Buttons
Description
Alarm has been set
Amber alarm
Amber alarm Selected
Red Alarm
Red Alarm Selected
Red alarms are used to indicate an abnormal system condition and is usually associated with the
shutdown of a component or the whole system. There is an audible alarm for this condition and
requires an action from the customer for the system to restart.
Amber alarms are warnings to indicate an abnormal system condition, but the system or components
are not shut down. There is no audible alarm for this condition.
For specific alarm conditions and troubleshooting information, refer to section
Settings Screen
Figure 44 Setting Menu
Setting Units
The units of measure for temperature and pressure can be selected in the Settings Menu. The options
available for temperature are
°
C/
°
F and for Pressure are Bar/Psi.
Choosing the Coolant
The coolant (Water/ Ethylene Glycol) can be chosen on the Settings Menu. The Ethylene Glycol
Percentage can be chosen once the EGW button is pressed. This selection limits the temperature set
point value that the customer can select. Below are the temperature range for different glycol
percentages. Note that selecting the correct coolant is the responsibility of the customer and should
match what is filled in the system by the customer. Selecting the wrong coolant may cause damage to
the equipment.
Water: 10
°
C to 40
°
C
10% Ethylene Glycol: 5
°
C to 40
°
C
20% Ethylene Glycol: 0
°
C to 40
°
C
30% Ethylene Glycol: -5
°
C to 40
°
C
40% Ethylene Glycol: -10
°
C to 40
°
C
Summary of Contents for Nextreme Series
Page 1: ...Nextreme Recirculating Chiller Specification and User Manual Part Number 387004848 ...
Page 17: ...17 Component Locations Figure 2 Isometric Views of Unit Figure 3 Top View ...
Page 18: ...18 Figure 4 Front View Figure 5 Rear View Figure 6 Side View ...
Page 39: ...39 Figure 25 Sensor Wiring Low Voltage ...
Page 40: ...40 Plumbing Refrigeration Diagram Figure 26 Plumbing and Refrigeration Diagram ...
Page 43: ...43 Figure 31 Pump Performance of NRC5000 with Cooling Fluids Water and 40 EG W ...
Page 60: ...60 PCFLT Returns FLT fault or NO FAULTS FOUND PCFLT C Clears Fault Returns FLT Faults Cleared ...
Page 69: ...69 Declaration of Conformity ...