TESTING GAS SUPPLY LINES AND BURNER CONTROLS
Refer to Figure 2-8, and open the main shut-off valve for the oven/steamer gas supply line.
Test the pipe joints for leaks with soap and water solution.
If you smell gas, turn off the main gas shut-off valve.
If no other inspections or tests are planned at this time, replace the right side access panel;
otherwise proceed to the next test. Do not leave manual gas valve open during initial installation
or burner control system servicing, until after the automatic gas valve has been tested.
TESTING THE AUTOMATIC GAS VALVE AND BURNER CONTROL SYSTEM
Test the automatic gas valve and burner control system during the initial installation Start-
Up Checks, or after servicing any components of the valve or system. If this testing is part of
initial installation or if gas line components have been altered, DO NOT TEST the automatic
gas valve and burner control system until the gas supply lines have passed the pressure test
procedure above.
If this test is part of the initial installation Start-Up Checks, perform checks 1 through 10
before starting this procedure.
Turn off electrical power to the unit by pressing the main push button.
Turn off the electrical power to the unit at the main power switch (Refer to figure 2-5,
Recommended Electrical Layout).
Turn the main manual gas valve to the OPEN position. Wait five minutes.
• If you smell gas, referto to Gas Leak Instruction.
• If you do not smell gas, continue this procedure.
Turn on the electrical power to the unit at the main power switch.
Install the access panel removed at step (4).
52
90028771rev00
3
-
4
-
5
-
6
-
1
-
2
-
3
-
4
-
5
-
6
-
Summary of Contents for Naboo Compact CBEN061
Page 2: ... 2 90028771rev00 ...
Page 20: ... 20 90028771rev00 INSTALLATION DIAGRAMS ...
Page 64: ... 64 90028771rev00 ...
Page 65: ... 65 90028771rev00 65 90028771rev00 ...
Page 66: ... 66 90028771rev00 66 90028771rev00 ...
Page 67: ......