OilSET-1000 Oil Separator Alarm Device 

 

     

                                 

D15492AE-2 

Installation and Operating Instructions

  

 

 

Copyright © 2019 Labkotec Oy 

6/13 

We reserve the right for changes without notice 

OPERATION AND SETTINGS 

The OilSET-1000 alarm device is initialized at the factory.  

The operation of the alarm device should be checked always after the 
installation. 

Functionality test 

1. Immerse the sensor into water. The device should be in normal mode. 

 

2. Lift the sensor up in air or oil. An Oil alarm should be generated (see 

chapter 3.1 for more detailed description). 

 

3. Immerse the sensor back into water. The alarm should go off after a 

delay of 5 sec. Clean up the sensor if necessary before placing it back 
into the oil separator. 

A more detailed description of the operation is provided in chapter 3.1. 
If  the  operation  is  not  as  described  here,  check  the  factory  settings 
(chapter 3.2.) or contact a representative of the manufacturer. 

3.1 

Operation 

The  operation  of  a  factory-initialized  OilSET-1000  is  described  in  this 
chapter. 

Normal mode 

– no alarms 

SET/DM3AL sensor is totally immersed in water. 

 

 

 

Mains LED indicator is on. 

 

Other LED indicators are off. 

 

Relays 1 and 2 are energized. 

 

 

Oil alarm 

SET/DM3AL sensor is immersed in oil. (The sensor gives an alarm when 
the upper electrode is in oil.) 

 

 

 

Mains LED indicator is on. 

 

Oil Alarm LED indicator is on. 

 

Buzzer on after 5 sec delay. 

 

Relays de-energize after 5 sec delay. 

 

(Note. The same alarm takes place when SET/DM3AL sensor is in the 
air.) 

 

 

 

After removal of an alarm, the Oil Alarm LED indicator and buzzer will be 
off, and relays will be energized after a fixed delay of 5 sec. 

 

 

Fault alarm 

Sensor cable break, short circuit or a broken sensor, i.e. too low or too 
high sensor signal current. 

 

 

 

Mains LED indicator is on. 

 

Sensor circuit Fault LED indicator is on after 5 sec delay. 

 

Buzzer is on after 5 sec delay. 

 

The relays de-energize after 5 sec delay. 

 

 

Reset of an alarm 

When pressing the Reset push button.

 

 

 

 

Buzzer will go off. 

 

Relay 1 energizes. 

 

Relay 2 will stay de-energized until the actual alarm or fault is off. 

 
TEST FUNCTION 

Test function provides an artificial alarm, which can be used to test the 
function  of  the  OilSET-1000  alarm  device  and  the  function  of  other 
equipment, which are connected to OilSET-1000 via its relays. 

Attention! Before pressing the Test button, make sure that the change 
of relay status does not cause hazards elsewhere! 

 

 

Normal situation 

 
When pressing the Test push button: 

Summary of Contents for OilSET-1000

Page 1: ...8 29 006 260 Fax 358 29 006 1260 23 9 2019 Internet www labkotec fi D15492AE 2 1 13 Copyright 2019 Labkotec Oy We reserve the right for changes without notice OilSET 1000 Oil Separator Alarm Device wi...

Page 2: ...trol unit 4 2 2 SET DM3AL sensor 5 2 3 Cable joint 5 3 OPERATION AND SETTINGS 6 3 1 Operation 6 3 2 Factory settings 7 4 TROUBLE SHOOTING 8 5 REPAIR AND SERVICE 9 SAFETY INSTRUCTIONS 9 6 TECHNICAL DAT...

Page 3: ...is installed into the light liquid storage chamber and gives an alarm when the chamber is filled to a pre determined degree The sensor is normally immersed in water The function is based on the measu...

Page 4: ...re beneath the mounting holes of the front cover The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must be in...

Page 5: ...ined in figure 3 Cable shields and possible excess wires need to be connected to the same point in galvanic contact Please make sure that the sensor and cable between OilSET 1000 control unit and the...

Page 6: ...LED indicators are off Relays 1 and 2 are energized Oil alarm SET DM3AL sensor is immersed in oil The sensor gives an alarm when the upper electrode is in oil Mains LED indicator is on Oil Alarm LED...

Page 7: ...OilSET 1000 is not as described in the previous chapter check that the device settings are as in figure 7 Change the settings according to the following instructions if needed The following tasks mus...

Page 8: ...ensor should give an alarm again Problem FAULT LED indicator is on Possible reason Current in sensor circuit too low cable break or too high cable in short circuit The sensor might also be broken To d...

Page 9: ...tentially explosive atmosphere Sensors connected to it may be installed in zone 0 1 or 2 potentially explosive atmospheres In case of installations in explosive atmospheres the national requirements a...

Page 10: ...e g 19 2019 Due to non linear characteristics of the sensor voltage the interaction of both capacitance and inductance must be taken into account The table below indicates the connecting values in exp...

Page 11: ...DECLARATION OF CONFORMITY...

Page 12: ...DECLARATION OF CONFORMITY...

Page 13: ...DECLARATION OF CONFORMITY...