54
2
6
) “UR24” MODULE
The UR24 module is an optional interface board equipped with a relay (C - NA - NC clean contact), designed to be inserted into the OUT1
and OUT2 output connectors of the ET-LOGIC-B electronic control unit.
MAX CAPACITY RELAY CONTACT = 1A - 24Vdc ; 0,5A - 120Vac
Regard the UR24 module on the OUT1 output, select the desired operating mode by F41m function.
ATTENTION!
If the interlock function is enable (F27 = ON), output OUT1 works as
interlock mode therefore all the functions foreseen by F41m are
automatically excluded.
Regard the UR24 module on the OUT2 output, select the desired operating mode
by F45m function.
For each output one of the following functions can be selected (see details on the
function table in the paragraph "FUNCTIONS AND ADJUSTMENTS"):
A = LOCK
The output is active when the contact on LOCK 1 input is closed.
B = GONG
The output is active for 2 seconds by crossing the automatic door.
Refer to the "GONG FUNCTION" paragraph for a detailed description of the GONG operation.
C = AIR BLADE
Air blade command. Device that generates a cold or heated air flow to separate the external temperature from the internal temperature.
The output is active when the door is moving or open, whereas it deactivates when the door is closed.
D = BATTERY STATUS
The activation of the output signals the battery faulty.
E = DOOR STATUS
Signalling of the automatic door operation:
OPENING MOVEMENT = SLOW FLASHING
DOOR OPEN = FIXED LIGHT ON
CLOSING MOVEMENT = FAST FLASHING
DOOR CLOSED = LIGHT OFF
F = ALARM WARNING
The output activates for two seconds if in the NIGHT LOCK work program the activation radar or closing safety sensor inputs activate
when the door is closed.
G = MAINTENANCE WARNING
The output is active when the number of cycles required by the scheduled maintenance plan set by potentiometer P48 is reached.