MODEL A39 "UNIVERSAL CHARGER"

The La Marche Model A39 "Universal Charger" is a microprocessor controlled SCR charger which has

adjustable output voltage, adjustable output current limit, and an adjustable charge timer.

The output voltage, output current, time left to charge, and error codes are displayed on a 1/2" high red

LED digital display.

The voltage range adjusts from 10% to 100% of the rated value, the current limit range from 5% to

100% of rated output current, and the charge timer range adjusts between 30 minutes to 99 hours in 30

minute increments.

The A39 may be used as a constant current charger where the open circuit voltage can be adjusted, or

as a constant voltage charger with a current limit mode.  The voltage characteristics in the constant

voltage mode are programmable by "dip

 switches for a  "flat

 1% regulation curve or a tapered charge

curve.

A  "select

 push-button changes the display function from amps, to volts, or to time.  These are displays

of actual unit conditions.

The "set

 mode is actuated by depressing the "select

 push-button and holding it in.  The toggle switch

then allows adjustment of voltage current limit, or timer hours up or down from the initial setting.

The initial voltage setting is derived from the actual battery voltage when the battery is connected.  The

current limit automatically defaults to 20% of the rated output and the charge timer defaults to 8 hours

on start up.

The Model A39 will "Auto" start upon connection to a battery and "Auto" stop when the charge cycle is

terminated by disconnection or a normal charge complete.

STANDARD FEATURES

*  Microprocessor Control

*  Auto Start/Stop Circuitry

*  Digital Display 1/2" Red LED (Amps, volts, amp

hours, elapsed time, error codes, voltage setting,

current setting, timer setting)

*  AC Breaker

*  LED Lights for "ON" charge, Charge complete,

Unit failure, Current limit

*  Automatic Surge Protection

*  Digitally adjustable current limit, output voltage,

and charge time

*  Output cables with lugs

*  Constant current mode

*  Single & Three Phase inputs

*  "Flat" 1% Regulation mode

*  Fault   mode  diagnostics

*  Tapered charge curve mode

* DC fuse (Standard)

*  Wide Current, voltage, & timer ranges

* DC Breaker (Optional)

* Reverse Polarity Protection

Summary of Contents for A39

Page 1: ... Page 1 of 8 A39 UNIVERSAL SCR CHARGER ECN DATE CPN35971 15349 03 05 02 14268 10 00 16816 6 05 14575 02 01 10400 9 96 106 BRADROCK DRIVE DES PLAINES IL 60018 1967 847 299 1188 FAX 847 299 3061 ISSUE DATE 6 90 INSTRUCTION DRAWING NUMBER P25 LA39 1 ...

Page 2: ...w a spark or flame in vicinity of a battery f Be extra cautious DO NOT drop metal onto a battery It might spark or short circuit the battery or cause an explosion g Remove personal metal items such as rings bracelets necklaces and watches when working with a battery A battery can produce a short circuit current high enough to weld these items causing severe burns h NEVER charge a frozen battery i ...

Page 3: ...e claim to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for handling Until the equipment is securely mounted care must be used to prevent the equipment from being accidentally tipped over NOMENCLATURE PLATES Each piece of La Marche Mfg Equipment shipped is identifie...

Page 4: ...ys of actual unit conditions The set mode is actuated by depressing the select push button and holding it in The toggle switch then allows adjustment of voltage current limit or timer hours up or down from the initial setting The initial voltage setting is derived from the actual battery voltage when the battery is connected The current limit automatically defaults to 20 of the rated output and th...

Page 5: ...t button to the Elapsed Time mode hold in on the push to select switch and use the adjust up down switch until the desired charge time is reached 6 The A39 will stay in current limit until the set voltage is reached Once the set voltage is reached the current will start to taper The A39 will run for the specified amount of time and then go to a Complete mode which is indicated by the complete ligh...

Page 6: ...A 123 printed circuit board D Check S2A 122 printed circuit board TO TROUBLESHOOT MODULES A Disconnect power transformer secondary wire from top connection of module B Disconnect positive wire from buss bar C Disconnect negative wire from buss bar D Disconnect 6 pin connector from terminal J3 on S2A 122 assembly E Measure resistance from top terminal of module to center buss bar must read high res...

Page 7: ...nel meters and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REPEAT ALL WITH THE ADDITION OF 1 Filter resonating capacitors and control relays should be replaced 10th Year REPEAT ALL WITH THE ADDITION OF except replacing capacitors and control relays they should be replaced every 7 years 1 Chec...

Page 8: ...f the purchaser elects not to return the equipment to the factory and wishes a factory service representative to make adjustments and or repairs at the equipment location La Marche s field service labor rates will apply A purchase order to cover the labor and transportation cost is required prior to the deployment of the service representative In accepting delivery of the equipment the purchaser a...