36
POTENTIOMETERS TABLE
POTENTIOMETER
EXPLANATION
"SLAVE
P01
Opening speed
Increasing the value increases the speed during the opening movement.
S
P02
Closing speed
Increasing the value increases the speed during the closing movement.
S
P03
Opening safety sensor disabling distance
When the wall is near the open door, by increasing the value, the degrees in the final stage of
the opening run in which the activation of the safety sensor leads to the immediate switch of the
opening speed to the approach speed are increased to prevent leaf stop due to wall detection.
S
P04
Open door pause time in automatic work programs
Setting values range between 0 (closing immediately after opening) and 60 seconds. Door open
time before automatic closing.
P05
Potentiometer enabled
if F17 = ON
Pause time with open door in the disabled function
Setting values range between 0 (closing immediately after opening) and 60 seconds. Door open
time before automatic closing when the opening command is given by the disabled, operating the
button connected to the OPEN input or by the Label remote control.
P06
Holding tension with door closed
Increasing the value increases the thrust exerted by the leaf on the closing ledge.
S
P07
Wind stop when the door is closed
At the default value 0%, the function is disabled. Increasing the value increases the intensity of the
force contrasting the wind thrust to keep the leaf closed.
S
P08
Push & go
At the default value 0%, the function is disabled. As soon as the door is pushed manually, an
automatic opening cycle starts. Increasing the value increases the degrees of leaf motion required
before starting the opening.
Adjustment between 2° and 15°.
S
P09
Potentiometer enabled if
F02 = ON and F03 = OFF
Final push for electric lock engagement
Increasing the value increases the leaf speed in the last degrees of the closing movement to ease
the engagement of the electric lock.
S
P10
Potentiometer enabled
if F02 = ON
Closing thrust to release the electric lock
At the default value 0%, the function is disabled. Increasing the value increases the power of the
closing thrust before door opening to ease electric lock release.
S
P11
Potentiometer enabled
if F02 = ON
Opening start delay after electric lock activation.
At the default value 0%, the function is disabled.
Increasing the value introduces a delay in leaf opening start with respect to electric lock activation
(4" at 100%).
S
P12
Potentiometer ON
if F02 = ON, F03 = OFF,
F05 = ON
Electric lock excitation time when you select the program "manual free door"
At 100%, the electric lock is always powered.
S
P13
Deceleration starting distance when opening
Increasing the value increases the degrees of the opening run starting from which the leaf
proceeds at approach speed.
S
P14
Deceleration starting distance when closing
Increasing the value increases the degrees of the closing run starting from which the leaf proceeds
at approach speed.
S
P15
Thrust power during closing
Increasing the value increases the thrust power of the motor during the closing movement.
S
P16
Motor thrust time at the end of the closing
Increasing the value increases the time the motor keeps thrusting in the last degrees of the closing
movement, to overcome possible frictions and ease the approach of the leaf to the closing ledge.
At 100%, thrust time 1.5 seconds.
S