27
multimeter, and then regulate ±BUS voltages to 370±0.1V by using BUS regulation command.
(BUS voltage can be regulated about 0.1V every point by using BUS regulation command).
2. INV output voltage regulation: When the UPS run into the Inverter mode, measure the output
voltage with the multimeter, and regulate the output voltage to 230±0.2V by using output
voltage regulation command. (INV output voltage can be regulated about 0.2V every point by
using output voltage regulation command).
Notes:
1. Make sure the ground of the UPS connects to earth safely during parameter regulation.
2. New assembly UPS must be regulated.
3. UPS which have been replaced CNTL/PFC/INV must be regulated again.
4. All the commands use capital letters.
5. All the above parameter regulation cannot be accumulated.
6. All the regulation will be saved in the flash memory of the CNTL when UPS shutdown with
battery connected.
7.2.5 Quick Start
Before any detail check for UPS, please check the components listed in the following table. This action
could help you find problem quickly and make debug procedures go smoothly.
Note:
Make sure that the capacitor voltage is lower than the safety voltage before disassembling any
parts to do checking procedure.
10k R-PFC&INV Section
Circuit Block
Checked components
Component Type
Failure condition
DC FUSE
F4
Fuse
Open
AC FUSE
F2
Fuse
Open
Rectifier
Q17, Q18, Q21
SCR
A-K Short or open
R-PFC
D33, D35, D34, D36
Diode
Short or open
Q24, Q25
IGBT
C-E short or open
INV
D15, D16, D17, D18
Diode
Short or open
Q7, Q8, Q9, Q10
IGBT
C-E short or open
STS
Q13, Q14, Q20, Q31
SCR
A-K Short or open
SPS
F6
Fuse
Open
Q6, Q44
MOSFET
D-S short or open
D3, D4, D5, D6, D7, D8, D21
Power Diode
Short or open
U2, U3, U4, U5
Power IC
I-O short or open
U1
Power Control IC
Vcc short to GND
Others
Q1, Q2, Q11, Q12, Q29, Q30, Q32, Q43
MOSFET
D-S short or open
10k S&T PFC Section
Circuit Block
Checked components
Component Type
Failure condition
DC FUSE
F4,F5,F6,F7,F8
Fuse
Open
AC FUSE
F2,F3
Fuse
Open
Rectifier
Q24,Q25,Q26,Q44,Q45,Q46,Q49,Q58,Q59
SCR
A-K Short or open
PFC
D43,D44,D45,D49, D52, D53,D54,D58
Diode
Short or open
Q32, Q52,Q43,Q55
IGBT
C-E short or open
15k/20k PFC Section
Circuit Block
Checked components
Component Type
Failure condition
Rectifier
Q17,Q18,Q21,Q27,Q24,Q25,Q26,Q49,Q44,Q45,
Q46,Q58
SCR
A-K Short or open
Summary of Contents for G31 Series