EXHAUST PORT VENTILATION
NOTE:
In case oven equipped with canopy is installed under a commercial ventilation
hood, respect minimum distance “D” between canopy and commercial ventilation hood
D = “d” x 1.25 = 1.25 times canopy port diameter.
Appliance suitable for connection to a flue gas vent when used with draft hood (provided
as optional).
Appliance to be installed under a ventilation hood when draft hood is not provided
.
Refer to exhaust ports 1 (steam generator) and 2 (chamber) on the appropriate dimension
drawings. These ports must be vented to an exhaust flue by the Flue Diverter.
A ductwork connection must comply with all local and national codes for venting gas-fired
appliances. After sizing and positioning the collars secure them tightly to the exhaust ports.
Fit the flue diverter using 4 fixing screws for this purpose.
The oven can also be installed without the flue diverter under a commercial ventilation
hood (see Figure B).
When venting to an exhaust hood, the hood must be sized to the ventilation requirements of
the Oven/Steamer installed.
45
90028771rev00
Figure A
Figure B
Stack connection
pipe
Adaptor
Damper
Hood filter
Suction hood
Ducted
ceiling
1
-
2
-
3
-
4
-