SPC Settings:
For the Single Pulse Check an internal independent 100MHz clock is used. You may choose an appropriate
value for the check. For example:
Input frequency = 20 MHz
100𝑀𝐻𝑧
20𝑀𝐻𝑧
= 5
choosing 9 to ensure that asynchrony clocks not trigger the system and smaller then twice the calculated
number.
SPC
–
ON/OFF … activate the Single Pulse Check and show the actual state
Single Pulse Check … setup the value for the check 0…255
Save Settings … save
system setting and spc settings actual values in the device
Limit Settings:
In this section you can use the additional Level Check to ensure signal quality and power at optical input port.
When activated the AOM Output and monitor Port is blocked in any case of limit error.