37
P17
Thrust power at the end of the opening cycle
The value of this parameter must be increased in order to increase the motor thrust power if the
door has difficulty opening in the last degrees.
S
P18
Distance between the end of the leaf run and the final ledge during opening
Increasing the value reduces the opening degrees, decreasing the value increases the opening
degrees with respect to the default value stored during the setup. The adjustment range is
approximately 5°.
S
P19
Push & close
If the stationary open door is pushed manually, an automatic closing cycle starts.
Increasing the value increases the degrees of leaf motion required before starting the closing.
Adjustment between 2° and 15°.
S
P20
Wind stop when the door is open
Increasing the value increases the intensity of the force contrasting the wind thrust to keep the
stationary leaf open.
S
P21
Acceleration ramp when opening
Increasing the value increases door acceleration during the opening movement.
S
P22
Assisted manual opening
Increasing the value increases the feeling of lightness of the leaf during manual opening. At the
minimum value 0% the assisted function is disabled.
S
P23
Spring aid when closing (only active with F38 = OFF)
Increasing the value increases the force of the thrust at the start of the closing manoeuvre, for
situations in which the force of the spring is not sufficient to guarantee the start of the closing
movement.
S
P24
Distance from the final closing ledge where the door reopens if an obstacle is detected
during the closing cycle
Increasing the value increases the degrees from the final closing ledge in which the closing
movement stop is achieved without reversing the running direction in case of detection of an
obstacle.
S
P25
Intensity of door braking at the end of the opening after a manual push
Increasing the value increases the leaf braking.
S
P26
Distance from the end of the run during opening, starting from which it is braked after a
manual push
Increasing the value increases the distance from the final ledge in opening where the door is
braked during the manual push.
S
P27
Leaf braking intensity when the opening safety sensor trips
Increasing the value reduces the braking distance.
S
P28
Potentiometer enabled if
the function F26 = ON
Time after which the interlock between two automatic doors gets disabled if the open door
doesn't close back
Please refer to the "Interlock system" paragraph. At the default value 0%, the function is disabled.
Time after which the interlock is disabled automatically if the door that is open does not close
due to the high flow of people. In this case, if the radar inside the second door is activated by
the persons in the space between the two doors, the second door opens allowing the outflow of
people.
At 01% the interlock disabling time and the ensuing second door opening time will be 10 seconds.
At 50% the interlock disabling time will be 60 seconds, at 100% the interlock disabling time will be
120 seconds.
P29
Not used
P30
Leaf delay during opening
For dual leaf door. Increasing the value increases the starting delay during opening of the Slave
automation with respect to the Master automation, necessary in case of overlapping leaves. At the
minimum value 0%, both leaves start together during opening.
P31
Leaf delay during closing
For dual leaf door. Increasing the value increases the starting delay during closing of the Master
automation with respect to the Slave automation, necessary in case of overlapping leaves. At the
minimum value 0%, both leaves start together during closing.
P32
Thrust power during opening.
Increasing the value increases the thrust power of the motor during the opening movement.
S