I N STALLER’S M AN UAL
E
nsure that the oven is set to the type of gas used (see label on the gas connector).
I
f the gas supply is not compatible with the gas setting of your range the setting must be modiied.
Refer to the “Changing the hob gas” section of the present instructions.
Butane-fuelled units
: Connect unit to 2.6 kg/h pressure reducer. Use two cylinders connected to a
3-way valve ahead of the pressure regulator in case of prolonged, continuous duty.
Propane-fuelled units
: Connect unit to a 3.0 kg/h pressure reducer. Use two cylinders and a 3-way
valve ahead of the pressure regulator in case of prolonged, continuous duty. The use of 37 kg or
extern cryogenic tanks is both possible and recommended.
Before connection
Check
:
◊ Pipework is perfectly clean in order to prevent the injectors becoming blocked and malfunctioning
of the magnetic heads.
◊ The gas for which the appliance was set up: Rating plate and markings.
◊ Cross-sectional area of gas supply pipework is compatible with the appliance’s thermal output.
◊ Provide adequate air supply during use of the appliance.
Gas connection
Female coupling
Ø
15/21, 1/2” ID NPT on
A
/ figure
1
.
After connection
Check the manifold pressure on pressure connection Ø 15/21, 1/8” NPT on
B
/ figure
2
.
Subsequently check the circuit for gas leaks.
GAS CONNECTION
Table 1
Country
GAS
Pressure (Pn)
U.S
Natural gas
6’’ WC
U.S
L.P. propane
10’’ WC
A
B
The appliance is designed to operate with the gases in Table 1.
1
2
Notice provisoire Beaune - Bussy UL - FT164h - Date : 16/10/12
10/42