OilSET-1000 Oil Separator Alarm Device 

 

     

                                 

D15492AE-2 

Installation and Operating Instructions

  

 

 

Copyright © 2019 Labkotec Oy 

5/13 

We reserve the right for changes without notice 

2.2 

SET/DM3AL sensor 

SET/DM3AL sensor should be installed as described in figure 3. 

The sensor gives an alarm when the upper electrode is in oil. 

Please check the correct installation depth also from the instructions of 
the oil separator. 

2.3 

Cable joint 

 

 

 
Fig. 4. Cable joint  

 

Connections of the sensor cable inside the cable joint are explained in 
figure 3. Cable shields and possible excess wires need to be connected 
to the same point in galvanic contact.  

Please  make  sure,  that  the  sensor  and  cable  between  OilSET-1000 
control  unit  and  the  sensor  do  not  exceed  the  maximum  allowed 
electrical parameters 

– see chapter 7 Technical data. 

IP  rating  of  the  cable  joint  is  IP68.  Make  sure,  that  the  cable  joint  is 
closed properly. 

If  the  sensor  cable  must  be  extended  and  there  is  a  need  for 
equipotential grounding, it should be done with the junction box LJB2. 
The cabling between the OilSET-1000 control unit and the junction box 
should be done with a shielded twisted pair instrument cable. 

 

 

Fig. 5. Cable installation example 

Fig. 6. Installation accessories 

 

 

 

Summary of Contents for OilSET-1000

Page 1: ...8 29 006 260 Fax 358 29 006 1260 23 9 2019 Internet www labkotec fi D15492AE 2 1 13 Copyright 2019 Labkotec Oy We reserve the right for changes without notice OilSET 1000 Oil Separator Alarm Device wi...

Page 2: ...trol unit 4 2 2 SET DM3AL sensor 5 2 3 Cable joint 5 3 OPERATION AND SETTINGS 6 3 1 Operation 6 3 2 Factory settings 7 4 TROUBLE SHOOTING 8 5 REPAIR AND SERVICE 9 SAFETY INSTRUCTIONS 9 6 TECHNICAL DAT...

Page 3: ...is installed into the light liquid storage chamber and gives an alarm when the chamber is filled to a pre determined degree The sensor is normally immersed in water The function is based on the measu...

Page 4: ...re beneath the mounting holes of the front cover The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must be in...

Page 5: ...ined in figure 3 Cable shields and possible excess wires need to be connected to the same point in galvanic contact Please make sure that the sensor and cable between OilSET 1000 control unit and the...

Page 6: ...LED indicators are off Relays 1 and 2 are energized Oil alarm SET DM3AL sensor is immersed in oil The sensor gives an alarm when the upper electrode is in oil Mains LED indicator is on Oil Alarm LED...

Page 7: ...OilSET 1000 is not as described in the previous chapter check that the device settings are as in figure 7 Change the settings according to the following instructions if needed The following tasks mus...

Page 8: ...ensor should give an alarm again Problem FAULT LED indicator is on Possible reason Current in sensor circuit too low cable break or too high cable in short circuit The sensor might also be broken To d...

Page 9: ...tentially explosive atmosphere Sensors connected to it may be installed in zone 0 1 or 2 potentially explosive atmospheres In case of installations in explosive atmospheres the national requirements a...

Page 10: ...e g 19 2019 Due to non linear characteristics of the sensor voltage the interaction of both capacitance and inductance must be taken into account The table below indicates the connecting values in exp...

Page 11: ...DECLARATION OF CONFORMITY...

Page 12: ...DECLARATION OF CONFORMITY...

Page 13: ...DECLARATION OF CONFORMITY...

Reviews: