INSTRUCTIONS FOR THE INSTALLER 

 

 

2.  

 

INSTRUCTIONS FOR THE 

INSTALLER  

2.1.

 

Warning to installers 

All  local  and  national  regulations, 

including all those referring to national and 
European  standards,  must  be  observed 
when installing the appliance. 

Installation  of  the  appliance  must  be 

performed by an authorised installer. 

An  incorrectly  installed  appliance  may 

lead  to  serious  incidents  (fires,  creation  of 
harmful  gases,  deterioration  of  nearby 
fixtures, etc.). 

Lacunza’s  liability  is  limited  to  the 

supply of the material and does not include 
installation of the appliance. 

2.2.

 

Room for installation 

2.2.1.

 

Ventilation of the room 

The  appliance  needs  to  consume 

oxygen  (air)  in  order  to  work  properly. 
Ensure a suitable air supply in the room in 
which the appliance is fitted. This quantity 
of  oxygen  is  additional  to  the  oxygen  that 
we need in order to breathe (air renewal).  

In  order  to  ensure  the  high  quality  of 

the  air you breathe and to avoid potential 
accidents 

resulting 

from 

high 

concentrations  of  the  gases  produced  by 
combustion  (mainly  carbon  dioxide  and 
carbon monoxide), it is absolutely crucial to 
ensure  the  suitable  renewal  of  the  air  in 
the room in which the appliance is fitted. 

the room must always have at least two 

permanent  grilles  or  openings  to  the 
exterior in order to renew the air (one  for 
intake and the other for extraction). 

For  the  installation  of  its  appliances, 

Lacunza recommends an additional section 
for these openings. One of these two grilles 
must  be  situated  high  up  in  the  room  (at 

less  than  30  cm  from  the  ceiling)  and  the 
other  one  low  down  (at  less  than  30  cm 
from  the  floor).  Both  grilles  must  open 
outdoors  in  order  to  renew  the  air  in  the 
room with fresh air. 

The minimum section that each of these 

grilles  must  have  depends  on  the  nominal 
output of the appliance in accordance with 
the following table: 

 

 

 

 

Figure No.2 -

 

Guideline indications for 

ventilation grilles 

The appliance must always be used with 

the door(s) closed.  

In  rooms  equipped  with  Controlled 

Mechanical 

Ventilation, 

the 

system 

extracts  and  renews  the  ambient  air;  in 
such  cases,  the  room  is  at  slightly  low 
pressure and it is necessary to install a non-
closable  outside-air  inlet  with  a  section  of 
at least 90 cm². 

Output of the 

appliance 

(kW)

Minimum 

additional section 

of each of the 

grilles (cm

2

)

P ≤ 10kW

70

10 < P ≤ 15

90

15 < P ≤ 20

120

20 < P ≤ 25

150

25 < P ≤ 30 

180

30 < P ≤ 35 

210

P > 35

240

Summary of Contents for CALPE

Page 1: ...CALPE Instruction Book ...

Page 2: ...STALLER 5 2 1 Warning to installers 5 2 2 Room for installation 5 2 2 1 Ventilation of the room 5 2 2 2 Location of the appliance in the room 6 2 3 Installation of the appliance 6 2 3 1 Floor 6 2 3 2 Safety distances 6 2 3 3 Checks before lighting for the first time 6 2 3 4 Height adjustment and levelling the appliance 6 2 3 5 Connection to the flue 6 2 4 Chimney flue 6 2 4 1 Type of flue 6 2 4 2 ...

Page 3: ...1 4 1 3 Flue socket 15 4 1 4 Painted sheet steel cast iron parts 15 4 1 5 Firebox glass 15 4 2 Maintenance of the chimney flue 15 4 3 Important advice 15 TROUBLESHOOTING 16 BASIC BREAKDOWNS 17 DECLARATION OF PERFORMANCE 18 CE MARK 20 ...

Page 4: ... Efficiency at N H O 85 CO emission at 13 O2 at N H O 0 04 Gas mass flow at N H O g s 7 9 Gas temperature of flue at N H O ºC 252 Optimum flue draught Pa 12 Wood consumption beech at N H O Kg h 3 3 Dimensions of the firebox Width mm 530 Depth mm 280 Useful height mm 220 Maximum length of the logs cm 50 Volume heated 45w m at N H O m 267 Log load frequency h 1 Capacity of the ashpit L 1 5 Weight kg...

Page 5: ...PRESENTATION OF THE APPLIANCE 4 1 Figure No 1 Dimensions of the CALPE series in mm ...

Page 6: ...olutely crucial to ensure the suitable renewal of the air in the room in which the appliance is fitted the room must always have at least two permanent grilles or openings to the exterior in order to renew the air one for intake and the other for extraction For the installation of its appliances Lacunza recommends an additional section for these openings One of these two grilles must be situated h...

