BA_072_2020-02_10.00 Pressure transmitter PASCAL Ci4
Page 25/28
6.4.8 Menue "Communication"
In the "Communication" menue the settings for the HART communication are summarised.
Menue entry
Description
HART address
Setting the HART address for device identification in multi-drop
mode
Current mode
Setting the current mode (proportional/constant)
HART data
Display of HART information (HART-Tag, HART-Descriptor etc.)
Send-preambles
Setting of the number of send-preambles for
HART communication
Table 18: "Communication" menue
6.4.8.1 HART address
This address corresponds with the short address which is used for the HART-
Communication. It can be set within a range of 0 to 63. Please note, that setting the short
address between 1 and 63 will not automatically activate the constant current mode. This
must be done under the menue “Current mode” (see 6.4.8.2).
6.4.8.2 Current mode
The current mode determines whether the output current of the device is set to respond
proportionally to the measured value (selection “proportional”) or whether it should remain
constant at 4 mA (selection “constant”). When the current mode “constant” is in use, the
measurement value can only be read using HART-commands (e.g. for HART-multidrop-
operation).
6.4.9 "System" menue
In the "System" menue, device-relevant functions are summarised.
Menue entry
Description
Device ID
Setting the device ID (e.g. to display a free-text in the display)
Device data
Display of device data (such as from measured value display)
Factory data reset
Reset to factory settings
Restart
Restarting the device (such as after a power outage)
Config.-memory
Configuration memory: reading, writing and status
Table 19: "System" menue