UPS Location
•
Allow at least 6 inches of free air on all vented surfaces for proper cooling
•
Allow sufficient clearance to open the front panel for servicing.
•
Do not operate this UPS in a closed-in area or restrict ventilation in any way.
•
Do not place UPS below battery.
•
Never allow battery electrolyte to drip on this UPS when reading the specific gravity or filling the battery.
•
Never place this UPS directly above a standard flooded battery. Gases from the battery will corrode and
damage equipment.
•
A sealed maintenance free or valve regulated lead acid (VRLA) battery may be placed below this equipment.
Check for Damages.
Prior to unpacking the product, note any damage to the shipping container and take pictures. Unpack the product
and inspect the exterior and interior of product for damage. If any damage is observed, take pictures and contact
the carrier immediately to file a damage claim. Contact La Marche for a Return Material Authorization number to
have the UPS sent back for evaluation and repair.
CAUTION:
Failure to properly file a claim for shipping damages, or provide a copy of the claim to La
Marche, may void warranty service for any physical damages reported for repair.
Returns for Service
Save the original shipping container. If the product needs to be returned for service, it should be packaged in its
original shipping container. If the original container is damaged/unavailable, make sure the product is packed
with at least three inches of shock-absorbing material to prevent shipping damage.
La Marche is not responsible
for damage caused by improper packaging of returned products.
Handling
Equipment can be very heavy with uneven distribution of weight. Use adequate manpower or equipment for
handling. Until the equipment is securely mounted, care must be used to prevent equipment from being accidently
tipped over or dropped.