Page 7: ...rectly positioned Make sure that the airtight joints on the flue circuit are in perfect condition Make sure that the doors close properly Make sure that all moving parts are fitted in place 2 3 4 Height adjustment and levelling the appliance The appliance must be perfectly level horizontally and vertically both at the front and on the sides use a spirit level 2 3 5 Connection to the flue The appli...

Page 8: ...raught cowl a static cowl or a smoke extraction fan or reshape the chimney Never make 90º bends due to the great loss of draught they cause and reduce 45º bends down to an absolute minimum Each 45º bend is equivalent to a 0 5m reduction in flue length Horizontal flue sections should not be installed because they cut updraught a great deal If the flue draws at more than 20 Pa then an effective damp...

Page 9: ...tacle located within a 10m radius of the chimney outlet by more than 1m Figure No 4 Distances between the chimney crown and objects within a 10m radius The chimney crown must clear any neighbouring building or obstacle located within a radius of 10m to 20m from the chimney outlet Figure No 5 Distances between the chimney crown and objects within a radius of between 10 and 20m ...

Page 10: ...anliness height verticality straightness chimney crown etc If sufficient updraught is not achieved by correcting the flue installation Lacunza supplies an accessory for exceptional cases a part which seals the top of the front part of the appliance and helps prevent smoke escaping into the room Logically this reduces both the view of the fire and the loading aperture on the appliance Figure No 6 A...

Page 11: ...ely chopped wood produces greater heat output but also burns more quickly Optimum fuels Beech Other fuels Oak chestnut ash maple birch elm etc Pine and eucalyptus logs are low density and produce very long flames and may cause the parts of the appliance to wear out more quickly than normal Resinous wood may mean that the appliance and the flue need to be cleaned more often Non permitted fuels All ...

Page 12: ...n of the parts of the appliance 3 2 1 Operating components Figure No 8 Operating components on the appliance A Firebox door handle B Primary air intake o B1 open right o B2 closed left C Secondary air intake o C1 open right o C2 closed left ...

Page 13: ... of operation If you notice water around the appliance this is produced by the condensation of the moisture in the wood on lighting the fire This condensation will no longer appear when the appliance has been lit three or four times and has adapted to its flue If it does not disappear then check the flue draught length and diameter of the flue flue insulation airtightness and the humidity of the w...

Page 14: ...ce and reduces emissions Figure No 9 Double combustion air intake open Figure No 10 Double combustion air intake closed IMPORTANT The appliance is exposed to extreme changes in temperature and may as a result make noises when in operation These noises are a natural result of expansion contraction of the parts which make up the appliance Do not be alarmed by noises of this kind In order to obtain m...

Page 15: ...the stainless steel reinforcement In order to do this draw it towards the front of the appliance to release it from the vermiculite parts Figure No 11 First movement to release the reinforcement The vermiculite deflectors can then be extracted as shown Figure No 12 Extracting the vermiculite deflectors Extract the rest of the firebox vermiculite Figure No 13 Extract the rest of firebox vermiculite...

Page 16: ...ner for longer However the glass may get dirty the longer the appliance is used Special degreasing products designed for the purpose should be used to clean it Clean when the glass is cold and taking care not to apply the glass cleaner directly onto the glass as it could come into contact with the door seal cord and damage it 4 2 Maintenance of the chimney flue VERY IMPORTANT In order to avoid inc...

Page 17: ... continually burn chips carpentry scraps plywood pallets etc Cold flue Heat up the flue by burning a piece of paper in the firebox Smoke during burning The room is at low pressure In rooms with Controlled Mechanical Ventilation leave an outdoor window ajar until the fire is fully alight Too little wood loaded Load as recommended Loads notably smaller than those recommended lead to low smoke temper...

Page 18: ...Recer Vermiculita Trasera DCHA 1 6 5020000931 Ocean 600 Recer Cjto Registro 1º 1 7 502570000007 Pieza móvil registro secundario Ocean 1 8 5020000932 Ocean 600 Recer Refuerzo deflector vermiculita 1 9 502620000003 Cristal hogar Ocean 600 1 10 509020000042 Cordón Negro Ø13mm 3m 11 500000000510 Cordon plano pelos 8x2mm 2m 12 5040000904 Nickel Adour Parrilla hogar 1 13 5020000933 Ocean 600 Recer Vermi...

Page 19: ...DECLARATION OF PERFORMANCE 18 7 DECLARATION OF PERFORMANCE ...

Page 20: ...DECLARATION OF PERFORMANCE 19 7 ...

Page 21: ...CE MARK 20 8 CE MARK ...

Page 22: ......

Page 23: ......

Page 24: ...LACUNZA KALOR GROUP S A L Pol Ind Ibarrea s n 31800 Alsasua Navarra Spain Tel 00 34 948 56 35 11 Fax 00 34 948 56 35 05 e mail comercial lacunza net Website www lacunza net EDITION 0 ...

Reviews: