28
Cleaning of Strainer
Fig. 12:
Locations of ball valve and strainer
1 Strainer cover
2 Ball valve
1)
Disconnect the unit from mains.
2)
Remove the side panel.
3)
Close the ball valve.
4)
Remove the strainer cover using a metric AF24 wrench.
5)
Take off the strainer and clean it. In case of damage the strainer must be replaced.
6)
Remount the strainer and screw on the cover.
7)
Re-open the ball valve.
8)
Should any coolant leak from the strainer the cover must be screwed on using a little more force.
9)
Remount the side panel.
10)
Start-up the unit for venting the cooling circuit (see page 22).
11)
Check the coolant level and refill, if required.
CAUTION
A small amount of coolant will leak from the pump.
Use a cloth or an appropriate vessel for absorption.
CAUTION
Risk of damage to the pump, if the unit is operated with a fully closed ball valve!
Never start the unit, when the ball valve is closed.
1
2
Summary of Contents for WL3004
Page 1: ...WL3004 Liquid to Air Cooling System Specification and User Manual Version 1 2 ...
Page 35: ...35 Addendum Flow scheme ...
Page 36: ...36 Wiring diagram ...
Page 37: ...37 ...