10 seconds.
At 50% the interlock disabling me will be of 60 seconds, at 100% the interlock disabling me will be of 120 seconds.
44
PARAMETER
EXPLANATION